Digital intelligent pressure transmitter / differential pressure transmitter (31 pages)
Summary of Contents for EYC THS307
Page 1
THS30X Series Multifunction Temperature & Humidity Transmitter Operation Manual...
Page 2
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 1. Features 2. Security considerations 3. Installation 4. Connection 5. Display and LED instruction 6. Software setting and calibration operation steps 7. Maintenance and exception PAGE:2 OF 65 Version:03 Date:2017.08.25...
Page 3
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual Oder Code: PAGE:3 OF 65 Version:03 Date:2017.08.25...
Page 4
Do not use this product in a situation where human life may be affected. This product can not be used for explosion-proof area. Do not use this product in a situation where human life may be affected. EYC-TECH will not bear any responsibility for the results produced by the operators. Electromagnetic Compatibility Directive:2014/30/EU...
Page 5
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual Warning!! ●Installation and wring must be performed by qualified personnel in accordance with all applicable safety standards. ●This product must be operated under the operating conditions specified in manual to prevent equipment damages.
Page 6
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3. Installation 3.1 Dimension PAGE:6 OF 65 Version:03 Date:2017.08.25...
Page 7
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual PAGE:7 OF 65 Version:03 Date:2017.08.25...
Page 8
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3.2 Electric Connector Dimension PAGE:8 OF 65 Version:03 Date:2017.08.25...
Page 9
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3.3 Installation BASE Installing Flange Installing Fitting thread COVER Installing Shield PAGE:9 OF 65 Version:03 Date:2017.08.25...
Page 10
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3.3 Option accessory 1. Fixed type Order code Name Desciption Dimension Metal Flange Material 4415000022 Stainless Steel Din-rail board Material HS-S Stainless Steel L board Material 4435000005 SPCC+Zinc plated Fitting thread Material 8203104012 Stainless Steel...
Page 11
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual Order code Name Description Features Material: PC fire-proof class + Common filtering effect 8203104010 cotton filter Max. temp. : 80 Outside diameter:12mm Length:32mm Material SUS316L SUS sintered filter Excellent filterable, and Sinter type pollution, corrosion and HD 40μm...
Page 12
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 4. Connection 4.1 Analogue Diagram 4.2 RS-485 Diagram 4.3 Analogue + RS-485 Diagram PAGE:12 OF 65 Version:03 Date:2017.08.25...
Page 13
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Display and LED instruction 5.1 LCM display 5.2 LED Indication 1. Power LED P, Green light 2. RS-485: LED P, Red light 3. LED light position statement: PAGE:13 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.1 Application Program statement 1. Free installation program THS UI_F19.exe a. Operating System requirements above Windows XP 2. Other application program requirements above Microsoft Office 2003 PAGE:15 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.2 Setting RS-485connection 1. Connect product to PC via RS-485 cable 2. Execute THS 3. Click PAGE:16 OF 65 Version:03 Date:2017.08.25...
Page 17
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 4. Select the corresponding values of com port as fallowing : 5. Click Apply PAGE:17 OF 65 Version:03 Date:2017.08.25...
Page 18
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6. Connect successfully a. Show value and trend chart of Temperature and Relative Humidity b. Show Open port, Read successful PAGE:18 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.3 Scan RS-485 connection Use scan function to connect when forgetting the connection information or having more facilites. 1. Connect the product to PC via RS-485 cable 2. Execute 3. Click PAGE:19 OF 65 Version:03 Date:2017.08.25...
Page 20
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 4. Select the corresponding values of com port as fallowing: a. Port b. RS-485 4. Click Scan to execute connection facilities PAGE:20 OF 65 Version:03 Date:2017.08.25...
Page 21
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Scan connection facilities and set up Select Station ID Click CLOSE AND EXPORT PAGE:21 OF 65 Version:03 Date:2017.08.25...
Page 22
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6. Click Apply PAGE:22 OF 65 Version:03 Date:2017.08.25...
Page 23
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 7. Connect successfully a. Show values and trend chat Temperature and Relative Humidity b. Show Open port, Read successful PAGE:23 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.4 Setting RS-485 ModBus Protocol 1. Setting RS-485 connection step as step 6.1 2. Click Setting PAGE:24 OF 65 Version:03 Date:2017.08.25...
