Download Print this page

Sigma K1000 Series Operation & Maintenance Manual

1, 2, 4 & 6 zone fire control panels

Advertisement

Quick Links

Sigma
K1000 Series 1, 2, 4 & 6 Zone
Fire Control Panels
Operation and Maintenance Manual
Man-1048
Issue 05 October 2009

Advertisement

loading
Need help?

Need help?

Do you have a question about the K1000 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Sigma K1000 Series

  • Page 1 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009...
  • Page 2: Table Of Contents

    Sigma Installation & Mains Supply Connection ............2 Connections To Detectors & Sounders..............3 K1002 PCB Layout (1 & 2 Zone), K1006 PCB Layout (4 & 6 Zone) ...... 4 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual...
  • Page 3 2.6 The mains fuse must only be replaced with a 2 amp fuse conforming to BS:4265. Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 2 of 10...
  • Page 4: Front Panel Indications - Continued

    Mains Failure Battery Disconnection. System Fuse Failure Total Power Failure Battery Fuse Failure Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 3 of 10...
  • Page 5 The common fire indicator will be illuminated if the panel is in an alarm condition or in an evacuate condition. Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 4 of 10...
  • Page 6: Internal Indicators

    6.1 The panel has an internal DIL Switch, which provides the following functions:- Six zone Sigma One zone Sigma Normal switch positions Normal switch positions Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 5 of 10...
  • Page 7: Terminal Functions - Continued

    10.2 All contacts are rated at 30V DC 1 Amp maximum and should under no circumstances be used to switch greater voltages or currents (see annex 3). Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 6 of 10...
  • Page 8: Typical Wiring Connections & Use Of Aux.24V Output

    24V output. ANNEXE 1 Typical wiring connections & use of Aux.24V output Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 7 of 10...
  • Page 9 ANNEXE 2 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10...
  • Page 10 Line continuity unit wiring. Diode bases are used. Removal of a detector indicates fault and detectors beyond the removed one remain operative. Connections to sounders. Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 9 of 10...
  • Page 11 K1002 PCB layout - 1 & 2 zone Sigma, fuse & option resistor locations K1006 PCB layout - 4 & 6 zone Sigma, fuse & option resistor locations Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 10 of 10...