10.4 Parallel System Setting
The parallel setting page can be visited in the following steps in the screen:
USER->1. SETUP->PASSORD CHECK->15.parallel
10.4.0 Setting
Interface
Parallel.
1.NUM.
2.MASTER/SLAVER
3.ADDRESS
4.COMMON BAT
5.COMMON CT
6.PHASE A/B/C
7.DISCHARGE CURR
8.CHARGE CURR
9.PARALLEL EN
10.4.1 Parallel Error information
Interface
ERROR NO.
11:parallel fail
This interface shows parallel setting.
1.
Total numbers of the inverters.
2.
In a parallel system,the master unit broadcasts the
bms and other information to the slavers. Make
sure only one unit is configued as master.
3.
Local unit address(1-8).
4.
Common battery or independent battery.
5.
Common CT Enable
6.
Local phase of unit for three-phase installation.
(reserved function)
7.
DISCHARGE CURR, Total battery discharge current
command, only be settable in master unit in
parallel mode.
8.
CHARGE CURR, Total battery charge current
command, only be settable in master unit in
parallel mode.
9.
PARALLEL EN,Enable/Disable the parallel function
A parallell warning may occur because of the following reasons:
1. Wrong setup of the parallel num.
2. Wrong inter-unit parallel communication cable.
3. Wrong setup of the unit address.