5.4.1 Available Diagnostics

Revised Mar-2011
ControlWave Express Instruction Manual (CI-ControlWave Express)
Figure 5-9. WINDIAG Main Diagnostics Menu
Select the component to be tested. See Section 5.4.1 for a
3.
description of the tests. Enter any prompted parameters (slot #,
etc.). WINDIAG performs the diagnostics and displays pass/fail
results.
After performing all diagnostic testing, exit WINDIAG.
Set switches SW2-3 and SW2-8 on the CPU module to ON. The
4.
ControlWave Express should resume normal operation.
WINDIAG's Main Diagnostics Menu (see Figure 5-9) provides the
following diagnostic selections:
Option
CPU & Peripherals
Analog Output
High Speed Counter
Prom/Ram
Analog Input
Communications
Service & Troubleshooting
Tests
Checks the CPU/System Controller board except
for memory.
Checks the AO on the Process I/O board.
Checks HSCs on the Process I/O board and
Pulse Counter inputs on the CPU/System
Controller board.
Checks the SRAM and FLASH memory.
Checks AIs on the Process I/O board.
Checks serial communication ports COM1,