Endress+Hauser PROFIBUS PA Micropilot FMR54 Brief Operating Instructions
Endress+Hauser PROFIBUS PA Micropilot FMR54 Brief Operating Instructions

Endress+Hauser PROFIBUS PA Micropilot FMR54 Brief Operating Instructions

Free space radar

Advertisement

Quick Links

KA01130F/00/EN/04.22-00
71575731
2022-08-01
Products
Brief Operating Instructions
Micropilot FMR53, FMR54
PROFIBUS PA
Free space radar
These Instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Detailed information about the device can be found in the
Operating Instructions and the other documentation:
Available for all device versions via:
• Internet:
www.endress.com/deviceviewer
• Smart phone/tablet: Endress+Hauser Operations App
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PROFIBUS PA Micropilot FMR54 and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser PROFIBUS PA Micropilot FMR54

  • Page 1 Operating Instructions pertaining to the device. Detailed information about the device can be found in the Operating Instructions and the other documentation: Available for all device versions via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App...
  • Page 2: Associated Documentation

    Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 About this document Symbols used 2.1.1 Safety symbols DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
  • Page 3 Symbols for certain types of information and graphics  Permitted Procedures, processes or actions that are permitted  Forbidden Procedures, processes or actions that are forbidden  Tip Indicates additional information Reference to documentation Reference to graphic Notice or individual step to be observed Endress+Hauser...
  • Page 4: Basic Safety Instructions

    To ensure that the measuring device remains in proper condition for the operation time: ‣ Use the measuring device only for media to which the process-wetted materials are sufficiently resistant. ‣ Observe the limit values in the "Technical data". Endress+Hauser...
  • Page 5: Workplace Safety

    Clarification in the case of borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
  • Page 6: Incoming Acceptance And Product Identification

    • Does the data on the nameplate match the order specifications on the delivery note? • Is the DVD with the operating tool present? If required (see nameplate), have the Safety Instructions (XA) been provided? If one of these conditions is not met, please contact your Endress+Hauser sales office. Storage and transport 4.2.1 Storage conditions •...
  • Page 7: Mounting Location

    15 cm (5.91 in) to the tank wall. Use of a weather protection cover; protection from direct sunlight or rain Installation in the center, interference can cause signal loss Do not install above the filling curtain Endress+Hauser...
  • Page 8 Micropilot FMR53, FMR54 PROFIBUS PA Orientation Internal vessel fittings α A0018944 Avoid the location of internal fittings (limit switches, temperature sensors, struts, vacuum rings, heating coils, baffles etc.) inside the signal beam. Take into account the beam angle. Avoiding interference echoes α A0016890 Endress+Hauser...
  • Page 9: Beam Angle

    6 m (20 ft) 2.44 m (8 ft) 9 m (30 ft) 3.66 m (12 ft) 12 m (39 ft) 4.88 m (16 ft) 15 m (49 ft) 6.1 m (20 ft) 20 m (66 ft) 8.14 m (27 ft) Endress+Hauser...
  • Page 10 • Align the antenna perpendicular to the product surface. • A marking is provided on the flange (at a point between the flange holes) or the gland to aid the alignment. This marking must be aligned towards the tank wall as much as possible. Endress+Hauser...
  • Page 11 Micropilot FMR53, FMR54 PROFIBUS PA Mounting 90° 90° 90° 90° 90° 90° 90° 90° 90° 90° A0018974 Depending on the device version the marking may be a circle or two parallel lines. Endress+Hauser...
  • Page 12 Information concerning threaded connections • Tighten by the hexagonal nut only. • Tool: open-ended wrench 55 mm • Maximum permissible torque: • Thread PVDF: 35 Nm (26 lbf ft) • Thread 316L: 60 Nm (44 lbf ft) Endress+Hauser...
  • Page 13: Mounting Cladded Flanges

    60 to 90 Nm NPS 8" Cl.150 115 to 170 Nm NPS 8" Cl.300 90 to 135 Nm 10K 50A 40 to 60 Nm 10K 80A 25 to 35 Nm 10K 100A 35 to 55 Nm 10K 150A 75 to 115 Nm Endress+Hauser...
  • Page 14 Depending on the device version the marking may be a circle or two parallel lines. Information concerning nozzles The horn antenna should project out of the nozzle; if necessary, select the version with antenna extension 100 to 400 mm (4 to 16 in) (accessory). Endress+Hauser...
  • Page 15 • Do not install any fittings or attachments between the antenna and the tank that could reflect the signal. Suitable thickness of the tank ceiling: Penetrated material PTFE Plexiglass ε Optimum thickness 16 mm (0.65 in) 17 mm (0.68 in) 16 mm (0.65 in) 14 mm (0.56 in) Endress+Hauser...
  • Page 16: Container With Heat Insulation

    350° 8 mm 8 mm A0032242 Unscrew the securing screw using an open-ended wrench. Rotate the housing in the desired direction. Tighten the securing screw (1.5 Nm for plastic housing; 2.5 Nm for aluminum or stainless steel housing). Endress+Hauser...
  • Page 17: Turning The Display

    Turn the display module to the desired position: Max. 8 × 45 ° in each direction. Feed the coiled cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment until it engages. Endress+Hauser...
  • Page 18: Electrical Connection

    Turn the securing clamp 90 ° in the clockwise direction and, using an Allen key (3 mm), tighten the screw of the securing clamp on the electronics compartment cover with 2.5 Nm. Electrical connection Connecting requirements 6.1.1 Terminal assignment Endress+Hauser...
  • Page 19 Cable screen; observe cable specification Connection PROFIBUS PA / FOUNDATION Fieldbus Measuring device Switch output (open collector) 6.1.2 Device plug In the case of the device versions with a plug, the housing does not need to be opened to connect the signal cable. Endress+Hauser...
  • Page 20 • Ex ia + Ex d(ia) / IS + XP Feature 020 in the product structure Feature 010 in the product structure Input voltages up to 35 V do not damage the device. Polarity-dependent FISCO/FNICO compliant according to IEC 60079-27 Endress+Hauser...
  • Page 21: Connecting The Device

    Loosen the screw of the securing clamp of the connection compartment cover using an Allen key (3 mm) and turn the clamp 90 ° counterclockwise. Unscrew the connection compartment cover and check the cover seal; replace it if necessary. 6.2.2 Connecting A0036418  7 Engineering unit: mm (in) Endress+Hauser...
  • Page 22  8 Engineering unit: mm (in) To remove the cable from the terminal again: Using a flat-blade screwdriver ≤ 3 mm, press down on the slot between the two terminal holes Simultaneously pull the cable end out of the terminal. Endress+Hauser...
  • Page 23: Integration Into A Profibus Network

    Overview of device master file (GSD) Manufacturer ID 17 (0x11) Ident number 0x1559 Profile version 3.02 GSD file Information and files available at: • www.endress.com GSD file version • www.profibus.org Setting the device address A0015686  9 Address switch in the connection compartment Endress+Hauser...
  • Page 24: Hardware Addressing

    The device restarts automatically and reports the current address (factory setting: 126). Configuring the address via the operating menu: Setup → Device address A0015903  11 Example of software addressing; switch 8 is set to the "ON" position; the address is defined in the operating menu (Setup → Device address). Endress+Hauser...
  • Page 25: Operation Options

    Micropilot FMR53, FMR54 PROFIBUS PA Operation options Operation options The device can be operated as follows: • Operation via operating menu (display) • DeviceCare / FieldCare, see Operating Instructions • SmartBlue (app), Bluetooth (optional), see Operating Instructions A0033202  12 Download link Endress+Hauser...
  • Page 26: Structure And Function Of The Operating Menu

    Visualization of a parameter (here: parameter with picklist) 3.1 Header containing parameter name and error symbol (if an error is active) 3.2 Picklist;  marks the current parameter value. Input matrix for numbers Input matrix for alphanumeric and special characters Endress+Hauser...
  • Page 27 • If present, opens the help text for the function of the parameter. • In a text and numeric editor: Pressing the key briefly: • Opens the selected group. • Carries out the selected action. • Carries out the selected action. Endress+Hauser...
  • Page 28: Opening The Context Menu

     The context menu is closed and the operational display appears. Calling up the menu via the context menu Open the context menu. Press  to navigate to the desired menu. Press  to confirm the selection.  The selected menu opens. Endress+Hauser...
  • Page 29: Operating Menu

    PROFIBUS PA has been defined. Disabling write protection If the device is write-protected, it must first be unlocked, see Operating Instructions. BA01126F - Operating Instructions, FMR53/FMR54, PROFIBUS PA Setting the operating language Factory setting: English or ordered local language Endress+Hauser...
  • Page 30 Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1 Sprache Deutsch Betrieb Setup A0029420  15 Taking the example of the local display Endress+Hauser...
  • Page 31: Configuring Level Measurement

     Optimizes the signal filters for the respective bin type. Note: ' W orkbench test' deactivates all filters. This option should exclusively be used for tests. Setup → Medium group  Specify media group ("aqueous": DK>4 or "other": DK>1.9) Endress+Hauser...
  • Page 32: User-Specific Applications

    Advanced setup submenu. User-specific applications To configure the parameters for user-specific applications, see: BA01126F - Operating Instructions, FMR53/FMR54, PROFIBUS PA Also, for the Expert submenu: GP01018F - Description of device parameters, FMR5x, PROFIBUS PA Endress+Hauser...
  • Page 36 *71575731* 71575731 www.addresses.endress.com...