Air For Combustion And Ventilation; Installation; Check Gas Type - Desa HFVMR18 Owner's Operation And Installation Manual

Desa owner's operation and installation manual natural gas log vented decorative appliances hfvmr18, hfvmr24
Table of Contents

Advertisement

VENTED NATURAL GAS LOGS
AIR FOR
COMBUSTION AND
VENTILATION
WARNING: This appliance
shall not be installed in a con-
fined space or unusually tight
construction unless provisions
are provided for adequate com-
bustion and ventilation air. Read
the following instructions to in-
sure proper fresh air for this and
other fuel-burning appliances in
your home.
Today's homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.
While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

INSTALLATION

CAUTION: Do not remove the
metal data plates attached to the
burner pan. The data plates contain
important warranty information.
WARNING: Before installing
in a solid fuel burning fireplace,
the chimney flue and firebox must
be cleaned of soot, creosote,
ashes, and loose paint by a quali-
fied chimney cleaner. Creosote
will ignite if highly heated. A dirty
chimney flue may create and dis-
tribute soot within the house. In-
spect chimney flue for damage.
NOTICE: Installation, service, and
repair of this appliance must be
performed by a qualified installer,
service agency, company or gas
supplier experienced with this
type of gas appliance. Only fac-
tory authorized components listed
in these instructions may be used
in
accordance
manufacturer's instructions and
all codes and requirements of the
authority having jurisdiction. Any
modifications to this kit, or use of
unauthorized components or ac-
cessory items will void the
manufacturer's warranty, and may
result in a hazardous condition.
FLUE OPENING
SPECIFICATIONS
Note: This vented appliance must be in-
stalled only in a solid-fuel burning fireplace
with a working flue and constructed of non-
combustible material.
The charts in Figure 2 indicate technical
information regarding the installation of
your gas log set. Please make sure that all of
the specifications shown are applicable be-
fore installation is attempted.
The fireplace must include a working flue
and venting system with the minimum open-
ings shown in the Figure 2.
MODEL
DESCRIPTION
HFVMR18 18" Multi-Side
HFVMR24 24" Multi-Side
MINIMUM FIREBOX SIZES
LOG FRONT
BACK
SIZE WIDTH* WIDTH** DEPTH HEIGHT
18"
28"
28"
24"
29
3
/
"
29
3
/
4
4
* Add 6" if safety valve/pilot is used
**At depth indicated
BURNER ORIFICE
LOG
NATURAL
PROPANE/LP
SIZE
IN.
NUM.
18"
.111
34
24"
.129
30
Figure 2 - Technical Information Charts
4

CHECK GAS TYPE

Use only natural gas. If your gas supply is not
natural gas, you must install ON/OFF Safety
Valve/Pilot Kit (see Accessories, page 13).
Call dealer where you bought log set.
If the fireplace does not have a gas supply
shut-off valve, one must be installed.
with
the
VENTING SPECIFICATIONS
FOR INSTALLATION
The fireplace chimney flue and vent must be
drafting properly. To check the vent for
proper drafting: Light a tightly rolled news-
paper on one end and place it at the inside
front edge of the fireplace. Observe the
smoke and be sure the vent is properly
drawing it up the chimney. If the smoke
spills out into the room, extinguish the flame
and remove any obstruction until proper
venting is achieved.
The chimney flue must remain open a mini-
mum of 3" at all times during the operation
of this log set.
Btu Input
Btu Input
Natural Gas
Propane Gas
55,000
65,000
16"
18"
"
16"
18"
IN.
NUM.
.073
49
.086
44
Minimum
Vent Opening
45,000
8" dia.
55,000
8" dia.
FUEL INLET PRESSURE
SPECIFICATIONS (W.C.)
Min.
Max.
NG
5.5"
10.5"
LP
11"
13"
901915

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hfvmr24Comfort glow rga 2-72

Table of Contents

Save Article as PDF