Coster XSE 602 Manual

Coster XSE 602 Manual

Slave optimising compensator for control two zones

Advertisement

SLAVE OPTIMISING COMPENSATOR
FOR CONTROL TWO ZONES
OPTIONAL
C
BUS
C RING
XSE 602
C1 Eng.
• Slave optimising compensator for two zones
– functions only if connected in C-Ring with a "PRIMARY" controller
• Communication systems :
– C-Ring for exchanging data between local controllers.
– C-Bus : XSE 602 Telemanagement optional;
to enable Telemanagement use the ""C-Bus Plug-in" type ACB 400 C1 or later,
to be ordered separately as accessory
• Power supply 230 V AC (or 240 for UK market) ; DIN rail mounting
1. APPLICATION
XSE 602 controller can function only if connected in C-Ring with a "Primary" controller and is able to exchange data
of common interest with other controllers.
XSE 602 is designed for compensated/optimised control of two heating zones in :
– commercial and public buildings
– schools
– residential complexes
By means of C-Bus interface it can be inserted in a telemanagement system.
2. FUNCTIONS
The principal functions of XSE 602 are :
• Compensated control of two heating zones by three-wire control of valves :
– optimisation of start and stop times of plants
– control of plant pumps (with delay in switching off) according current programme of event times
– minimum and maximum temperature limits of flows
– correction of heating curve origin
– self-adjusting
– Eco Off
• Timed programming: twentyfive 24Hour programs & two 7Day periods
• Programming with dates : twentyfive holiday periods ; winter season ; special period.
• Summer plant exercise of valves and pumps
• Automatic change GMT / BST
• Metering of degree-days
• Remote control for modifying current timed programme of events
• Three On-Off inputs for signalling status or alarm
• Alarms for detector short or open circuits and for irregular operation of plants and components
• C-Ring connection for exchange of data with other local controllers
• C-Bus connection for exchange data with local PCs or remote telemangement PC
• Optional C-Bus transmission of data with local PCs or remote Telemanagement PC.
To enable data transmission and Telemanagement use the "C-Bus Plug-in" type ACB 400 C1 or later
To communicate locally with a PC use the test Plug-in type ACX 232
3. DETECTORS, REMOTE CONTROLS & ACCESSORIES
No.
1
Heating flow surface
1
Outside temperature detector
Accessories :
1
Ambient temperature detector
1
Boiler anticondensing immersion detector
1
Remote control for modifying current programme
Options :
1
1) Immersion temperature detector
Accessory for Telemanagement
1
Plug-in for communicating via C-Bus
We reserve the right to make changes witout notice
COSTER
Description
temperature detector
(1)
B 268 - XSE 602 C1 Eng.
Type
Sensing
element
SCH 010
NTC 10 kΩ
SAE 001
NTC
1kΩ
SAB 010
NTC 10 kΩ
SIH 010
NTC 10 kΩ
CDB 300
SIH 010
NTC 10 kΩ
ACB 400C1
22.11.10 AM REV. 02
B 268
22.11.10 AM
REV. 02
Code
Data
sheet
B1-B5
N 130
B2
N 120
B3-B6
N 111
B4
N 140
R
B1-B5
N 140
T 433
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XSE 602 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents