CAUTION!!! Read these instructions carefully before installing, starting, using or maintaining this appliance. INSTALLATION, USE AND MAINTENANCE MANUAL AGUADENS H GAS WALL-MOUNTED CONDENSING HOT WATER HEATER 62403968 - R02 17-03-2025_UK - INGHILTERRA - COSMOGAS...
6.6 - Controlling the supply gas pressure and any adjustments ..................43 6.7 - Checking the level of CO2 and making any adjustments ..................44 6.8 - Adjusting the domestic hot water flow rate ......................45 6.9 - Checking the maximum heat input ......................... 45 AGUADENS H COSMOGAS...
Page 3
8.22 - Wiring diagram ..............................70 9 - TECHNICAL DATA ............................72 10 - PRODUCT FILE ............................74 11 - COMMAND MENU DIAGRAM ........................75 12 - ADVANCED SETTINGS MENU ........................76 13 - NOTES ................................80 14 - EU DECLARATION OF COMPLIANCE ......................83 COSMOGAS AGUADENS H...
Do not leave parts of the packaging and any instructions given by the manufacturer or with replaced parts within the reach of children. applicable national and/or local laws. AGUADENS H COSMOGAS...
This means that the content of dissolved salts (responsible for the formation of scale inside the heat exchanger), can continuously vary in an uncontrolled manner. For this reason, damage caused by scale deposits, inside the heat exchanger, is not covered by the product warranty. COSMOGAS AGUADENS H...
Congratulations! You have chosen an outstanding product, among the most innovative and reliable currently available on the market. Each unit is the result of COSMOGAS’s expertise and experience, designed, manufactured, and tested with the utmost care in our own facilities.
This manual uses the following acronyms: terms of Community Directive 2012/19/EU. N/A: Not applicable. For further information regarding correct decommissioning DHW: Domestic hot water. of these appliances, users can contact the public service in charge or retailers. COSMOGAS AGUADENS H...
Key of Figure 4-2 A = AGUADENS 16H B = AGUADENS 22H C = AGUADENS 37H Water flow rate (l/min) Figure 4-2 – Domestic hot water head losses curve COSMOGAS AGUADENS H...
Figure 4-3 - Example of system without recirculation Figure 4-4 - Example of system with recirculation and external pump (see section 5.12) Figure 4-5 - Example of system with storage tank (section 5.13) AGUADENS H COSMOGAS...
Page 15
Figure 4-6 – Example of system with solar panels and storage tank (Section 5.13) Figure 4-7 – Example of system with solar panel Figure 4-8 – Example of incorrect installation with natural circulation (maximum temperature of the appliance water is 85°C). COSMOGAS AGUADENS H...
3 - 3/4" gas inlet 4 - 3/4" cold water inlet Figure 5-2 – Dimensions and attachments centre-to- 5 - Flue gas outlet / Air intake 6 - Support attachments centre distances 7 - Ø20 condensate drain Models 16H and 22H AGUADENS H COSMOGAS...
(Figure 5-4). Choose a place sheltered from the weather and from frost. It must not be exposed to temperatures below 0.5°C and above 50°C. AGUADENS H Combustion air flow rate G20 m3/h Combustion air flow rate G31 m3/h Figure 5-4 key –...
4.- remove the paper template (where present); 5.- make holes “A” and insert the wall plugs “B”; 6.- make the appliance hydraulic and gas connections; 7.- hang the appliance on the plugs “C”; 8.- make the hydraulic connections. Figure 5-5 – Support plugs AGUADENS H COSMOGAS...
There is no input for stopping the burner for this purpose; the main power supply to the appliance must be cut. Insert a closing cock before the cold water inlet, useful for maintenance work. COSMOGAS AGUADENS H...
It is prohibited to drain into gutters or rainwater drainpipes. CAUTION!!! The condensate drain must slope continuously towards the drain point; avoid high points, which could pressurise the pipe. 020002.01.017 Figure 5-6 – Condensate drain pipe AGUADENS H COSMOGAS...
Figure 5-8 – Water and gas connections for AGUADENS 37H (on request) min10 mm max 30 mm 020002.01.028 Figure 5-9 – F = Condensate drain pipe G = anti-odour syphon (on request) Figure 5-10 – Example of typical full installation COSMOGAS AGUADENS H...
Key for Figure 5-12 A = AGUADENS 16H and 22H B = AGUADENS 37H Water flow rate (l/hr) Figure 5-12 – Residual head of recirculation circuit with internal pump curve COSMOGAS AGUADENS H...
