Compaq 207590-B21 - Power Distribution Unit Strip Quick Install Manual page 3

Rack-mounted power distribution unit (pdu) high voltage models
Hide thumbs Also See for 207590-B21 - Power Distribution Unit Strip:

Advertisement

Connecting PDU to the UPS
5
When installing the 16A IEC-to-IEC power cord for connectivity between
the Compaq High Voltage PDU (part number 207590-B21) and these Compaq UPS
models, install the power cord as shown.
Compaq R3000 XR UPS
(International models only, for the North
America and Japan models, order
part number 340653-001)
Attaching the Input Line Cord
6
Connect the detachable power cord now. If the appropriate power cord is not
included in the PDU kit, contact your authorized Compaq service representative
to obtain the proper power cord. Suitable power cords include:
! Euro
295547-002
! UK
295547-031
! Denmark/Switzerland
295547-003
! South Africa/India
295547-AR1
! Australia/New Zealand
295547-011
7
Connecting Devices
When connecting devices to this PDU, distribute loads to remain within the
capability of the load group and the PDU.
Model 207590-B21 has twelve receptacles, divided into two load groups, with each
load group controlled by a circuit breaker. Load groups 1 and 2 are rated at 8A each
and contain six receptacles each. This model has a maximum rating of 16A.
Models 207590-B31 and 207590-D72 have twelve receptacles, divided into four load
groups, with each load group controlled by a circuit breaker. Load groups 1, 2, 3 and
4 are rated at 8A each and contain three receptacles each. Model 207590-B31 has a
maximum rating of 32A. Model 207590-D72 has a maximum rating of 24A.
Model 207590-B23 has nine receptacles, divided into five load groups, with each
load group controlled by a circuit breaker. Load groups 1, 2, and 3 are rated at 12A
each and contain one receptacle each. Load groups 4 and 5 are rated at 8A each and
contain three receptacles each. This model has a maximum rating of 40A.
(model 207590-B21)
Compaq R6000 Series UPS
(model 207590-B21)
Hardwiring
Model 207590-B23 must be hardwired by a qualified electrician in accordance with
local electrical installation codes.
Safety Precautions
Take the following safety precautions when connecting multiple pieces of information
technology equipment to UPS and PDU units.
WARNING:
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY
The summation of the input power for multiple pieces of Information Technology
Equipment through the use of a UPS or PDU can result in high leakage currents.
If the total system leakage current for a system of components exceeds 3.5 mA:
! The use of a detachable input power cord for the UPS or PDU is prohibited.
! The input cord must be securely attached to the UPS or PDU and it should be
connected to the AC Mains by hard wiring or through the use of a
non-residential, industrial style plug that maintains positive earth connection.
! If the total system leakage current through the ground conductor exceeds 5%
of the input current per line, under normal operating conditions, the system
loads should be divided among multiple power connections.
WARNING:
To reduce the risk of personal injury resulting from electric
shock, do not remove the cover from the Power Distribution Unit. There are
no field-serviceable or user-serviceable components inside.
About the Circuit Breakers
The circuit breakers protect the PDU and all devices connected to it from damage
caused by an incoming electrical surge or equipment malfunction.
If power to a device is interrupted, check the circuit breakers and reset, if necessary.
If power is still not restored, contact your authorized Compaq service representative
at 1-800-OK-COMPAQ (1-800-652-6672). For continuous quality improvement,
calls may be recorded or monitored.
For additional information, visit the Compaq website at www.compaq.com.
Installation is complete.