Page 25
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3. Select Modbus Protocol parameter a. Station ID 1~247 b. Baud Rate 9600, 19200, 38400, 57600, 115200 c. Data Frame None-8Bit-1Stop, None-8Bit-2Stop, Even-8Bit-1Stop, Even-8Bit-2Stop, Odd-8Bit-1Stop, Odd-8Bit-1Stop 4. Click Apply 5. Execute connection as step 6.2 or 6.3 again PAGE:25 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.5 Display and save data 1. Show data Click Display PAGE:26 OF 65 Version:03 Date:2017.08.25...
Page 27
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Icon function statements Clear the chart records Change the chart style Select the OUTPUT channel Set line color chosen from OUTPUT Snap chart Save the data measuring when the system start connecting before clinking the Export icon Show/Not show the statement of Y axis Show/Not show the statement of X axis Show/Not show the statement of Y secondary axis...
Page 28
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 3. Setting time interval of record a. File > Log Interval b. Select time interval of record PAGE:28 OF 65 Version:03 Date:2017.08.25...
Page 29
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 4. Save/Log measuring data a. Log measuring range Save the data measuring when the system start connecting before clinking the Export icon a-1. Click Display > Export a-2. Appoint path and Key in file name > save 1.
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual b. Log measuring data Log the data which is on from start or off b-1. Display > Log(OFF) b-1. Appoint path and Key in file name > save > Log(ON) 1. If file name is some as the path name, the original file will be covered. 6.6 Choose parameter of Output 1.
Page 31
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual PAGE:31 OF 65 Version:03 Date:2017.08.25...
Page 32
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Select relative parameters from Output1and Output2 a. Output style b. Responding time c. Voltage or currant Output d. Voltage or current analog range e. Upper and Lower point of Output 3.
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.7 Temperature Calibration with two points 1. Calibrate upper point of temperature a. Click Calibration PAGE:33 OF 65 Version:03 Date:2017.08.25...
Page 34
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual b. Put the product in the temperature control box, and adjust the upper point of temperature (ex: 100 ) c. Wait the temperature of control box is becoming stable d. Click Temperature > UPPER POINT PAGE:34 OF 65 Version:03 Date:2017.08.25...
Page 35
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual e. Input the reference temperarue, then click f. That calibrating upper point temperature is done. PAGE:35 OF 65 Version:03 Date:2017.08.25...
Page 36
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Calibrate lower point of temperature a. Put the product in the temperature control box, and adjust the lower point of temperature (ex: b. The difference temperature between Upper and Lower point must be at least 30 . c.
Page 37
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual e. Input reference temperature, then click f. That calibrating lower point temperature is done. PAGE:37 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.8 Humidity Calibration with two points 1. Calibrate Upper point of humidity a. Click Calibration PAGE:38 OF 65 Version:03 Date:2017.08.25...
Page 39
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual b. Put the product in the humidity control box, and adjust upper point of humidity (ex: RH 80%) c. Wait the humidity of control box is becoming stable. d. Click Relative Humidity > UPPER POINT PAGE:39 OF 65 Version:03 Date:2017.08.25...
Page 40
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual e. Input reference humidity, then click f. That calibrating upper point humidity is done. PAGE:40 OF 65 Version:03 Date:2017.08.25...
Page 41
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Calibrate humidity lower point a. Put the product in the humidity control box, and adjust lower point of humidity (ex: RH 20%) b. Wait the humidity of control box is becoming stable. c.
Page 42
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual d. Input reference humidity, then click e. That calibrating lower point humidity is done. PAGE:42 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.9 Temperature Calibration with signal points 1. Click Calibration PAGE:43 OF 65 Version:03 Date:2017.08.25...
Page 44
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Put the product in the temperature control box, and adjust the temperature point which you want to calibrate (ex: 50 ) 3. Wait the temperature of control box is becoming stable. 4.
Page 45
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Input reference temperature, then click 6. That calibrating signal point temperature is done. PAGE:45 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.10 Humidity Calibration with signal point 1. Click Calibration PAGE:46 OF 65 Version:03 Date:2017.08.25...
Page 47
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Put the product in humidity control box, then adjust the humidity point which you want to calibrate (ex: 50%) 3. Wait the humidity of control box is becoming stable. 4. Click Relative Humidity > OFFSET POINT PAGE:47 OF 65 Version:03 Date:2017.08.25...
