GMC-P7 1. Outline GMC-P7 bulk scale controller is a weighing control instrument specially developed for discontinuous automatic accumulation scale. The controller adopts a full English touchscreen display interface, has the characteristics of moderate size, high precision, powerful function and simple and practical operation.It can be widely used in...
Page 6
GMC-P7 erface Description User info: Show user ID, system time, recipe ID, target value, total ACUM and batch. Weight status: Weight value display, weight unit display, Status display and shortcut I/O Function. Packaging info:Display current target flowrate, total stock in and out volume and ACUM data etc.
GMC-P7 Debug interface description: Shortcut setting recipe paremeter: Can promptly setting recipe parameter, debug controller easliy. Packing history record: Can view the current packaging history data directly, easy to compare. 1.3 Rear Panel Description 1.4 Technical Specifications...
GMC-P7 Zero adjustment range: 0. 00 2~ 15.625 mV ( when load cell is 3mV/V) Input sensitivity: 0 . 0 2 u V / d Input range: 0 . 0 0 2 ~ 1 5 . 6 2 5 m V Conversion: Sigma - Delt a A/D Conversion rate:...
1)Make appropriate installation holes on the control box, ( size: 213(±1)mm ×147(±1) 2)Install the GMC-P7 into a control box 3)Remove the fixing plates on both sides of GMC-P7, fix it with the fixing plates and lock them with M4*12 screws.
GMC-P7 I/O Function Input port diagram I/O Function output connection diagram I/O Function value of GM C- P7 is user-defined to facilitate wiring and some special applications. Please refer to section 4.5 2.4 Power Supply Connection GM C -P 7 bulk scale controller use 24V DC power supply.
2.6 Touch Screen Calibration Fisrt use new controller or laid-aside for a long time need to calibrate touch screen, calibrate instruction: GMC-P7 power on, long press any point on the touch screen at the same time, system - 7 -...
Page 12
GMC-P7 turn to touch screen calibrate interface, long press cursor position on touch screen, cursor position calibrate finish, after the interface displays the coordinates of this point, enter to next calibrate automatically. Follow cursor position changes long press accordingly, calibrate finish, and interface show 5 calibration point coordinates, enter to main interface automatically.
GMC-P7 3. User Permission Description In order to prevent wrong operation causing GMC-P7 working improperly, it provides three rights (operators, administrators and system administrators): System administrator can perform all operations (not open to users). The operator and administrator rights restrictions...
GMC-P7 4. Menu Click menu, can check and modify the parameters Under the menu interface, can check the version information of the controller software and scan the QR code on the right to download user’s manual.
GMC-P7 4.1 Recipe parameter In【Home】interface press recipe parameter, display recipe interface: Can switch recipe ID at left side. Click sub option button at right side, enter correspond interface, set parameter information. Click upper left corner, esc current interface back to superior interface.
Page 16
GMC-P7 When in the process of discharging,if weight≤Near Zero, Near Zero then start the discharge delay timer. Band Initial value:0; range: 0~full scale Used to set time - related delay timer parameters in the feeding process...
Page 17
GMC-P7 quantitative process or input emergency stop signal to clear the alarm and return to the stop state. Over/Under test is turn to ON, after “Result Waiting Timer” Over/Under finish,when hopper is stable, starts Over/Under test and output Alarm Over/UnderAlarm Timer,when time up enter discharge.
GMC-P7 Group ID current formula Motor Group This parameter used filling Motor Para. Group ID. Initial value:0,range:0~4 4.2 Weight parameter In the menu interface, click the【Weight】 to enter the current parameter to view and set...
Initial value:0;range:0~99 4.3 Calibration The calibration scale is the calibration of the controller. When the GMC-P7 bulk scale controller or any part of the weighing system is changed for the first time and the current equipment calibration paracontrollers cannot meet the user's requirements, the controller should be calibrated.
Page 20
GMC-P7 Weight calibrate and Theoretical Calibrate Press top left corner,esc current interface back to superior interface. Calibration Description parameter Unit Initial value is available. :kg;g/kg/t/lb decimal Initial value 0~0.0000 is available. : ;...
