A.O. Smith Burkay HW-300 Installation Operation & Maintenance page 41

Up-flow models gas-fired commercial copper boilers for hydronic heating and hot water supply
Hide thumbs Also See for Burkay HW-300:
Table of Contents

Advertisement

ONE HW-300, HW-399, HW-420, HW-520, HW-610 OR HW-670 UP-FLOW MODEL
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT
FIXTURES. SEE TANK TEMPERATURE CONTROL WARNING ON PAGE 32. IF
HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO
FIXTURES.
BOOSTER RECOVERY SYSTEM (PATENTED)
TWO TEMPERATURE SYSTEM WITHOUT RECIRCULATION
COMMERCIAL BOILER WITH HORIZONTAL TANK
DANGER
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED TO
PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR
CIRCULATOR FAILURE (A.O. SMITH PKG. NO. 211480).
+
PIPING AND FITTINGS BETWEEN GATE VALVES AND BOILERS SHOULD BE
BRASS OR BRONZE. OTHER PIPING SHOULD CONFORM TO LOCAL CODES.
GATE VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES
SHALL GOVERN THEIR USAGE.
*
PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE
CAPACITY OF ANY COMPONENT IN THE SYSTEM.
**
INSTALL THERMOMETER AND PRESSURE RELIEF IN OPENINGS PROVIDED
ON HW-520 & HW-610.
USE THIS TABLE FOR CORRECT
PUMP AND WATER PIPE SIZE
Model
Number
HW-300
HW-399
HW-420
HW-520
HW-610,670
*Assumes 50 equivalent feet pf piping or less.
CIRCULATING LOOP TO DISHWASHER
Type L Copper Tubing
Allowable
Distance from Heater to Dishwasher (Feet./Meters)
Pressure
Drop (PSI)
25"
50"
(7.6m) (15m) (22.8m) (30m) (53m) (60m) (76m) (91m)
10
1/2
3/4
20
1/2
1/2
30
1/2
1/2
40
1/2
1/2
50
1/2
1/2
FAIRLY ROUGH PIPE
Allowable
Distance from Heater to Dishwasher (Feet./Meters)
Pressure
Drop (PSI)
25"
50"
(7.6m) (15m) (22.8m) (30m) (53m) (60m) (76m) (91m)
10
3/4
3/4
20
1/2
3/4
30
1/2
1/2
40
1/2
1/2
50
1/2
1/2
NOTE: Allowable pressure drop is the difference in PSI between supply
water pressure and the 20 PSI required at the dishwasher.
FIGURE 36
41
41
41
41
41
Minimum
B & G
*Armstrong
Pipe Size
Pump
(Inches)
Size
1-1/4"
125
1-1/2"
1-1/2" HV
1-1/2"
1-1/2" HV
1-1/2"
1-1/2" HV
2"
2"
WIRING - FIGURE 25 OR 27
INSTALL IN ACCORDANCE
WITH ALL LOCAL CODES
PIPE SIZES "B"
75"
100"
175"
200"
3/4
3/4
3/4
3/4
1/2
3/4
3/4
3/4
1/2
1/2
3/4
3/4
1/2
1/2
1/2
3/4
1/2
1/2
1/2
3/4
75"
100"
175"
200"
3/4
3/4
1
1
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1/2
3/4
3/4
3/4
Pump
Size
S-25 1-1/4"
H-32 1-1/2"
H-32 1-1/2"
H-32 1-1/2"
S-35
250"
300"
1
1
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
250"
300"
1
1
3/4
1
3/4
3/4
3/4
3/4
3/4
3/4