Page 1
EACTIVATED RYERS PE SERIES/EE SERIES/PB SERIES Owner’s Manual Printed in U.S.A. Publication No. OM-A-10E April 2004...
Page 2
To receive Extended Warranty, you must regis- ter on line at: www.pneumatech.com. Doing this will extend the warranty to 24 months from date of shipment from Company’s factory. See back page for actual Warranty details. DATE OF PURCHASE MODEL SERIAL NO.
GENERAL INFORMATION SAFETY INSTRUCTIONS The Pneumatech Drying System is designed to remove moisture from compressed air. When using air compressors and compressed air When properly installed, the unit requires little accessories, basic safety rules and precautions must maintenance or adjustment.
DISCLAIMER OF WARRANTY SECURE DRAIN LINES Fasten drain lines from prefilter/separator to floor or If this unit is used to produce breathing air, the special drain. Pressurized air will periodically pass through equipment and precautions expressed in OSHA 29 CFR drain lines, which will cause an unsecured line to 1910.134 for specifications of the necessary equipment whip and may cause bodily injury.
DESICCANT REPLACEMENT PROCEDURES DRAINING PROCEDURE Pneumatech uses Activated Alumina Grade A desiccant for all standard heat reactivated air dryers. Dryers up to The desiccant can be removed by the two methods listed 1500 SCFM are factory filled with desiccant. Dryers below.
PE & EE SERIES HEAT REACTIVATED AIR e. Prior to start-up, check the heater element resistance. The element (phase) to ground should DRYER INSTALLATION & OPERATION exceed the resistance value by 20 megohms. If this value is not indicated, energize the heater at low voltage to drive the moisture from the General element insulation.
“ADVANCE” push button is disabled whenever the INTRODUCTION timing is stopped by an inhibit switch. GENERAL: The Pneumatech DMP controller is a microprocessor controlled, ten (10) channel sequence timer with LCD and LED display features. The DMP controller consists of the main control unit and the remote LCD, LED and I/O module.
Page 11
LOW PRESSURE: All heated regenerative dryers b. The high temperature set point to be adjusted will are supplied with Low Pressure Switch Inhibit. When be displayed on the LCD. Use the “TEMP the low pressure is detected, all timing functions stop DISPLAY”...
FAIL TO SHIFT: The fail to shift inhibit will be With the power switch in the ON position at energized if the inhibit switch remains closed for 30 time equal to 0.0 hrs., the left tower air inlet valve is minutes beyond the normal cycle.
ZERO 240 MINUTES 480 MINUTES LEFT TOWER SWITCHING RIGHT TOWER SWITCHING LEFT TOWER REGENERATING RIGHT TOWER REGENERATING HEATER DEMAND CYCLE LEFT TOWER DEPRESSURIZING (OPT.) RIGHT TOWER DEPRESSURIZING (OPT.) ZERO 240 MINUTES 480 MINUTES R TOWER R TOWER L TOWER L TOWER TIMING STAGE: HEATING COOLING...
Page 14
TYPICAL PE SERIES FLOW DIAGRAM AIR OUTLET PILOT AIR LINE EX (SLIGHT BLEED) CLOSED OPEN CLOSED OPEN DRYING REGEN FLOW FLOW CLOSED CLOSED OPEN OPEN CLOSED INLET PRESSURE VESSEL 16. HEATER CONTROL THERMOSTAT AIR INLET VALVE 17. OVER TEMPERATURE THERMOSTAT AIR OUTLET CHECK VALVE 18.
PB SERIES HEAT REACTIVATED BLOWER e. Prior to start-up, check the heater element resistance. Element (phase) to ground should PURGE AIR DRYER INSTALLATION & exceed the resistance value by 20 megohms. If this value is not indicated, energize the heater at OPERATION low voltage to drive the moisture from the element insulation.
Slowly open the dryer outlet isolation valve to With the power switch in the ON position at pressurize the downstream system. time equal to 0.0 hrs., the left tower air inlet valve is open to allow the air to pass through the left tower. The 10.