4.4 COM Para. GMC-P7 can provide two serial communication interfaces. For the connection of serial 2.5. You can select COM Para. On the [Maintenance] interfaces, please refer to Section –[Communication] page,For serial ports 1 and 2, you can choose modbus-RTU, print,...
GMC-P7 Port No. Initial value:502; 0~65535 IP address Initial value:192.168.101.246; 0~255 MAC address BC.66.41.9X.XX.XX ON/OFF,Initial value:OFF. When choose“ON” When the packaging is completed, the packaging Auto Print result will be automatically printed (serial port is required and select "Print").
GMC-P7 4.4.2 Response Mode-1 Negative response: indicates that the command cannot be executed. The following types of negative responses are returned: ◆Command error (CE), STX address CE CRC CR LF, If the command is not in the Columns table or checksum error.
Page 24
GMC-P7 S SP SP None Read controller state Back to same command,refer example Description. None Command example, ◆read total ACUM, ACUM weight(R T SP SP) send format:02 30 31 52 54 20 20 32 39 0D 0A Controller respond,receive correct:...
GMC-P7 Stop, stable, GS state,weight value is 0.87. Note:when controller receive error,back to negative respond 4.4.3Response Mode-2 Send format refer Response Mode1 Response Mode-2 : function data Operation description code object Read total ACUM and ACUM weight...
GMC-P7 ◆read ACUM weight(R T SP SP):02 30 31 52 54 20 20 32 39 0D 0A respond: COM ID ACUM ACUM weight 30H 31H 4bit 9bit 返 回 eg : 02 30 31 52 54 20 20 20 34 2C 20 20 20 20 32 30 2E 33 31 32 39 0D 0A——ACUM4;ACUM weight:21.31...
Page 27
GMC-P7 30.2 30.0 29.7 -------------------------------------- -------------------------------------------- IN/OUT FINISH IN/OUT FINISH Current ACUM weight: 120.4kg Current ACUM weight: 90.6 kg -------------------------------------- ---------------------------------------------- 4.4.5.2ACUM PRINTING Under the parameter of formula accumulation in the 【 Statistics 】 interface, click 【Print】...
GMC-P7 4.4.5.4 User ACUM report Under the parameter 【User ACUM】 of the 【Statistics】 interface, click 【Print】 to select the items to be printed in the pop-up box, such as printing ACUM total, current user accumulative total, select user print and print all user accumulative total.
Page 29
GMC-P7 Illegal data The portion of data written and the allowed range. value An unrecoverable error occurs when the controller is Slave failure attempting to perform the requested operation. Unsuccessful For the controller, the received command cannot be executed programming under the current conditions.
Page 30
GMC-P7 Description 0 : stop; 1 : run Before feed CO-Fill Fi-Fill Result Waiting Over/Under test DISC 0001 40002 Operating state NearZero FILL Supplemant Empty Stock-in/out Done Last Feed OVER UNDER Stop reserved Description Supplement FULL...
Page 31
GMC-P7 Stable Judge Overtime scale unstable Target Error, Unable To Start Clear ACUM Before Next Discharge Gate Not Closed Feeding Gate Not Closed Feeding Gate Close Overtime Discharge Gate Open Overtime Discharge Gate Close Overtime...
Page 32
GMC-P7 Calibration Fail, No Gain Voltage Record ( The relative Gain Voltage is not calibrated when the weight is calibrated with None weight) Over&Under Pause Reserved .11~.15 0005 40006 Reserved 4 bytes, signed number (display Weight weight).
Page 33
GMC-P7 0151 40152 decimal 0:0bit;1:1bit;2:2bit;3:3bit;4:4bit 0152 40153 Resolution 1;2;5;10;20;50。 0153 40154 Load cell sensitivity 3:3mV/V(can not be changed) 0154-0155 40155-40156 Capacity≤Resolution×100000 When write is 1, the current Calibrate weight is regarded as zero, and 0156-0157...
