Operational Information; Power On Check; Error Codes; Thermostat Troubleshooting - Carrier TOTALINE Gold P274-0200-C Installation, Start-Up, And Operating Instructions Manual

Residential non-programmable thermostat
Table of Contents

Advertisement

OPERATIONAL
INFORMATION
Five-Minute
Compressor
Time Guard -- This tim-
er
prevents the compressor
from starting unless it has been off
for at least 5 minutes. It can be defeated for 1 cycle by simulta-
neously pressing
the FAN mode button and the INCREASE
TEMPERATURE
button.
Fifteen-Minute
Cycle Timer -- This
timer
prevents
the stall of a heating or cooling cycle until at least 15 minutes
aller the last st;ut of the salne cycle. Its fimction is to assure that
equipment is not cycled more than 4 times per hc This timer is
defeated for 1 cycle when the desired temperatme
is manually
changed. It can also be defeated for 1 cycle by simultaneously
pressing the FAN mode button and file INCREASE
TEMPER-
ATURE button.
Fifteen-Minute
Staging
Timer
--
In multistage
heat-
ing or cooling,
this timer
prevents
any higher
stage
from
turning on until the preceding
stage has been on for 15 minutes.
This timer is defeated
if the temperature error is greater than
5 ° F (usually due to a lmge change in desiled temperature).
Three-Minute
Minimum
On Time
--
In normal op-
eration, when a stage turns on, it will not turn off for a minimum
of 3 minutes.
Heat/Cool
Set
Points
(Desired
Tempera-
tures)
--
A minimum diffelence
of 2 ° F is required between
heating and cooling set points. This is done by allowing
one
setting to "push" the other, to maintain this difference.
Auto Changeover
--
When the autochangeover
mode is
selected, a change from heat to cool (or vice versa) will not
occur until an opposite
mode demand has existed for 20 min-
utes. If the set point is changed, the 20-minute
requirement
is
deleted. Auto mode may be disabled.
Emergency
Heat Mode -- When thermostat is config-
ured
as a heat pump and Emergency
Heat mode is selected, all
Y signals are locked out and W becomes energized
upon a call
for heat.
Heat On and Cool On Icons
-- When
a heating or
cooling demand exists, the HEAT ON or COOL ON icon will
either remain on or flash. If flashing, the equipment
is tempo-
rarily prevented
from turning on by one of the timel_
(see
above). While the icon remains on without flashing, the equip-
ment is on.
Power On Check
-- When AC power is first applied, all
segments of file display are turned on for a few sec. Following
this, the temperature display indicates the model/configuration
via the following 2-digit code: AC -- 1-speed air conditioneL
HP --
l-speed heat pump, A2 -- 2-speed air conditioner,
H2-- 2-speed heat pump.
Error Codes
-- -- If the thermostat cannot properly read room temperature,
the display will indicate
-- (2 dashes) and all outputs
(except
the fan if on) will turn off. This is to plevent operation
of the
equipment if the thermostat has failed.
E2 -- If the AC line voltage drops below a minimum
(brown-
out) level, all outputs are turned off and file display indicates
E2. This condition will remain for 15 sec ;trier proper line volt-
age is restored. If the AC line voltage disappems
completely,
the display will immediately
go blank.
E3 -- If the thermostat
cannot propedy read outdoor tempera-
ture, and it is needed for proper operation
(heat pump system
and Option 8 is not set to OF), E3 will flash ;alternately with
room temperature.
See Table 3 for error code descriptions.
Table 3 -- Thermostat Troubleshooting
SYMPTOM
WHAT TO CHECK
Blank LCD
Check for 24 vac between R and C at terminal connections
or battery.
Temperature sensor reading out of range. Check sensor for damage. If recycling power
"--" (2 dashes) on temperature
display
does not clear display, thermostat should be replaced.
"E2" on temperature
display
Brownout condition or too low of voltage to thermostat.
Double check wiring and check for
24 vac between R and C. E2 will clear 15 sec after proper voltage is restored.
"E3" on temperature
display
The outdoor temperature
sensor is open, not connected,
or shorted.
After the selected number of hour of blower operation "FILTER" will display on LCD. This
"SERVICE FILTER"
on temperature
display
is to remind the home owner to "check" the filter. Press RESET FILTER button to clear
display and reset timer to 0.
Select COOL mode. Set desired temperature
to 10° F below room temperature.
Simulta-
neously press FAN and INCREASE TEMPERATURE
buttons to defeat timers. Check for
Cooling
will not come on
COOL ON icon and 24 vac at Y (first-stage) terminal. If present, thermostat
is okay and
_roblem is with equipment or wiring. If not present, replace thermostat.
Select HEAT mode. Set desired temperature to 10° F above room temperature. Simultaneously
3tess FAN and INCREASE TEMPERATURE
buttons to defeat timers. Check for HEAT ON and
Heating will not come on
24 vac at Y (first-stage)
terminal (with heat pump) or W/W1 (with air conditioner)
terminal. If
_resent, thermostat
is okay and problem is with equipment or wiring. If not present, replace
thermostat.