Table of contents Introduction ..............4 1. Project planning ............5 Technical data............6 General information ..........7 3.1 Operation of the LRS 01 ......... 7 3.2 Transport, storage and unpacking ......7 3.3 Scope of supply ............7 Rules and regulations..........8 Installation instructions..........9 5.1 Mounting the LKS 02 ..........
Installation Instructions LRS 01 Introduction Figure 01 The LRS 01 consists of a ventilation duct socket LKS 02 and an ORS 210 optical Smoke Switch with alarm latching. It is used for monitoring smoke in ventilation ducts. The LKS 02 provides a mounting for Smoke Switch ORS 210 and is fitted on the outside of a ventilation duct.
Kanalmaß Figure 02 Figure 02 provides recommendations for project planning. To ensure reliable smoke detection, in large ducts several LRS 01 Smoke Switches should be instal- led. The airflow parameters must be taken into account when determining their positions.
120 g The ORS 210 has latching alarm functions. Following an alarm , the relay (contacts 4 and 5) remains open until the supply voltage is briefly interrupted. HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006...
Resetting is carried out by briefly interrupting the power supply when the duct is free of smoke. 3.2 Transport, storage and unpacking The LRS 01 is supplied in a suitable carton package. This package can be recy- cled. Please note the properties of the package! The carton in which the LRS 01 is packed complies with minimal package requirements, and can support up to 10-times its own weight when stacked.
As a matter of principle, if a product simultaneously falls within the scope of other directives, all directives will be applied in parallel so that the special requirements of all directives can be fulfilled. HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006...
Ensure that the place where the socket LKS 02 is installed is, as far as possible, free of vibration. 7002428 100206.VDA Ausgabe 10.02.2006 HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg...
Page 10
Figure 05 Warning! When mounting the LKS 02 socket, it is important to ensure that the airflow direction is correct, and that the socket is properly sealed. HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006...
Page 11
Smoke Switch will not be subject to dew formation. TheLRS 01 must not be used out of doors. These instructions must be taken into account when planning the installation. 7002428 100206.VDA Ausgabe 10.02.2006 HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg...
In the LKS 02, the LED of the ORS 210 and the arrow in the socket point towards the outlet tube. The LRS 01 can only operate correctly when the cover is properly closed.
Page 13
Smoke Switch ORS 210. Status information, transmitted via the communication interface (terminal 3), is purely for ease of operation and information 7002428 100206.VDA Ausgabe 10.02.2006 HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg...
6.2 Display of operating status of the ORS 210 Signal, frequency Colour of LED Meaning green Operating status green/yellow Slight contamination green/yellow Heavy contamination yellow Fault Alarm „Off“ No power HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006...
By observing basic maintenance measures according to DIN 31051 in conjunction with DIN EN 13306, the LRS 01 system should be kept permanently ready for operation; it should be serviced annually as specified by the manufacturer.