Combustion Air And Ventilation; Appliances In Unconfined Spaces; Appliances In Confined Spaces - Kenmore Elite 153.331010 Use & Care Manual

Hybrid gas water heater
Hide thumbs Also See for Elite 153.331010:
Table of Contents

Advertisement

COMBUSTION
AIR AND VENTILATION
A gas water heater cannot operate properly without the
correct amount of air for combustion.
Do not install in a
confined area such as a closet, unless you provide air as
shown in the "Facts to Consider About Location" section.
Never obstruct the flow of ventilation air. If you have any
doubts or questions at all, call your gas supplier. Failure to
provide the proper amount of combustion air can result in
a fire or explosion and cause death, serious bodily injury,
or property damage.
Breathing
Hazard - Carbon Monoxide
Gas
• Install water heater in accordance with
the instruction manual and NFPA54 or
CAN/CSA- B149.1
° To avoid injury,combustion and ventilation
air must be taken from outdoors.
• Do not place chemical vapor emitting
products near water heater.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
12" MAX.
(30.5 cm) --
100 sq in <
VENTILATION
(645 sq cm)
AIR
o
_NG
--
12" MAX.
(30.5 cm)
FRONT VIEW OF DOOR
REGTANGUI.AR]I 3" MIN.
MR DUCT
(7.6 cm)
AIR DUCT
FIGURE 10
If this water heater will be used in beauty shops, barber
shops, cleaning establishments,
or self-service laundries
with dry cleaning equipment, it is imperative that the water
heater(s) be installed so that all air for combustion and
ventilation is taken from outdoors.
Note: Vent length should be long enough that the outside
air will not freeze the water heater.
Propellants of aerosol sprays and volatile compounds,
(cleaners, chlorine based chemicals, refrigerants, etc.)in
addition to being highly flammable in many cases, will also
react to form corrosive hydrochloric acid when exposed to
the combustion products of the water heater. The results
can be hazardous, and also cause product failure.
APPLIANCES
IN UNCONFINED SPACES
UNCONFINED SPACE is space whose volume is not less
than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters
per kW) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with
the space in which the appliances are installed, through
openings not furnished with doors, are considered a part
of the unconfined space.
In unconfined
spaces
in buildings,
infiltration
may be
adequate to provide air for combustion,
ventilation and
dilution
of flue gases.
However,
in buildings
of tight
construction
(for example,
weather
stripping,
heavily
insulated, caulked, vapor barrier, etc.), additional air may
need to be provided
using the methods
described
in
"Appliances in Confined Space" that follows."
APPLIANCES
IN CONFINED SPACES
CONFINED
SPACE is a space whose volume is less
than 50 cubic feet per 1,000 Btu per hour (4.8m 3 per kW)
of the aggregate input rating of all appliances installed in
that space.
When drawing combustion air from inside a building to a
confined space, such a space should be provided with two
permanent openings. ONE WITHIN 12 in. (30cm) OF THE
ENCLOSURE TOPAND
ONE WITHIN 12 in. (30cm) OF
THE ENCLOSURE BOTTOM. Each opening should have
a free area of 1 square inch per 1000 Btu/hr (22 cm2/kW)
of the total input of all appliances in the enclosure, but not
less than 100 square in. (645 cm2).
If the confined space is within a building, air for combustion
and ventilation
must be obtained from outdoors. When
directly communicating with the outdoors or communicating
through vertical ducts, two permanent openings, located
in the above manner, should be provided. Each opening
should have a free area of not less than 1 square inch per
4000 Btu/hr (5.5 cm2/kW) of total input of all appliances in
the enclosure. If horizontal ducts are used, each opening
should have a free area of not less than 1 square inch per
2000 Btu/hr (11 cm2/kW) of the total input of all appliances
in the enclosure.
A. ALLAIR FROM INSIDE BUILDINGS: (See Figures 10
&11)
The confined space should be provided with two permanent
openings
communicating
directly
with an additional
room(s) of sufficient volume so that the combined volume
of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed in
the combined space should be considered in making this
determination. Each opening should have a minimum free
area of 1 square inch per 1,000 Btu per hour (22 cm2/kW)
of the total input rating of all gas utilization equipment in
the confined space, but not less than 100 square in. (645
cm2). One opening should commence within 12 in. (30cm)
of the top and one commencing within 12 in. (30cm) of the
bottom of the enclosures.
17

Advertisement

Table of Contents
loading

Table of Contents