13 - Check valve 14 - Recirculation pump (where present) 15 - Expansion tank 16 - Polyphosphate softener (on request); * The recirculation line is not compulsory. Figure 5-13 – Hydraulic connection to storage tank AGUADENS H COSMOGAS...
CAUTION!!! The appliances installed in type C43 must only be connected to natural-draught flues. CAUTION!!! With C43 exhausts, the condensate coming from the chimney cannot be conveyed into the appliance. Figure 5-14 – Outlet/intake systems COSMOGAS AGUADENS H...
- Be constructed in such a way that the opening inlets both inside and outside the wall cannot be blocked; - Be protected, for example with grids, mesh, etc. The net passage cross-section must not be reduced by these systems; AGUADENS H COSMOGAS...
Figure 5-16 – Overall dimensions sheath. CAUTION!!! If the air intake and flue gas outlet terminals are positioned on the same wall, they must remain at a minimum distance of 1 metre. Figure 5-17 – Fixing the outlet and intake pipes COSMOGAS AGUADENS H...
CAUTION!!! If the air intake and flue gas outlet terminals are positioned on the same wall, they must remain at a minimum distance of 1 metre. Figure 5-20 – Fixing the outlet and intake pipes AGUADENS H COSMOGAS...
- outlet on the outside, directly via the appliance pipes with condensate collection inside the appliance itself. The intake must slope towards the outside to prevent rain water entering. Figure 5-21 – Example of “80/80 PP system” installation Figure 5-22 – Example of “80/80 PP system” installation AGUADENS H COSMOGAS...
9. Every 45° bend has a loss equivalent to the value in section 9. Figure 5-24 – Measurements and centre space distances for coaxial outlet preinstallation hole Figure 5-25 – Positioning the coaxial pipe COSMOGAS AGUADENS H...
9. Every 45° bend has a loss equivalent to the value in section 9. Figure 5-27 – Measurements and centre space distances for coaxial outlet preinstallation hole Figure 5-28 – Positioning the coaxial pipe AGUADENS H COSMOGAS...
To this end, it must be installed under sloping roofs (or ledges, balconies or other suitable protection) with the minimum dimensions shown in Figure 5-29. Figure 5-29 – Examples of coaxial pipe installation AGUADENS H COSMOGAS...
9. Every 45° bend has a loss equivalent to the value in section 9. Figure 5-31 – Measurements and centre space distances for coaxial outlet preinstallation hole Figure 5-32 – Positioning the coaxial pipe COSMOGAS AGUADENS H...
To this end, it must be installed under sloping roofs (or ledges, balconies or other suitable protection) with the minimum dimensions shown in Figure 5-33. Figure 5-33 – Examples of coaxial pipe installation COSMOGAS AGUADENS H...
CAUTION!!! The temperature of the outlet pipe can reach 90°C during operation. If the pipe passes through walls that are sensitive to these temperatures, insert a protective heat-insulating sheath. Figure 5-35 – Measurements and centre space distances for single exhaust preinstallation hole AGUADENS H COSMOGAS...
CAUTION!!! If the appliance remains off for more than 3 months, the siphon must be filled again as explained above. Figure 6-1 – Filling the condensate drain siphon Models 16 and 22. 020008.01.023 Figure 6-2 – Filling the condensate drain siphon Model COSMOGAS AGUADENS H...
2. - Ventilate the room; 3 - From another room, or from a neighbour’s property, immediately call a professionally qualified technician or the gas supply company. Call the Fire Service if the former are not available. AGUADENS H COSMOGAS...
3 - From another room, or from a neighbour’s property, immediately call a professionally qualified technician or the gas supply company. Call the Fire Service if the former are not available. 020022.01.008 020002.01.042 Figure 6-5 – Replacing the gas nozzle and checking correct OR position COSMOGAS AGUADENS H...
12.- check for any gas leaks at the pressure point using suitable tools. WARNING!!! Test the gas seal using a soap and water solution only. Strictly no open flames. 020003.01.023 A- Gas inlet tapping point. Figure 6-9 – Gas valve COSMOGAS AGUADENS H...
17.- once the check has been completed, seal screw “B” (Figure 6-12) with red paint or a similar method; 18.- go into the “installer” menu (Section 7.8); 2010 19.- set parameter 020002.01.045 Figure 6-12 – Labels certifying the new appliance status AGUADENS H COSMOGAS...
