Electrical Installation Requirements; Junction Box Location - Amana AKED3060 Series Owner's Manual

Electric downdraft cooktop
Hide thumbs Also See for AKED3060 Series:
Table of Contents

Advertisement

6 inch ducting pieces
6 inch to 3¼ x 10 inch
transition = 5 equivalent
feet
6 inch to 3¼ x 10 inch
transition = 1 equivalent
foot
6 inch 90 degree elbow =
5 equivalent feet
6 inch 45 degree elbow =
2½ equivalent feet
6 inch wall cap
(Unrestricted) = 0
equivalent feet

Electrical Installation Requirements

Installation of this product must conform with local codes
or in the absences of local codes with the current
National Electric Code ANSI NFPA 70 or Canadian
Electrical Codes.
Cooktop requires a 3 wire 240 volt, 60 hertz, AC circuit
protected by a separate 30 amp circuit breaker or time
delay fuse. Ground cooktop using #10 gauge ground
wire attached to burner box.

Junction Box Location

Power supply enters cooktop in right, rear corner.
Junction box must be located within 30 inches of power
supply entry point. Locate junction box within shaded
area.
A—6¾ inches
B—Within 30 inches of power supply entry point
C—24 inches
D—Center line
8
A
B
D
C