AIR FOR COMBUSTION

AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a con-
fined or unconfined space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1.
Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol-
ume of space)
If additional ventilation to adjoining room is sup-
plied with grills or openings, add the volume of
these rooms to the total volume of the space.
2.
Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
_______ (volume of space) x 20 = (Maximum
Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3.
Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater
Gas water heater* ______________ Btu/Hr
Gas furnace
Vented gas heater
Gas fireplace logs ______________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater
Vent-free heater
Total
6
______________ Btu/Hr
______________ Btu/Hr
______________ Btu/Hr
= __________ Btu/Hr
40,000
______________ Btu/Hr
20,000
+ _____________ Btu/Hr
60,000
= _____________ Btu/Hr
www.desatech.com
4.
Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
______________ Btu/Hr (maximum the space
______________ Btu/Hr (actual amount of
Example:
51,200 Btu/Hr (maximum the space can support)
60,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must pro-
vide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an ad-
joining room. If the extra space provides an un-
confined space, remove door to adjoining room
or add ventilation grills between rooms. See Ven-
tilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/
Hr the space can support, the space is an unconfined
space. You will need no additional fresh air ventilation.
WARNING: If the area in
which the heater may be oper-
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section
5.3 or applicable local codes .
can support)
Btu/Hr used)