Toshiba MMU-UB0071HP-UL Engineering Data Book
Toshiba MMU-UB0071HP-UL Engineering Data Book

Toshiba MMU-UB0071HP-UL Engineering Data Book

4 - way cassette type

Advertisement

Quick Links

Tentative
Engineering Data Book
4 - Way Cassette Type
MMU-UB0071HP-UL
MMU-UB0091HP-UL
MMU-UB0121HP-UL
MMU-UB0151HP-UL
MMU-UB0181HP-UL
MMU-UB0241HP-UL
MMU-UB0301HP-UL
MMU-UB0361HP-UL
MMU-UB0421HP-UL
MMU-UB0481HP-UL
MMU-UB0541HP-UL
RBC-U32PGP-UL
RBC-U33P-UL
RBC-U33PB-UL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MMU-UB0071HP-UL and is the answer not in the manual?

Questions and answers

Summary of Contents for Toshiba MMU-UB0071HP-UL

  • Page 1 Tentative Engineering Data Book 4 - Way Cassette Type MMU-UB0071HP-UL MMU-UB0091HP-UL MMU-UB0121HP-UL MMU-UB0151HP-UL MMU-UB0181HP-UL MMU-UB0241HP-UL MMU-UB0301HP-UL MMU-UB0361HP-UL MMU-UB0421HP-UL MMU-UB0481HP-UL MMU-UB0541HP-UL RBC-U32PGP-UL RBC-U33P-UL RBC-U33PB-UL...
  • Page 2: Table Of Contents

    INVERTER MULTI SYSTEM R32 INVERTER MULTI SYSTEM R32 Engineering Data Book Engineering Data Book Residential Fix Speed R410A Residential Inverter Heat Pump [ Premium SHORAI ] Engineering Data Book Engineering Data Book MMU-UB___1HP-UL TCTC-E24-VRF005 Contents Specifications ..........Dimensions .
  • Page 3: Specifications

    MMU-UB___1HP-UL TCTC-E24-VRF005 1. Specifications Model name MMU- UP0091HP-UL UP0121HP-UL UP0151HP-UL UP0181HP-UL UP0071HP-UL Power supply 1 ph 60Hz 230V (208 / 230V) Cooling capacity (*1) kBtu/h 12.0 15.4 18.0 Sensible cooling capacity (*1) kBtu/h 12.0 12.8 Heating capacity (*1) kBtu/h 10.5 13.5 17.0 20.0...
  • Page 4 MMU-UB___1HP-UL TCTC-E24-VRF005 Model name MMU- UP0241HP-UL UP0301HP-UL UP0361HP-UL UP0421HP-UL UP0481HP-UL UP0541HP-UL Power supply 1 ph 60Hz 230V (208 / 230V) Cooling capacity (*1) kBtu/h 24.0 30.0 36.0 42.0 48.0 54.0 Sensible cooling capacity (*1) kBtu/h 16.5 20.6 24.7 29.4 33.6 37.8 Heating capacity (*1) kBtu/h...
  • Page 5: Dimensions

    MMU-UB___1HP-UL TCTC-E24-VRF005 2. Dimension MMU-UB*___1HP-UL (*007 / 009 / 012 / 015 / 018 / 024 / 030) (Unit : in(mm))
  • Page 6 MMU-UB___1HP-UL TCTC-E24-VRF005 MMU-UB*___1HP-UL (*036 / 042 / 048 / 054) (Unit : in(mm))
  • Page 7: Center Of Gravity

    MMU-UB___1HP-UL TCTC-E24-VRF005 3. Center of gravity Total weight Model name X (in) Y (in) Z (in) Ceiling panel Main unit (Ibs) (Ibs) MMU-UB0071HP-UL 18.5 17.9 MMU-UB0091HP-UL MMU-UB0121HP-UL MMU-UB0151HP-UL 18.5 17.9 MMU-UB0181HP-UL MMU-UB0241HP-UL MMU-UB0301HP-UL MMU-UB0361HP-UL MMU-UB0421HP-UL 18.5 17.7 MMU-UB0481HP-UL MMU-UB0541HP-UL Center of gravity...
  • Page 8: Piping Diagram

    MMU-UB___1HP-UL TCTC-E24-VRF005 4. Piping diagram MMU-UB*___1HP-UL (*007 / 009 / 012 / 015 / 018 / 024 / 030 / 036 / 042 / 048 / 054) Liquid side Gas side Strainer Capillary Tube Air heat exchanger Pulse Motor Valve Distributor Sensor (TCJ)
  • Page 9: Wiring Diagram

    MMU-UB___1HP-UL TCTC-E24-VRF005 5. Wiring diagram MMU-UB*___1HP-UL (*007 / 009 / 012 / 015 / 018 / 024 / 030 / 036 / 042 / 048 / 054)
  • Page 10: Electrical Current Characteristics

    MMU-UB___1HP-UL TCTC-E24-VRF005 6. Electrical current charateristic Indoor unit power supply Normal Voltage Voltage Range (V) MOCP Type Model name (V-Ph-Hz) Min. Max. MMU-UB0071HP-UL 208/230-1-60 0.63 0.79 MMU-UB0091HP-UL 208/230-1-60 0.63 0.79 MMU-UB0121HP-UL 208/230-1-60 0.80 1.00 MMU-UB0151HP-UL 208/230-1-60 0.80 1.00 MMU-UB0181HP-UL 208/230-1-60 0.80...
  • Page 11: Sensible Capacity Table

    MMU-UB___1HP-UL TCTC-E24-VRF005 7. Sensible capacity table 4-way cassette type (MMU-UB*__1HP-UL) Indoor air temp. unit outdoor 59 ゚FWB 61 ゚FWB 64 ゚FWB 67 ゚FWB 68 ゚FWB 72 ゚FWB 75 ゚FWB size air temp. 71 ゚FDB 73 ゚FDB 77 ゚FDB 80 ゚FDB 82 ゚FDB 86 ゚FDB 90 ゚FDB...
  • Page 12 MMU-UB___1HP-UL TCTC-E24-VRF005 4 way cassette Type (MMU-UB*__1HP-UL) Indoor air temp. unit outdoor 59 ゚FWB 61 ゚FWB 64 ゚FWB 67 ゚FWB 68 ゚FWB 72 ゚FWB 75 ゚FWB size air temp. 71 ゚FDB 73 ゚FDB 77 ゚FDB 80 ゚FDB 82 ゚FDB 86 ゚FDB 90 ゚FDB ゚FDB 12640...
  • Page 13 MMU-UB___1HP-UL TCTC-E24-VRF005 4 way cassette Type (MMU-UB*__1HP-UL) Indoor air temp. unit outdoor 59 ゚FWB 61 ゚FWB 64 ゚FWB 67 ゚FWB 68 ゚FWB 72 ゚FWB 75 ゚FWB size air temp. 71 ゚FDB 73 ゚FDB 77 ゚FDB 80 ゚FDB 82 ゚FDB 86 ゚FDB 90 ゚FDB ゚FDB 30640...
  • Page 14 MMU-UB___1HP-UL TCTC-E24-VRF005 Heating capacity table Indoor air temp. °FDB Fahrenheit (°F) Celsius (°C) 16.7 18.3 21.1 22.2 23.9 Total capacity (TC) (kBtu/h) MMU-UB0071HP-UL MMU-UB0091HP-UL 11.0 10.8 10.6 10.5 10.4 10.1 MMU-UB0121HP-UL 14.1 13.9 13.7 13.5 13.3 13.0 MMU-UB0151HP-UL 17.8 17.5 17.2...
  • Page 15: Air Throw Distance Chart

    MMU-UB___1HP-UL TCTC-E24-VRF005 8. Air throw distance chart MMU-UB*___1HPUL (*007 / 009) 9.18 2.3 ft/s 1.64 ft/s 0.98 ft/s 3.28 6.56 9.84 13.1 16.4 Horizontal distance (ft) MMU-UB*___1HP-UL (*012 / 015 / 018) Adv. wind speed : 14.1 ft/s 9.18 2.3 ft/s 1.64 ft/s 0.98 ft/s 3.28...
  • Page 16 MMU-UB___1HP-UL TCTC-E24-VRF005 MMU-UB0361HP-UL Adv. wind speed : 17.7 ft/s 12.8 2.3 ft/s 1.64 ft/s 0.98 ft/s 3.28 6.56 9.84 13.1 16.4 Horizontal distance (ft) MMU-UB*___1HP-UL (*042 / 048 / 054) Adv. wind speed : 28.5 ft/s 12.8 2.3 ft/s 1.64 ft/s 0.98 ft/s 3.28 6.56...
  • Page 17: Sound Data

    MMU-UB___1HP-UL TCTC-E24-VRF005 9. Sound data Sound pressure spectrum 4.92 ft (1.5 m) Microphone MMU-UB0121HP-UL / UB0151HP-UL / UB0181HP-UL MMU-UB0071HP-UL / UB0091HP-UL Specification (dB) Specification (dB) Fan tap Fan tap Sound pressure Sound pressure 32.5 30.5 level (dB(A)) level (dB(A)) NC-70...
  • Page 18 MMU-UB___1HP-UL TCTC-E24-VRF005 MMU-UB0421HP-UL / UB0481HP-UL / UB0541HP-UL MMU-UB0361HP-UL Specification (dB) Specification (dB) Fan tap Fan tap Sound pressure Sound pressure 36.5 40.5 36.5 level (dB(A)) level (dB(A)) NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Audibility limits of Audibility limits of NC-20 NC-20...
  • Page 19: Accessories

    MMU-UB___1HP-UL TCTC-E24-VRF005 10. Accessories (Unit : in(mm)) Optional parts for 4-Way Cassette type RBC-U32PGP-UL Ceiling panel RBC-U33P-UL Ceiling panel (smart design) RBC-U33PB-UL Type Model name Qty/unit Note Ceiling panel RBC-U32PGP-UL White (2.5GY9.0/0.5) Ceiling panel (smart design) RBC-U33P-UL White (5PB9/1) Ceiling panel (smart design) RBC-U33PB-UL Black (Black 3C) Spacer for height adjustment...
  • Page 20: Appendix

    MMU-UB___1HP-UL TCTC-E24-VRF005 Appendix 1. Ceiling Panel 1.1 Ceiling Panel : RBC-U32PGP-UL Brand name indication given at factory shipping Adjust corner cap * Can be attached at any location. Refrigerant Indoor unit electrical control box pipe side Wireless receiver kit (separate sold parts) * Can be installed only at this location.
  • Page 21 MMU-UB___1HP-UL TCTC-E24-VRF005 1.3 Ceiling Panel ( Smart design: Black ) : RBC-U33PB-UL Mounting position for adjust corner cap with company name at factory default. (The corner cap can be installed at any position when not using the Wireless receiver kit The Wireless receiver kit (separate sold parts) •...
  • Page 22 MMU-UB___1HP-UL TCTC-E24-VRF005 2. Spacer for height adjustment (TCB-SP1602UUL) Unit: in (mm) Refrigerant pipe connecting port (Liquid) Drain pipe connecting port Refrigerant pipe connecting port (Gas) Ceiling bottom surface 39.4” (1000) or more 39.4” (1000) or more 37.8" (960) 2.0" (50) Material : Styrene foam Color : Moon white...
  • Page 23 MMU-UB___1HP-UL TCTC-E24-VRF005 3. Fresh-air chamber (TCB-GFC1602UUL) Unit: in (mm) Refrigerant pipe connecting port (Liquid) Refrigerant pipe Drain pipe connecting port connecting port (Gas) 33.3" (846) 27.8" (705) 4.4" (113) 24.8" (630) Ceiling bottom surface 39.4" (1000) or more 39.4" (1000) or more 24.8"...
  • Page 24 MMU-UB___1HP-UL TCTC-E24-VRF005 4. Fresh-air inlet box (TCB-GB1602UUL) Accessories Installation (The following parts are included.) (Fig. 1) Name Remark Shield plate for box (6) Heat insulating (Remove) material B Outside air introduction port Outside air (5) Heat insulating material A introduction port fixing metal part Duct flange Ø3.9"...
  • Page 25 MMU-UB___1HP-UL TCTC-E24-VRF005 6. Air discharge direction kit (TCB-BC1602UUL) Limited models only Wind shield A 3-way air flow Wind shield C Available only for Available only for Available for all models Available for all models 007 to 030 type 036 to 054 type Wind shield A 2-way air flow Wind shield C...
  • Page 26 MMU-UB___1HP-UL TCTC-E24-VRF005 7. Auxiliary fresh air flange (TCB-FF101URUL) Installation Duct fan 1. Using the knockout of the indoor unit main body, as a In order to take fresh air, provide the duct fan marker, cut off the flange with the heat insulator separately.
  • Page 27 CARRIER AIR CONDITIONING (THAILAND) CO.,LTD. 144/9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand Copyright © 2024 CARRIER AIR CONDITIONING (THAILAND), All Rights Reserved Notice : Carrier is committed to continuously improving its prod ucts to ensure the highest quality and reliability standard, and to meet local regulations and market requirements.

This manual is also suitable for:

Mmu-ub0091hp-ulMmu-ub0121hp-ulMmu-ub0151hp-ulMmu-ub0181hp-ulMmu-ub0241hp-ulMmu-ub0301hp-ul ... Show all

Table of Contents