“Technical Data” section, in Section 9; c) check that the heat exchanger and the burner are clean (Section 8.5). 020003.01.055 Figure 6-13 – Domestic hot water flow rate selector switch (“A”) COSMOGAS AGUADENS H...
U - Indicator of number of lockouts occurred in last 15 minutes V - Fan (fan is on when icon showing) X - Sparks (icon shows when burner ignition sparks switch on) Y - Valve (valve powered when icon showing) AGUADENS H COSMOGAS...
40°C to 60°C. By pressing and holding the key down even below 40°C, the message “ ” appears to indicate that the domestic hot water service is being switched off. The icon “F” (Figure 7-1) also switches off. COSMOGAS AGUADENS H...
1055 Number of failed ignition attempts Value 1056 Time between last two lockouts (Loc) 1: mins 2: hours 3: days 4: weeks 1057 Time between last two errors (Err) 1: mins 2: hours 3: days 4: weeks AGUADENS H COSMOGAS...
Page 49
* How to read the values of parameters 1056 and 1057: E.g. If it shows 1:29, it means 29 minutes; E.g. If it shows 2:12, it means 12 hours; E.g. If it shows 3:15, it means 15 days; E.g. If it shows 4:26, it means 26 weeks. COSMOGAS AGUADENS H...
Pressing the RESET OFF = Inactive; button again returns the display to normal operation. 2020 Climatic - Heating stop spring temperature °C 0-35 2021 Climate - Outside winter temperature °C -30-25 2022 Climate - Winter heating temperature °C 20-93 AGUADENS H COSMOGAS...
Page 51
Drying temperature holding time Hours 24-120 2107 (N/A) (N/A) (N/A) (N/A) 2108 (N/A) (N/A) (N/A) (N/A) 2109 (N/A) (N/A) (N/A) (N/A) 2110 (N/A) (N/A) (N/A) (N/A) 2111 DHW maximum continuous drawing time 0-24 N/A = Not applicable; COSMOGAS AGUADENS H...
Bleed the air if necessary. Loc 06 Flue gas overheat Check for any residue in the combustion chamber In the event of any residues, see section 8.5. If the issue is not solved, replace the primary heat exchanger. AGUADENS H COSMOGAS...
Page 53
In the event of any residues, see Section 8.5. detected during normal Check detection electrode integrity Replace if necessary. operation Check the spark generator is not short-circuited Check that there are no leaks from the gas valve COSMOGAS AGUADENS H...
Page 54
Check parameter 3001 is set to 0 Restore if necessary. cascade parameters Loc 54 Invalid delivery Check parameter 3001 is set to 0 and 3231 is set to 1 Restore if necessary. configuration N/A = Not applicable. AGUADENS H COSMOGAS...
Low flow rate in heating circuit (N/A) Err 115 DHW sensor circuit open Check that the electrical resistance of the sensor Replace if necessary. matches the graph in Section 8.21. Check the sensor is connected correctly Restore if necessary. COSMOGAS AGUADENS H...
Page 56
Restore if necessary. switch divider on master board Err 130 Flapper blocked open Check that 3006 = 1 Restore if necessary. Err 131 Flapper blocked closed Check that 3006 = 1 Restore if necessary. N/A = Not applicable; AGUADENS H COSMOGAS...
WARNING!!! Before any maintenance work, disconnect the appliance from the electrical power supply, using the relevant switch nearby. WARNING!!! Before any maintenance operation turn off the gas cock. COSMOGAS AGUADENS H...
2.- in the event of obstructions in the drain pipe, clean the pipe; 3.- visually check that the component does not have any signs of corrosion, physical damage, water marks or signs of rust; 4.- in the event of damage as indicated above, replace the component; AGUADENS H COSMOGAS...
1.- check that after attempts to start the appliance, with the gas shut-off valve closed, the appliance goes into lockout Loc 07 mode and the message appears on the display; 2.- if the lockout message does not appear, replace the command and control board; COSMOGAS AGUADENS H...
To access the electrical connections board: 1.- turn the control panel “D” towards the front; 2.- slide cover “E” out using the closing flaps “F”. 020003.01.018 Figure 8-1 – Removing the casing and opening the control panel AGUADENS H COSMOGAS...
