Catalyst 6500 series chassis and module power and heat values

Advertisement

Appendix D
Chassis and Module Power and Heat Values
Table D-10
Table D-10
Power Requirements and Heat Dissipation—Fast Ethernet Switching Modules
Model Number/
Module Type
WS-X6148-FE-SFP
48-port 100BASE-X module
WS-X6224-100FX-MT
24-port 100BASE-FX Ethernet
module, MMF
WS-X6324-100FX-MM
24-port 100BASE-FX Ethernet
module, MMF
WS-X6324-100FX-SM
24-port 100BASE-FX Ethernet
module, SMF
WS-X6524-100FX-MM
24-port 100BASE-FX Ethernet
module
Table D-11
Table D-11
Power Requirements and Heat Dissipation—10/100 Ethernet Switching Modules
Model Number/
Module Type
WS-X6148-RJ-21
48-port 10/100 Ethernet module
WS-X6148-RJ21V
48-port 10/100 Ethernet module
with WS-F6K-VPWR PoE
daughter card
WS-X6148-21AF
48-port 10/100 Ethernet module
with WS-F6K-FE48-AF PoE
daughter card
WS-X6148-RJ-45
48-port 10/100 Ethernet module
WS-X6148-RJ45V
48-port 10/100 Ethernet module
with WS-F6K-VPWR PoE
daughter card
OL-5781-08
lists the power and the heat numbers for the Fast Ethernet switching modules.
Module
Module
Current (A)
Power
(Watts)
2.3
96.60
1.90
79.8
1.52
63.84
1.52
63.84
1.90
79.8
lists the power and the heat numbers for the 10/100 Ethernet switching modules.
Module
Module
Current (A)
Power
(Watts)
2.39
100.38
2.39
100.38
2.57
107.94
2.39
100.38
2.39
100.38
AC
DC
AC-Input
Heat Diss.
DC-Input
Power
(BTU/HR)
Power
(Watts)
(Watts)
120.75
412.36
129.84
99.75
340.65
107.26
79.8
272.52
85.81
79.8
272.52
85.81
99.75
340.65
107.3
AC
DC
AC-Input
Heat Diss.
DC-Input
Power
(BTU/HR)
Power
(Watts)
(Watts)
125.48
428.5
134.92
125.48
428.50
134.02
134.93
460.77
145.08
125.48
428.50
134.92
125.48
428.50
134.92
Catalyst 6500 Series Switches Installation Guide
Heat Diss.
(BTU/HR)
443.40
366.3
293.03
293.03
366.3
Heat Diss.
(BTU/HR)
460.75
460.75
495.45
460.75
460.75
D-11

Advertisement