Hitachi L300P Series Quick Reference Manual page 22

Three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Func.
Code
A020/
Multi-speed frequency setting
A220
A021
Multi-speed frequency settings
to
(for both motors)
A035
A038
Jog frequency setting
A039
Jog stop mode
• 00 Free-run stop, jogging disabled during
motor run
• 01 Controlled deceleration, jogging disabled
during motor run
• 02 DC braking to stop, jogging disabled
during motor run
• 03 Free-run stop, jogging always enabled
• 04 Controlled deceleration, jogging always
enabled
• 05 DC braking to stop, jogging always
enabled
A041/
Torque boost method selection
A241
• 00 Manual torque boost
• 01 Automatic torque boost
A042/
Manual torque boost value
A242
A043/
Manual torque boost frequency adjustment
A243
A044/
V/f characteristic curve selection
A244
• 00 V/f constant torque
• 01 V/f variable torque
• 02 V/f free-setting curve
A045
V/f gain setting
A051
DC braking enable
• 00 Disable
A052
DC braking frequency setting
A053
DC braking wait time
A054
DC braking force during deceleration
A055
DC braking time for deceleration
A056
DC braking / edge or level detection for [DB]
input
A057
DC braking force for starting
A058
DC braking time for starting
A059
DC braking carrier frequency setting
Name / Description
• 01 Enable
20
Default
Value
Set
–FE2/–FU2/
Value
–FR
0.00
0.00
1.00
00
00
1.0
5.0
00 / 01 / 00
100.
00
0.50
0.0
0.
0.0
01
0.
0.0
3.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents