Control Panels Non Combination & Combination Dual Control Duplex Instruction Manual This manual contains important safety information and must be carefully read in its entirety and understood prior to installation by all personnel who install, operate and/or maintain this product. Manual No.
WARRANTY Quincy Compressor control panels and related parts are warrantied for a period of one year in service, provided the panels and related parts are sold with or used in conjunction with existing Quincy Compressor compressor models. A 90 day in-service warranty applies to all other situations.
At Quincy Compressor safety is not only a primary concern, but a faithfully performed practice. Beginning with the design stage, safety is built into all Quincy compressors. It is the intention of this manual to pass along the “safety first” concept to you by providing safety precautions throughout its pages.
Page 5
1910.134 or FDA 21 CFR 178.3570 or NFPA 99 regulations. Failure to do so may cause severe injury or death. The owner, lessor or operator of any compressor unit manufactured by Quincy Compressor is hereby warned that failure to observe the safety precautions and procedures outlined in this manual may result in serious personal injury, damage to property, and may void your warranty.
Page 6
Quincy Compressor neither states as fact, nor in any way implies that the above list of safety precautions is an all inclusive list, the observance of which will prevent all damage to property or injury to personnel. Every effort has been taken to ensure that complete and correct instructions have been included in this manual.
SECTION 2 CONTROL PANEL DYNAMICS Description & Application Quincy Compressor control panels are designed to control the operation of two separate air compressors feeding into LED Indicators one tank. These control panels provide the ability to define a starting sequence in which the compressors operate, and/ or manually disable one or both compressors.
CONTINUOUS RUN mode cannot satisfy the demand, the other compressor (set to run in the START / STOP mode) will start and run until the demand is satisfied. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Lead cut-in and cut-out setting or PS1 Lead pressure switch settings. Lead designation automatically alternates after AUTO demand for compressed air is satisfied. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Unit of measure for temperature in degrees Celsius Alarm Fault Shutdown Conditions Quincy Compressor duplex control panels are capable of receiving and process- ing signals from sensors installed on the compressor unit that detect motor overload, high air temperature, low oil level or low oil pressure conditions.
Discharge Line Unloader Solenoid Valves (SV3 & SV4) A solenoid valve for compressor units that are equipped with Start / Stop con- trol and plain head(s) on the basic compressor (excludes QR-25 models with hydraulic unloaders). It provides loadless starting by unloading the discharge line when the system air pressure reaches the CUTOT setting, or the Lead pressure switch opens.
Pressure Switch (Digital Pressure Sensor) A pressure switch sends a digital signal to the I/O board and is used instead of a pressure transducer when retrofitting a control panel on a Quincy com- pressor unit already in service. I/O Board Jumper The I/O board is equipped with a feature that allows the compressor to be configured at the factory to satisfy the customer’s needs.
Overload relays are designed to protect the motor from damage due to motor overload. If the overload relay trips persistently, DO CAUTION ! NOT CONTINUE TO PRESS THE RESET BUTTON OR INCREASE THE OVERLOAD SETTING! Contact your local Quincy distributor for assistance. Electrical Specifications Enclosure Type...
2 Discharge Unload Solenoid Valves: 120VAC @ 40VA sealed (used on units equipped with Start / Stop control only and excluding QR-25 models) Relay Outputs 2 Alarms: (common for Low Oil, Motor Overload and High Discharge Air Temperature): single pole-double throw dry contact.
“ON” to start the compressor. Setting Control Parameters Quincy Compressor control panels feature adjustable control parameters which allow the user to customize the control system for specific applications. Refer to the chart below for a listing of control parameters, default settings, setting ranges and accessibility of parameters.
Page 16
Never exceed 300 PSI cut-out setting. Contact your local Quincy Compressor distributor for assistance. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
ON switch knob to “ON” to start the compressor. FOR 3 SEC. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
ON switch knob to “ON” to start the compressor. MODE PRESS EITHER FOR 3 SEC. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SEC. ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SEC. ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SEC. ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
MODE 1 (Compressor 1) & MODE 2 (Compressor 2) Start / Stop (STSTP) or Continuous Run (CORUN) Modes of Operation Quincy Compressor duplex control panels are factory set and deliv- ered in the Start / Stop mode of operation (an I/O board jumper is not provided).
/ ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SEC. ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SELECT button for 3 seconds, or turn either OFF / NAVIGATE TO VARIOUS SELECT ON switch knob to “ON” to start the compressor. OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SEC. ON switch knob to “ON” to start the compressor. NAVIGATE TO VARIOUS SELECT OTHER PARAMETERS OFF / ON TURN TO “ON” TO START COMPRESSOR Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
If there are any questions re- garding any part of the instructions, please call your local Quincy distributor. Never assume a compressor is safe to work on just because it is not WARNING ! operating.
Page 28
After the first eight hours, monitor the compressor at least once every eight hours. If the digital display indicates any type of alarm or fault condition, refer to SECTION 6, TROUBLESHOOTING for corrective action. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Step 5 Wait for the unit to cool before starting to service. (Temperatures of 125°F can burn skin. Some surface temperatures exceed 350°F when the compressor is operating.) Pressure Switch Adjustment Pressure switches provided by Quincy Compressor are preset at the factory ELECTRICAL CONTACTS and usually do not require adjustment.
4. Thermocouple temperature sensor or pressure transducer ALRM” contacts actuates on I/O board. wired to I/O board incorrectly. 5. Turn disconnect switches & OFF/ON switches to “”ON”” position to reset. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 31
4. Replace defective pressure switch(es). contact is closed). ALRM” contacts actuate on I/O board. 5. Turn disconnect switches & OFF/ON switches to “”ON”” position to reset. Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
SECTION 7 REFERENCE INFORMATION Component Drawings Single Power Source with Control Power Transformer Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 33
Harness, Control, Duplex Single-Power with CPT 2023700800 Harness Control, Duplex Single Power 120V 2023700801 Overload Relay, Class-10 Bi-Metallic 2024000800 Flatwasher, Zinc, 1.50 O.D. x .81 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 34
Single Power Source 120 VAC Single Phase Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 35
Harness, Control, Duplex Single-Power with CPT 2023700800 Harness Control, Duplex Single Power 120V 2023700801 Overload Relay, Class-10 Bi-Metallic 2024000800 Flatwasher, Zinc, 1.50 O.D. x .81 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 36
Non-Combination Dual Power Source with Control Power Transformer Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 37
Harness, Control, Duplex with CPT 2023700804 Harness, Control, Dual Power 120V 2023700805 Jumper, I/O Board 2024000800 Flatwasher, Zinc, 1.50 O.D. x .80 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 38
Non-Combination Dual Power Source 120 VAC Single Phase Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 39
Harness, Control, Duplex with CPT 2023700804 Harness, Control, Dual Power 120V 2023700805 Jumper, I/O Board 2024000800 Flatwasher, Zinc, 1.50 O.D. x .80 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 40
Combination Fused with Control Power Transformer Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 41
Harness, Control, Duplex, Combination Fused with CPT 2023700806 Harness, Control, Duplex, Combination Fused 120VAC 2023700807 Jumper, I/O Board 202400800 Flatwasher, Zinc, 1.50 O.D. x .80 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 42
Combination Fused 120 VAC Single Phase Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 43
Harness, Control, Duplex, Combination Fused with CPT 2023700806 Harness, Control, Duplex, Combination Fused 120VAC 2023700807 Jumper, I/O Board 202400800 Flatwasher, Zinc, 1.50 O.D. x .80 I.D. 110428N075 *Contact Distributor Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Never exceed 300 PSI cut-out setting. Contact your local Quincy Compressor distributor for assistance. Model QR 210 QR 210 QR 210 QR 310 QR 310 QR 310 QR 325 QR 325 Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 45
QR 310HP QR 310HP QR 310HP QR 325HP QR 325HP QR 340HP QR 350HP QR 350HP QR 370HP QR 370HP QR 390HP QR 5120HP QR 5120HP Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Combination Fused Duplex 1 Phase w/ CPT 2 of 4 2022000105 Combination Fused Duplex 1-Phase 120 VAC 3 of 4 Combination Fused Duplex Optional Equipment 4 of 4 *CPT = 120V Control Power Transformer Duplex Control Panel Quincy Compressor 2022201100, June 2012 3501 Wismann Lane, Quincy IL - 62305-3116...
Page 61
ENVIROMENTAL AND OSHA REQUIREMENTS: At the time of Seller shall in no event be liable for delays caused by fires, acts of God, shipment of the equipment from the factory, Quincy Compressor / Ortman strikes, labor difficulties, acts of governmental or military authorities, de-...