Operating manual Smoke alarm Genius Plus Genius Plus X...
Page 3
Behaviour in the event of fire 1. Rescue people slots and try to attract someone’s attention at the window. f Warn the people living with you. f Immediately leave the room / the building and close all doors on your way out to prevent a rapid spread of 2.
Plus X with the Standard X radio operating manual. module: This manual applies to the smoke alarms Genius Plus and Genius Plus X. To the Genius Plus X with radio networking, however, “Standard X radio module” operating manual shall apply additionally. The www.hekatron-brandschutz.de/...
The smoke alarm can be operated If the smoke alarm is used as a stand-alone smoke alarm improperly, Hekatron Vertriebs (Genius Plus) or as a smoke GmbH shall not assume any liability alarm with radio networking for the resulting damage. (Genius Plus X).
Do not cover or put tape over the instructions are not observed, smoke inlets. no liability and warranty claims against Hekatron Vertriebs GmbH The batteries are firmly installed shall be enforceable. and may not be replaced. Do not expose the smoke alarm to ...
Page 9
Safety | 9 Renovation work Protect the smoke alarm against dust and contamination (e.g. cover the smoke alarm or dismount it and store it in a plastic bag). Once the renovation work is completed, reassemble the smoke alarm or remove the cover.
10 | Product description 4. Product description Magnetic holder Base Elongated holes for 2-hole assembly Round hole for 1-hole assembly Smoke inlets Smoke alarm (including non-removable batteries) Test button with Not displayed Adhesive pad Screw and dowel for 1-hole assembly Opening for the acoustic alarm...
Product description | 11 4.1 Functional 4.2 Features principle Contamination compensation: The smoke alarm automatically smoke alarm utilises adapts to normal changes in its scattered-light principle. Light environment and thus guarantees beams are regularly sent out in a constant level of sensitivity and a the measuring chamber, which are long service life.
Hekatron Vertriebs GmbH deep frequencies, the alarm sound herewith declares that the Genius is better perceived by humans. Plus / Genius Plus X smoke alarm is compliant with EU regulations 2014/30/EU and 2011/65/EU. The complete declaration of conformity Radio networking option can be found on our website (only Genius Plus X)
Project planning | 13 5. Project planning The corresponding national directives Office and regulations shall apply to the project planning. The figures and Children’s information on the minimum fitting Bedroom room and the ideal fitting refer to Germany (mandatory smoke alarms). Living room Kitchen Minimum fitting:...
Monitored area per smoke alarm: max. 60 m² f The standard case and special cases must be observed. Genius Plus X: at least 0.5 m at least 0.5 m If radio smoke alarms are used, max. 6 m the chapter “Project planning”...
Assembly position | 15 6.2 Special cases Rooms with sloped ceiling > 20° Slope < 20°: Sloped ceilings with small inclination are treated like horizontal ceilings (see standard case). Slope > 20°: ≤ 1 m The following applies to sloped ceilings with a larger inclination: Clearance to peak: ...
Page 16
16 | Assembly position max. 3 m Long and narrow rooms (e.g. hallways) In rooms and hallways with a width of < 1 m, the following assembly position applies: In a central position on the ceiling between the walls max 7.5 m In hallways with a width of <...
Page 17
Assembly position | 17 Wall assembly The following conditions apply to wall assembly: The smoke alarm may be placed on the wall of a room in the following In a central position on the longer cases: wall Ceiling-assembly is not possible Clearance to ceiling: 0.3 to 0.5 m ...
2 screws: see 7.2 Assembly with an adhesive pad: see 7.3 secure permanent connection, Hekatron recommends the screw/dowel assembly. The fastening material for a 1-hole assembly is included in the scope of delivery. If other screws are to be used, the...
Assembly | 19 7.1 Screw/dowel 7.2 Screw/dowel assembly with assembly with 1 screw 2 screws f Hold the base against the ceiling f Hold the base against the ceiling and mark the hole for the desired and mark the holes for the assembly position.
Clean the surface in the desired Only the adhesive pad supplied assembly position. by Hekatron may be used for the assembly with adhesive pad. f Remove the protective foil on one CAUTION side of the adhesive pad and attach...
Commissioning | 21 8. Commissioning Genius Plus X: If the smoke alarm is removed With radio smoke alarms, from the base again, it will the radio module is to be automatically switch off after installed before commissioning 5 minutes. (see “Standard X radio module”...
22 | Seal (accessories) 9. Seal (accessories) f Insert the seal into the opening. The smoke alarm can be secured against removal by unauthorised Ö The opening is closed persons or sabotage by means of a completely. seal. Removing the seal Inserting the seal f Rotate the seal by 90°...
Status signals | 23 10. Status signals If using the Genius Plus X, the operating manual of the radio In normal operation, the smoke alarm module is to be observed in carries out an automatic self-check in addition. regular intervals. The corresponding...
Page 24
24 | Status signals Fire alarm As soon as the smoke alarm detects smoke, it enters the “fire alarm” mode. In this mode, the LED is flashing, and the acoustic alarm is sounded. Test button Acoustic alarm Cause Remedy Flashes every Alternating, loud Smoke is detected Exit the building second...
Maintenance | 25 11. Maintenance Carrying out maintenance f Remove the dust from the smoke able guarantee alarm with a soft cloth. impeccable function of the smoke alarm, an on-site inspection including f If required, remove any functional test is to be carried at contamination with a wet cloth.
Page 26
Replace the smoke alarm. Flashes 1x Sound indicating a Fault detected. negative test result Replace the smoke alarm. Examples for all different sounds can be found on our website, in the FAQ (only available in German): www.hekatron-brandschutz.de/faq/...
DIN EN ISO with the domestic waste is 9001 and DIN EN ISO 14001. inadmissible. The Genius Plus / Plus X smoke alarms meet the statutory RoHS requirements and are free from any illegal substances. Hekatron has already assumed the...
10 years. Installation of the radio module: at the latest 2 years after the initial Genius Plus and Genius Plus X commissioning of the smoke alarm Commission the smoke alarm Commissioning of the radio ...
Product complaints | 29 15. Product complaints Our smoke alarms meet the highest quality requirements. Should you nevertheless have any reason to complain, please directly contact your dealer.
Ambient humidity at ≤ + 40 °C 10 to 70 % rH (permanent, without condensation) For safety reasons, an uninterrupted power supply is required for the smoke alarm. The optionally available radio modules are supplied via an internal battery of the Genius Plus X.
Page 31
Technical data | 31 Weight with base approx. 162 g Protection classs IP 40 Colour white, silk-matte, similar to RAL 9010 Material PC-ABS Dimensions, height/diameter 48 mm x 104 mm Subject to technical changes and changes in colour. No liability is accepted for mistakes and printing errors!
Page 32
Obliged to safety. The protection of people and material assets in the event of a fire has always been the main objective of Hekatron Brandschutz. We are the leading provider of technical fire protection systems in Germany and your number-one partner in this field.