Dry Air Sweep If the compressed air system has been piped with a bypass around the dryer, then In order to maintain constant dewpoint, the Pneumatech the following should be completed: dryer uses a dry air sweep during the cool down cycle.
Page 18
TYPICAL PB SERIES FLOW DIAGRAM AIR OUTLET PILOT AIR LINE EX (SLIGHT BLEED) CLOSED OPEN OPEN CLOSED REGEN DRYING FLOW FLOW CLOSED CLOSED OPEN OPEN CLOSED INLET PRESSURE VESSEL 19. PURGE ORIFICE ASSEMBLY AIR INLET VALVE 20. PURGE ADJUSTMENT PRESSURE GAUGE PURGE FLOW CHECK VALVE 22.
MAINTENANCE PE & EE SERIES HEAT REACTIVATED AIR Three Months Every three (3) months, close the purge adjusting DRYER MAINTENANCE valve momentarily to check for any leaks in the inlet and/or check valves indicated by air coming through the exhaust mufflers. Check the prefilter and afterfilter elements for excessive clogging or possible damage.
Mufflers Monthly Purge mufflers are installed to reduce the noise level. The Check the pilot air filter element. Replace if mufflers tend to plug up and increase back pressure over necessary. time due to oil carryover and contaminants from Check the blower intake filter. Replace if necessary. compressor, or due to desiccant dust at the initial start-up.
DEWPOINT DISPLAY KEY FUNCTIONS OPEN SENSOR CONDITION DIGITAL DISPLAY KEY FUNCTIONS When message oPEn1 is displayed, the dewpoint sensor BUTTON is likely to be disconnected from the hygrometer. -73.5F SETPOINT LIMIT INDICATION SP1 SP2 Prog. BUTTON Setpoint limit message is the flashing number within PROGRAM operating range of the hygrometer.
Page 22
FIGURE 6 — DEWPOINT DISPLAY CONTROL WIRING Pub. No. OM-A-10E — April 2004...
PLC Controller is standard on PB series Blower Purge Calibration: To maintain accuracy, replace the probe dryers and with Pneumatech’s Pulse Purge Regeneration every two years. option. It can also be added to control the operation of Probe Replacement: Turn the normal/demand selector standard regenerative dryers.
DEWPOINT DEMAND CONTROL “DPD” PULSE PURGE REGENERATION (PPR) WITH DEWPOINT DEMAND (DPD) The Dewpoint Demand control is an energy saver that can extend the drying cycle without purging, during periods of (PE & EE Series only) lower moisture loads. The Dewpoint Demand system offers, in one compact package, the utmost in flexibility Pulse Purge Regeneration systems use the same NEMA and accuracy sensing the actual dewpoint of the outlet air.
Table 1 — Troubleshooting Guide for Regenerative Dryers, continued Symptoms Cause Remedy D. Excessive flow through mufflers. 1. Check valves leaking. 1. Repair or replace faulty check valves. NOTE: To test for leaking, check valves during regeneration cycle, shut the purge adjusting valve.
Page 27
Table 1 — Troubleshooting Guide for Regenerative Dryers, continued Symptoms Cause Remedy L. Tower does not pressurize fully. 1. Inlet pressure low. 1. Calibrate and plot purge pressure and reset. 2. Purge pressure too low. 2. Reset proper purge pressure. 3.
Page 28
LIMITED WARRANTY Warranties and Limitation of Liability: Pneumatech/ConservAIR (“the Company”) warrants that it will, in its sole discretion, either repair or replace Products and/or Components of Products sold by it which have defects in material or workmanship (covering Components and reasonable labor) provided: (a) Customer notified the Company of any claim of defect in material or workmanship within fourteen (14) months from date of shipment from the Company’s factory or twelve (12) months from the date of initial operation of Product, whichever occurs...
Need help?
Do you have a question about the PB Series and is the answer not in the manual?
Questions and answers