Page 39
GMC-P7 0537~0599 40538~40600 reserved Motor Para. Feed Gate Drive 0:air drive,1 : motor drive 、 single 0600 40601 Mode Limit 0601 40602 Motor Group ID Feed Gate Open 0602 40603 0~9999 (0.0~99.99s) Timer(Co-F) Feed Gate Open...
Page 40
GMC-P7 0714-0715 40715-40716 User 2 ACUM weight high 6bit 0716-0717 40717-40718 User 2 ACUM weight low 9bit 0720-0721 40721-40722 User 3 ACUM weight high 6bit 0722-0723 40723-40724 User 3 ACUM weight low 9bit 0724-0725 40725-40726...
Page 41
GMC-P7 0774-0775 40775-40776 Recipe 3 ACUM weight high6bit 0776-0777 40777-40778 Recipe 3 ACUM weight low9bit 0778-0779 40779-40780 Recipe 4 ACUM 0780-0781 40781-40782 Recipe 4 ACUM weight high6bit 0782-0783 40783-40784 Recipe 4 ACUM weight low9bit 0784-0785...
Page 42
GMC-P7 0832-0833 40833-40834 Recipe 13 ACUM 0834-0835 40835-40836 Recipe 13 ACUM weight high6bit 0836-0837 40837-40838 Recipe 13 ACUM weight low9bit 0838-0839 40839-40840 Recipe 14 ACUM 0840-0841 40841-40842 Recipe 14 ACUM weight high6bit 0842-0843 40843-40844 Recipe 14 ACUM weight low9bit...
Page 44
GMC-P7 Write 1-20 clear ACUM data Clear recipe write 100 clear current recipe ACUM 0957 40958 ACUM write 101clear all recipe ACUM Read 0 Write 0-9 clear userACUM Write 100 clear current user Clear user...
Page 45
GMC-P7 All reset(do not 0072 00073 include calibration) Recipe 0073 00074 Para.reset 0074 00075 weight para reset 0075 00076 Motor Para.reset Calibration para 0076 00077 reset I/O Function self 0077 00078 defined reset 0078 00079 COM Para.reset...
Modbus-tcpaddress Refer to 4.4.6.3 modbus Address assignment. 4.5 I/O Function The GMC-P7 provides 12 inputs and 16 outputs interfaces to connect the controller with external devices. The input and output factory definition contents are as follows output 1 - 16 corresponds to the controller OUT1 ~ OUT16 interface, input 1 - 12 corresponds to the controller IN1 ~ 12 interface),...
Page 48
GMC-P7 feeding, current weight lower than Target-Free fall, this signal is valid. Result Waiting Used to indicate the end of the feeding process. This signal is valid until the end of fine feed. Over/Under This signal is valid when result waiting OVER or UNDER.
Page 49
GMC-P7 by serial port communication protocol Modbus. The output state of the I/O Function can be controlled Remote Ctr Output5 by serial port communication protocol Modbus. The output is valid during feeding period and invalid...
Page 50
GMC-P7 This input is valid once, and the Recipe ID changes to the next Recipe whose Target is not zero, skipping the Change Recipe Recipe ID whose Target is zero. Returns 1 if the Recipe ID is greater than 20.
GMC-P7 The signal is valid, discharge output is valid; Discharge Manual DISC(LS) Outputs invalid. The input is respond only under stop state. This input is valid once controllerFine feed output is Manual Fi-Fill valid; Again, the ControllerFine Feed outputs invalid The ControllerFine feed output is valid when the signal Manual Fi-Fill(LS)...
GMC-P7 connection of the I/O Function. 4.6 Statistics In the main interface, click 【 statistic 】 to enter the statistics interface. View recipe ACUM, userACUM, in&outACUM, change in&OUT mode, clean ACUM, print ACUM, etc. Under 【 Recipe ACUM 】 , switch between 1-8, 9-16, 17-20 Recipe ID to check the ACUM and ACUM weight for each Recipe ID.
Page 53
GMC-P7 Para. Initial value:Air Drived. 1. Feed Gate Air Drived:air drive control feed gate ON/OFF; Drive Mode Motor Drived:General motor control feeding door ON and OFF (1 limit bit: OFF threshold bit) The following parameters are the feeding parameters of " Motor Drived "...
GMC-P7 Discharge control mode set to “Normal Motor(One Pos.)” ,2/3/4/5 para can be set; Discharge control mode set to “Normal Motor(Two Pos.)” ,2/3/4/6 para can be set; Discharge control mode set to“Normal Motor Rotating”, 2/3/4/5 para can be Initial value:ON:If Closed:。...
GMC-P7 fine feed process:When material weight in hopper≥Target-Co-Feeding Remains, ● O22 gate close signal output valid,valid time is“Feed Gate Open Timer(Co-F) - Feed Gate Open Timer(Fi-F)”. Feed close:When material weight in hopper≥Target-Free fall,O22 gate close ●...
GMC-P7 Open signal(O23)and Alarm. ● DISC Gate Close process: After discharge is finish, output DISC Gate close signal (O24),control discharge motor turn to discharge gate close,until detect DISC Gate Closed Pos.(I27)input valid then stop output DISC Gate close signal(O24),DISC gate is close state.
Page 57
GMC-P7 4.4 COM Para. ) ACUM Password Clear ACUM password can be set separately for Management management. Permission Auto Permission post-set time. 5 mm/10 mm 20/ mm /30 Logout Multiple User Multi User Management function ONOFF,can set Acess ON-OFF User Management No.
GMC-P7 5. Flowrate Function 5.1 Real-time Flowrate Flowrate calculation principle: Everytime when start, make note for turn on time t0,start feeding, till empty finish a whole process. Set discharge value as DiscVal(1). Before start the second process, make note the second start time t1,then will know the time of dT(1),start the second feeding.
GMC-P7 5.2 Expected Flowrate Function Description When “Expected Flowrate” function is turn ON, when controller running will compute the conversion based on the“Expected Flowrate value”and“Target”,Calculate the time required to process a feeding process, then controller waits until the calculated time is up before start discharge.
GMC-P7 5.3 Supplement Control Application situation is different, packing scale hopper material level device installation is divided into three situations, triple supplement (Supplement Full, OK, Empty), double supplement (Supplement Full, Empty), single supplement (Supplement Empty) and none supplement.
No 'to exit" pops up;Click "Yes" and the "User Project Update" button pops up Click "user project update" button, select GMC-P7 engineering began to download Download success, restart automatically 5.4.2 Background upgrade steps Steps as follow:...
Page 63
GMC-P7 The controller pops up the display box of [Equipment vendor USB disk kit], and select "Update startup bitmap". Enter the LOGO selection interface, select the image to be upgraded, and click OK. It will prompt you to restart after successful bitmap update...
Page 64
GMC-P7 6. Bulk ACUM process GMC-P7 bulk scale controller in running state can auto control coarse, fine feed material, discharge material all metering ACUM process.Two working mode: Receipt mode and Delivery mode. In stop state,user click statistics enter statistics in&out interface.
Page 65
GMC-P7 Process description as follow: Process Description: Set Target none 0,input start signal,judge supplement Empty Start signal,if signal OFF,wait till ON. Filling PreDelay Timer Dela If I/O Function input defined“Fill-Go”, need to input Fill-Go ON , wait Feedling Start Delay finish,start filling;if not Fill-Go define“Fill-Go”,no need to wait Fill-Go start filling.
Page 66
GMC-P7 OVER/UNDER judged as auxiliary function,if Recipe OVER/UNDER Para.funtion is OFF,after WAIT do not respond,enter discharge. DISC 1)judge weight:material≤Near Zero; 2)start“Discharge Delay Timer”; 3) judge last scale, if yes Alarm remind “DeliveryDone” ,if Back to Zero not start next scale“Feedling Start Delay”.