Page 48
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Input reference humidity, then click 6. That calibrating signal point humidity is done. PAGE:48 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.11 Restore factory setting of signal/two point(s) 1. Restore factory setting temperature a. Click Calibration b. Click temperature > RECALL FACTORY CALIB c. Show store Factory Temperature d. That restore temperature of factory setting is done. PAGE:49 OF 65 Version:03 Date:2017.08.25...
Page 50
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Restore humidity of factory setting a. Click Calibration b. Clock Relative Humidity > RECALL FACTORY CALIB c. Show store Factory Rel. Humidity d. That restore humidity of factory setting is done. PAGE:50 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.12 Temperature Calibration with more points Because of that the product has high accuracy and using this calibration way can influence linear accuracy, we do not suggest to use this calibration way. 1.
Page 52
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Put the product in the environment of temperature which you want to calibrate 3. Wait the environment of temperature is becoming stable 4. Retain the factory setting a. Input the value which you want to calibrate in the Temperature area (ex: 25 ) a-1.
Page 53
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Delete factory setting a. click Temperature > CLEAR (clear data) b. Click Temperature > WRITE (clear factory setting) PAGE:53 OF 65 Version:03 Date:2017.08.25...
Page 54
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual c. Input the value which you want to calibrate c-1. Tunit[ ] Value which product shows c-2. Tstd[ ] Standard value of calibration 1 Please enter calibration points in the blank, 10 points maximal. 2 The interval between two points should be 10 above.
Page 55
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6. Retain the part of factory setting a. Click left keyboard twice on the mouse on the factory setting which you want to delete b. Click delete icon of Keyboard or right keyboard of mouse to clear data c.
Page 56
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual d. Input the value which you want to calibrate d-1. Tunit[%] Value which product shows d-2. Tstd[%] Standard value of calibration e. click Temperature > WRITE PAGE:56 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.13 Humidity Calibration with more points 1. Click Calibration Humidity Calibration with more points Statement The existing value is record of more points of calibrating which was executed by factory when operators log in Calibration page at the first time. PAGE:57 OF 65 Version:03 Date:2017.08.25...
Page 58
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Put the product in the environmental of humidity which you want to calibrate 3. Wait the environmental of humidity is becoming stable 4. Retain the factory setting a. Input the value which you want to calibrate in the Relative Humidity area a-1.
Page 59
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 5. Delete factory setting a. click Relative Humidity > CLEAR (clear data) b. Click Relative Humidity > WRITE (clear factory setting) PAGE:59 OF 65 Version:03 Date:2017.08.25...
Page 60
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual c. Input the value which you want to calibrate in the Relative Humidity area c-1. Hunit[%] Value which product shows c-2. Hstd[%] Standard value of calibration 1 Please enter calibration points in the blank, 10 points maximal. 2 The interval between two points should be 10% above.
Page 61
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6. Retain the part of factory setting a. Click left keyboard twice on the mouse on the factory setting which you want to delete b. Click delete icon of Keyboard or right keyboard of mouse to clear data c.
Page 62
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual d. Input the value which you want to calibrate in the Relative Humidity area d-1. Hunit[%] Value which product shows d-2. Hstd[%] Standard value of calibration e. Click Relative Humidity > WRITE PAGE:62 OF 65 Version:03 Date:2017.08.25...
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 6.14 Restore factory setting of more points 1. Recall temperature of factory setting a. Click Calibration b. Click Temperature > RECALL d. That restore more points temperature of factory setting is done. PAGE:63 OF 65 Version:03 Date:2017.08.25...
Page 64
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual 2. Recall the factory setting of more points of humidity a. Click Calibration b. Click Relative Humidity > RECALL e. That restore humidity of factory setting is done. 7. Inspection and maintenance 1.
Page 65
THS30 Series Multifunction Temperature & Humidity Transmitter Operation Manual shipment, no calibration on the installation site is necessary when this product is installed. For inspection and maintenance follow the instructions below 1) Periodic inspection Periodically inspect this product for its sensing accuracy, and clean the cover. Set the period between inspections based on atmospheric dust and other contaminants in the installation environment.