INSTALLATION MANUAL
AIR CONDITIONER (SPLIT TYPE)
Indoor unit
42TSAA010
42TSAA013
Outdoor unit
38TSAA010
38TSAA013
R32
ENGLISH
ภาษาไทย
1144180109

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 42TSAA013 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 42TSAA013

  • Page 1 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) ภาษาไทย Indoor unit 42TSAA010 42TSAA013 Outdoor unit 38TSAA010 38TSAA013 1144180109...
  • Page 2: Table Of Contents

    สารบั ญ CONTENTS ¢้ Í ¤ÇÃÃÐÇÑ § à¾× è Í ¤ÇÒÁ»ÅÍ´ÀÑ Â PRECAUTIONS FOR SAFETY..........1 ..........1 ªÔ é ¹ Ê‹ Ç ¹ÍØ » ¡Ã³ à ÊÃÔ Á ACCESSORY PARTS............5 ..............5 INSTALLATION DIAGRAM OF INDOOR AND ¼Ñ § ¡ÒÃμÔ ´ μÑ é § μÑ Ç à¤Ãè × Í §ÀÒÂã¹áÅÐÀÒ¹͡ ........6 ■...
  • Page 3: Precautions For Safety

    PRECAUTIONS FOR SAFETY PRECAUTIONS FOR SAFETY Read the precautions in this manual carefully before This appliance is filled with R32. operating the unit. ■ Warning indications on the air conditioner unit Warning indication Description CAUTION CAUTION BURST HAZARD BURST HAZARD Open the service valves before the operation, Open the service valves before the operation,...
  • Page 4 DANGER • FOR USE BY QUALIFIED PERSONS ONLY. • TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. • CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
  • Page 5 • The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater). • Be aware that refrigerants may not contain an odour. • Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, flame, sparks, or other sources or ignition.
  • Page 6 CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. •...
  • Page 7: Accessory Parts

    ACCESSORY PARTS ACCESSORY PARTS Indoor Unit Part name Part name Installation plate × 1 Wireless remote control × 1 Remote control holder × 1 Battery × 2 Mounting screw × 6 Ultra Fresh filter × 1 Flat head wood screw × 2 Owner’s Manual ×...
  • Page 8: Installation Diagram Of Indoor And Outdoor Units

    • Use Ø8 mm or Ø10 mm anchor bolts and nuts. Refrigerant piping Liquid side : Ø6.35 mm Gas side : Ø9.52 mm (42TSAA010) each : Ø12.70 mm (42TSAA013) Pipe insulating material (polyethylene foam, 6 mm thick) For 42TSAA010 (polyethylene foam, 8 mm thick) For 42TSAA013 Putty, PVC tapes each...
  • Page 9: Indoor Unit

    • The location of the remote control should be determined as shown below. Thread Pipe hole Indoor unit Weight Mounting screw For 42TSAA013 (Side view) (Top view) Indoor unit When the installation plate is directly mounted on the wall Remote 1.
  • Page 10: Piping And Drain Hose Installation

    Left-hand connection with piping Piping and Drain Hose Installation • Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall Piping and drain hose forming surface, the indoor unit may unstably be set on the wall.
  • Page 11: Drainage

    2. Put water in the drain pan and make sure that the water is drained out of Drainage doors. 3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe. 1. Run the drain hose sloped downwards. Shield pipe NOTE •...
  • Page 12: Evacuating

    Tightening connection CAUTION Align the centers of the connecting pipes and tighten the flare nut as far as • KEEP IMPORTANT 7 POINTS FOR PIPING WORK. possible with your fingers. Then tighten the nut with a spanner and torque (1) Take away dust and moisture (inside of the connecting pipes). wrench as shown in the figure.
  • Page 13: Electrical Works

    ELECTRICAL WORKS ELECTRICAL WORKS Model 42TSAA010 42TSAA013 Power source 50Hz, 220V Single phase Maximum running current 5.10A 7.10A Circuit breaker rating Power supply cable H07RN-F or 60245 IEC66 (0.75 mm or more) H07RN-F or 60245 IEC66 (1.25 mm or more)
  • Page 14: Power Supply And Connecting Cable Connection

    Power Supply and Connecting Cable Connection Power Supply Input at Indoor Unit Terminal Block (Recommend) Indoor Unit Outdoor Unit Stripping length of the power Power supply cable Power supply cable connect to supply cable Terminal block (L N 1 2 ) Earth line Terminal block Earth line...
  • Page 15: Others

    OTHERS OTHERS Gas Leak Test Test Operation To switch the TEST RUN (COOL) mode, press [RESET] button for 10 seconds. (The beeper will make a short beep.) Check places for the indoor unit. OPERATION / RESET Button Check places for the outdoor unit.
  • Page 17 ข้ อ ควรระวั ง เพื ื ่ อ ความปลอดภั ย ข้ อ ควรระวั ง เพื ื ่ อ ความปลอดภั ย Í‹ Ò ¹¢้ Í ¤วÃÃÐวั § 㹤ู ‹ Á × Í ¹ี é Íุ ป ¡Ãณ์ ¹ ี é ถ ู ¡ àμÔ Á ´้ ว  R32 Í‹...
  • Page 18 ÍÑ ¹ μÃÒ ãª้ โ ´Âผู ้ ª í Ò ¹Òญ§Ò¹à·‹ Ò ¹ั é ¹ • ปิ ´ μั ว ¨‹ Ò Âä¿ËÅั ¡ ¡‹ Í ¹¡ÒÃปฏÔ º ั μ Ô § Ò¹·ี ่ à ¡ี ่  ว¢้ Í §¡ั º ä¿¿้ Ò ãË้ á ¹‹ ã ¨ว‹ Ò ä´้ ป ิ ´ ÊวÔ μ ª์ ä ¿ •...
  • Page 19 Êí Ò ËÃั º Ãุ ‹ ¹ R32 ãË้ ã ª้ · ‹ Í á¿Ã์ ¹ ั · áÅÐà¤Ã× ่ Í §Á× Í ·ี ่ ¡ í Ò Ë¹´äว้ ã Ë้ ã ª้ ¡ ั º R32 ¡ÒÃãª้ à кº • ·‹ Í (R22) á¿Ã์ ¹ ั · áÅÐà¤Ã× ่ Í §Á× Í ·ี ่ Á ี Í Âู ‹ á Å้ ว ÍÒ¨·í Ò ãË้ à ¡Ô ´ ¤วÒÁ´ั ¹ Êู § ผÔ ´ ป¡μÔ ã ¹ว§¨Ã ÊÒ÷í...
  • Page 20 ¢้ Í ¤ÇÃÃÐÇÑ § ถ้ Ò à¤Ã× ่ Í §ถู ¡ ¹é í Ò ËÃ× Í ¤วÒÁª× é ¹ ¡‹ Í ¹¡ÒÃμÔ ´ μั é § ÍÒ¨·í Ò ãË้ à ¡Ô ´ ä¿¿้ Ò Åั ´ ว§¨Ãä´้ Í‹ Ò à¡็ º à¤Ã× ่ Í § •...
  • Page 21 ชิ ้ น ส่ ว นอุ ป กรณ์ เ สริ ม ชิ ้ น ส่ ว นอุ ป กรณ์ เ สริ ม μÑ Ç à¤Ã× è Í §ÀÒÂã¹ หÁÒÂàÅ¢ ª× è Í ªÔ é ¹ Ê‹ Ç ¹ หÁÒÂàÅ¢ ª× è Í ªÔ é ¹ Ê‹ Ç ¹ á¼่...
  • Page 22 สำ า หรั บ รุ ่ น 42TSAA010 ช่ อ งระบายนำ ้ า (โฟมโพลี เ อธี ล ี น หนา 8 มม.) สำ า หรั บ รุ ่ น 42TSAA013 ปู น อุ ด และเทปไวนิ ล อย่ า งละชิ ้ น...
  • Page 23 ตั ว เครื ่ อ งภายใน ตุ ้ ม นำ ้ า หนั ก สกรู ย ึ ด สำ � หรั บ รุ ่ น 42TSAA013 (มุ ม มองด้ า นข้ า ง) (มุ ม มองด้ า นบน) ตั ว เครื ่ อ งภายใน...
  • Page 24 ¡ÒÃμ‹ Í ·‹ Í ÍÍ¡´้ Ò ¹ซ้ Ò Â ¡ÒÃμÔ ´ μÑ é § ·‹ Í ¹ํ é Ò ·Ô é § áÅз‹ Í Ê‹ § • ดั ด ท่ อ ต่ อ ให้ ห ่ า งจากผนั ง 43 มม. ถ้ า ดั ด ท่ อ ต่ อ มากกว่ า 43 มม. อาจทำ า ให้ ต ั ว ¡ÒÃÇÒ§·‹...
  • Page 25 2. ทดลองใส่ น ำ ้ า ในถาดรั บ นำ ้ า ทิ ้ ง เพื ่ อ ทดสอบการระบายของนำ ้ า ออกสู ่ ภ ายนอก ¡ÒÃÃкÒ¹ํ é Ò 3. เมื ่ อ ต่ อ ท่ อ ต่ อ นำ ้ า ทิ ้ ง หุ ้ ม ส่ ว นเชื ่ อ มต่ อ ท่ อ ต่ อ นำ ้ า ทิ ้ ง ด้ ว ยฉนวนหุ ้ ม ท่ อ ฉนวนหุ...
  • Page 26 ¡ÒÃ¢Ñ ¹ ṋ ¹ ¢้ Í μ‹ Í ¢้ Í ¤ÇÃÃÐÇÑ § จั ด ให้ ท ่ อ ที ่ เ ชื ่ อ มอยู ่ ก ึ ่ ง กลาง และขั น แฟร์ น ั ท ให้ แ น่ น ด้ ว ยนิ ้ ว จากนั ้ น ขั น แป้ น เกลี ย ว 7 จØ...
  • Page 27: Μñ Ç À¤Ã× È Í §Àòâã¹

    การทำ า งานเกี ่ ย วกั บ ไฟฟ้ า การทำ า งานเกี ่ ย วกั บ ไฟฟ้ า ÃØ ‹ ¹ 42TSAA010 42TSAA013 แหล่ ง จ่ า ยไฟฟ้ า 50Hz, 220V 1 เฟส กระแสไฟฟ้ า สู ง สุ ด 5.10A 7.10A...
  • Page 28 áหÅ‹ § จ‹ Ò Âä¿áÅСÒÃàª× è Í Áμ‹ Í ÊÒÂàª× è Í Áμ‹ Í ¡ํ Ò ÅÑ § ¡ÃÐáÊä¿¿้ Ò ¢Í§áหÅ‹ § จ‹ Ò Âä¿·Õ è º Å็ Í ¤¢Ñ é Ç μ‹ Í ¢Í§μÑ Ç à¤Ã× è Í §ÀÒÂã¹ (á¹Ð¹ํ Ò ) μÑ...