3.- disconnect cables “B” and the detection cable from the ignition electrodes (ref. “35” Figure 3-2) and the detection electrodes (ref. “15” Figure 3-1); 4.- unscrew the four nuts “E”; 5.- extract the assembly “F”; 020002.01.024 Figure 8-2 – Removing the burner-fan unit COSMOGAS AGUADENS H...
Figure 8-3 - Burner assembly CAUTION!!! Gasket “M” in Figure 8-3 seals the combustion chamber. If the gasket is damaged DO NOT reuse it; it must be replaced along with the burner unit. Consult the manufacturer for information on replacing it. AGUADENS H COSMOGAS...
8.- check for any gas leaks using the relevant tools; WARNING!!! Test the gas seal using a soap and water solution only. Strictly no open flames. Figure 8-4 – Positioning the electrodes on the burner 020025.01.004 Figure 8-5 – Removing the electrodes COSMOGAS AGUADENS H...
“H” (supplied in the kit) correctly in the kit; the one removed previously can be disposed of; 10.- fit the appliance back together by performing the operations above in reverse order; 11.- open the gas cock; 020003.01.072 020025.01.040 Figure 8-6 – Removing the gas valve AGUADENS H COSMOGAS...
3.- disconnect the exhaust pipe from the valve to be replaced “A”; 4.- unscrew the side nut “B” from the hydraulic unit, thus freeing valve “A”; 5.- remove safety valve “A” and replace it. 020003.01.067 Figure 8-12 – Removing the safety valve AGUADENS H COSMOGAS...
2010 in the “installer” menu (section 7.8). To appliance as possible. Check whether the system 2010 return to normal operating conditions, set downstream of the appliance can support this temperature. COSMOGAS AGUADENS H...
RESET. All parameters are now synchronised from du-bic until appears, confirm by pressing the command board to the display reset to the previous RESET. All parameters are now synchronised from the values. display to the command board reset to the previous values. AGUADENS H COSMOGAS...
2.- check the combustion efficiency at full load with maximum delivery temperature for the type of system in which it is used; 3.- check that the detected value exceeds regulatory requirements; Figure 8-13 – Water sensors curve COSMOGAS AGUADENS H...
Page 71
21 - 24V power supply followed by a number (see example above). 22 - Not used This is to identify the correct follow-on of 23 - ON/OFF enabling the cables on the next page. 24 - Not used COSMOGAS AGUADENS H...
Max. length of flue gas outlet duct (split) (60) Max. length of flue gas outlet duct (split) (50) Flue gas pipe max. length (coaxial) 80/125 Equivalent length of a bend 45° bend = 0.5 m, 90° bend = 1 m AGUADENS H COSMOGAS...
(l) Smart control factor Emissions of nitrogen oxides mg/kWh In agreement with European Ruling (EU) No 812/2013 and No 814/2013; * Related to other load profile (g); N/A = Not applicable; AGUADENS H COSMOGAS...
7 - Access to the “installer” menu (section 7.8); 8 - Example of “installer” menu parameters; 9 - Button to enter and confirm editing parameters; 10 - Editing parameters; 2004 11 - Example adjustment field of parameter COSMOGAS AGUADENS H...
6 = Hot water heater with flowmeter (N/A); 7 = Hot water heater with flowmeter; 8 = Micro tank without flow switch (N/A); 9 = Instant DHW with flow switch (N/A); 10 = Micro tank with flow switch (N/A); AGUADENS H COSMOGAS...
Page 77
Instant DHW PID D 0-255 3044 Minimum operating flow rate in l/min 0.1-20 instant DHW mode 3045 Parameter 3044 hysteresis value 0.1-5 3046 Maximum DHW temperature with °C 80-93 storage tank 3047 Parameter 3046 hysteresis value 0-20 COSMOGAS AGUADENS H...
Page 78
1 = External alarm supply; * “MF” contacts are powered when 2 = “MF” contacts are managed via external the instant DHW preheat function is Modbus parameters; active (3014 other than 0). 3 = Recirculation pump power supply; * AGUADENS H COSMOGAS...
14 - EU DECLARATION OF COMPLIANCE The undersigned sole director of company COSMOGAS s.r.l., with registered office in Via Leonardo Da Vinci no. 16 - 47014 Meldola (FC) Italy, DECLARES under its own responsibility that the instant hot water heater: SERIAL No.
Page 84
COSMOGAS s.r.l. Via L. da Vinci 16 - 47014 MELDOLA (FC) ITALY info@cosmogas.com www.cosmogas.com...