Controlling Three NACs and One Door Holder With One Input

5.
Supervise the power wiring between the FCPS-24FS auxiliary 24 VDC output on TB4,
Terminals 9 & 10 with an EOL relay (P/N: EOLR-1).
6.
For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document #15384.
7.
IMPORTANT! When the power supply is programmed for both Selective Silence and Slave
Mode, TB4 Terminal 7 (IN+) must be jumpered to Terminal 9 (AUX+) and Terminal 8 (IN-)
must be jumpered to Terminal 10 (AUX-). The FACP will control the Selective Silence feature
with this configuration.
If the terminals are not jumpered as indicated, the horn portion of the horn/strobes will be
silenced at all times.
5.2 Controlling Three NACs and One Door Holder With One
Input
In this application, the power supply has been set as a master with synchronized outputs. All four
FCPS-24FS output circuits, three NACs and one door holder, can be controlled from one input such
as an addressable control module as illustrated in Figure 5.2. The control module can be powered
from the FCPS-24FS auxiliary 24 VDC power output (TB4, Terminals 9 & 10).
FCPS-24FS Series Instruction Manual — P/N 51883:H1 4/14/2011
SYNC SYNC
IN+
1
2
3
TB4
IN-
OUT+
OUT-
IN2+
4
5
6
7
Applications
IN2-
AUX+
AUX-
8
9
10
29