Page 1
OPzV-Technical Manual VRLA Tubular Gel Battery Rm.405,Tower C,Huahan Building,No.16Langshan Rd.,North High-tech Park, Nanshan District,Shenzhen,518057,China Tel:+86-755-3398 1668 Fax:+86-755-8347 5180 E-mail:sales@ritarpower.com Http:www.ritarpower.com CHINA RITAR POWER CO RP.
Page 2
(channels for oxygen recombination). During the China Ritar Power Corp.(Ritar) is a Chinese Sealed Lead Acid(SLA) battery company listed on later period of charging, the oxygen generated by the positive reaches the negative through U.S.
Page 3
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 5. Battery Structure Features 6.Product Advantages ● Environment friendly, little precipitation of acid mist 1.Battery Structure & Plate Design ● Wide operating temperature range and stable performance in low/high temperature ● Excellent performance in constant discharge power ●...
Page 4
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 8. Product Parameters and Drawings 3.Conductance, Internal Resistance and Short Circuit Current The OPzV battery’s conductance and internal resistance decrease with the capacity 1.OPzV Battery Parameters increasing. They are dynamic parameters instead of linear ones and change with Dimension temperature, SOC(state of charge) and discharge state.
Page 5
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 9.Technical Parameters Final Voltage at 1.83V per cell @ 25℃ 1, Constant Current Discharge Characteristics: Amps Final Voltage at 1.90V per cell @ 25℃ Model No. 30' 126.0 96.00 64.00 47.14 38.00 32.43...
Page 6
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) Final Voltage at 1.75V per cell @ 25℃ Final Voltage at 1.65V per cell @ 25℃ Model No. 30' Model No. 30' 156.0 111.4 69.40 50.44 39.40 34.00 30.60 23.67 20.40 177.4 122.2...
Page 7
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 2.Constant Power Discharge Characteristics: Watts Final Voltage at 1.90V per cell @ 25℃ Final Voltage at 1.83V per cell @ 25℃ Model No. 30' Model No. 30' 188.3 149.7 106.3 80.80 66.93 58.20...
Page 8
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) Final Voltage at 1.75V per cell @ 25℃ Final Voltage at 1.65V per cell @ 25℃ Model No. 30' Model No. 30' 275.2 197.6 128.0 93.87 76.38 66.40 59.80 46.37 40.74 300.1 208.4...
Page 9
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 10.Battery Characteristic Curves & Diagrams 3. Technical Data fot Solar Power/Wind Applications 3.1 Technical Data 1.Charge Characteristic Curve Max. Charge Current: ≦ 0.2 C10 A Charge Characteristics(25 °C ) Max. Charge Voltage: ≦ 2.45V per Cell...
Page 10
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 4. Discharge Characteristic Curve 7.Shock Discharge Characteristics after 0.5 hour Continuous Discharge U(V) U c h ( V ) 2 . 2 2 . 0 0.2C 0.15C 0.1C 0.25C 0.4C 0.55C 0.7C 0.8C...
Page 11
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 10.Cycle Life Characteristics 13.Cyclic Life Vs. Depth of Discharge (%DOD) 115% 80%DOD 110% 105% 100% 100%DOD 120 240 360 480 600 720 840 960 1080 1200 1320 1440 1560 1680 Equalizing Charge Cycles Depth of Discharge (%DOD) 11.High Temperature Accelerated Life Test at 60℃...
Page 12
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) Tightening Torque 11.Battery Installation & Maintenance Application Tightening Torque Value 1.Unpackaging and Inspection 6.5N*m ☆ Transportation: 9.0N*m 12.0N*m Do not press or pull the battery top and terminals to prevent damages to terminals and cracking in sealed part.
Page 13
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) Inspect the battery case, Please check the reason of 4.2 Charge lid to check wether there The appearance is the unusual appearance; is leakage, blow-up, or normal and if it affects the normal...
Page 14
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 2) OPzV2-800/48V Single-floor Vertical Installation Rack 3) Yearly Inspection Item Content Benchmark Maintenance If it is lower than the benchmark value, please Cut off the AC power and Verification discharge the battery bank The battery voltage discharge with load;...
Page 15
OPzV Series(Tubular Gel Battery) OPzV Series(Tubular Gel Battery) 5) OPzV2-200/48V ~ OPzV-300/48V Double-floor Vertical Installation Rack 4) OPzV2-2000/48V ~ OPzV-3000/48V Single-floor Vertical Installation Rack 2nd Floor 1st Floor OPzV-2000V/48V OPzV-3000V/48V Model 2894 2850 OPzV-200V/48V OPzV-300V/48V Model 1060...
Need help?
Do you have a question about the OPZV2-600 and is the answer not in the manual?
Questions and answers