Fire, electrical shock, property damage, personal injury, or death! All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. If additional information is required please contact your local distributor. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 5
Product damage! Make sure the blower motor support is tight (Figure 1). Then check if wheel is tightly secured to motor shaft before operating unit. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 6
WARNING Personal injury! The unit must be permanently grounded. Failure to do so may result in electrical shock causing personal injury or death. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 7
• Equipment marking must remain visible and legible. Markings and signs that are illegible shall be corrected. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 8
Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 9
Do not use the air conditioner until a service person confirms that the refrigerant leak is repaired. Keep ventilation openings clear of obstruction. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
The allowed maximum refrigerant charge (Mmax) and the required minimum room area (Amin) can be determined according to Table 5 and Tables 6-8. 12 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
The room area in which the unit is installed shall be not less than 20% Amin. Amin is shown in Tables 6-8. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 13...
Page 14
14 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 17
If the actual room area, air outlet height, and refrigerant charge amount are not reflected in the above table, more severe cases need to be considered according to the data in the tables 4-9. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 17...
“HACR” type circuit breakers. • High voltage wiring must be connected to the red and black wiring in the control section of the air handler. 18 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
TAPS NOT USED NOT USED THE FACTORY THE FACTORY SW6-3,4 DEFAULT DEFAULT SW7-1,2 THE FACTORY THE FACTORY DEFAULT DEFAULT SW7-3,4 Figure 7 Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 19...
1. Airflow data is without filter. 2. Use wet coil data for determining cooling airflow. 3. Bottom louver panel adds 0.05 in. static pressure. 20 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
1. Airflow data is without filter. 2. Use wet coil data for determining cooling airflow. 3. Bottom louver panel adds 0.05 in. static pressure. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 21...
Page 22
1. Airflow data is without filter. 2. Use wet coil data for determining cooling airflow. 3. Bottom louver panel adds 0.05 in. static pressure. 22 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Refer to local code requirements for usage of auxiliary drain pan and condensate overflow switch. 24 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
This residue could soil ceilings, walls, drapes, carpets and other articles in the house. Soot damage may occur with filters in place, when certain types of candles, oil lamps or standing pilots are burned. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 25...
. The sharp metal edges can cut you. Components and units must be properly disposed in accordance with federal or local regulations. 26 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Note: Any time the electric heat elements are active, the indoor fan will run in high stage. Support 3H and 1C thermostat non-communicating setup Figure 12 Thermostat wiring diagram for BOVA 15 with BICA series Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 27...
5: The rated operating condition of Alarm is 24 VAC/1A or 30 VDC/1A or 250 VAC/1A. Figure 13 Wiring Diagram for BICA 28 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Page 29
The blower motor is equipped with a Time Delay Board (TDB). There is a 90 second Fan-off delay when G is de-energized on the thermostat terminal. This setting cannot be changed. Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 29...
140 F? Figure 18 Replace the A2L refrigerant sensor and power the unit back up again. Figure 16 30 | Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024)
Alternatively, please visit our Service & Support webpage to find FAQs, videos, service bulletins, and more; www.boschheatingcooling.com/service or use your cellphone to scan the code below. Figure 19 Bosch IDS Heat Pump BICA Series Ceiling Mounted Air Handler Units - BTC 762003312 A (12.2024) | 31...