Page 1
SEAT 1080 m3/h The CONTROL E-SEAT controls the air extraction rate of a fume hood. It sends a 0/10v voltage to vary the frequency of a motor. A rotary sensor measures the height of the window sash and thus regulates the air flow. A speed sensor determines the flow rate, and an audible and visual alarm is triggered in case of insufficient speed, excessive sash height, or other malfunctions.
The backlit display shows face velocity, flow rate and system status. The B4 and B6 buttons are used to navigate through the menus and can also be configured to activate different functions. If the controller is connected to a CAPTUR E-SEAT controller, it can also be operated remotely.
1.2. CPU (Central Processing Unit) Output Relays Dry contact Inputs EC30 EC40 Analog output SA2 Sash position sensor Analog Output SA1 0-10V or 4-20mA Modbus link NC NO AL Power supply On / Off 100-230VAC VentilationVFD Alarm relay Light relay The CPU manage all the elements of the controller, it’s inside a protecting box that allows to attach it easily on the fume hood.
The remote HMI allows you to control the operation of the system and to make adjustments for each of the operating modes. Thanks to the MODBUS link, several CONTROL E-SEAT can be interconnected and the installation of a CAPTUR E-SEAT controller allows all air flows in the laboratory to be controlled.
2.2. Positioning on the fume hood Position sensor attached to the glass or counterweight Counterweight Setting up the HMI The HMI can be attached with screws to the top and bottom of the housing. First install the lower screw on the support, letting it protrude so that the HMI slides over it, then remove the upper cover with a small flat screwdriver to screw the upper part.
2.3. Installation Tips • Do not install the speed sensor in/on the extraction tube above the fume cupboard • Do not install the speed sensor in a fume hood dead zone • The speed sensor must not be subjected to aeraulic disturbances. •...
3. Detailed wiring Controller wiring: 0-10V MODBUS 1Ph 230V On / Off On / Off Supply light ventilation * If the sensor is positioned on the counterweight, reverse the green and brown wires on the AI1 terminal. 3.1. Terminal Block Specifications Power supply 230V.
Page 10
R40, R50, R60 Optional configurable relays (250VAC/2A). RS485-1 RS485 link with MODBUS protocol allows to connect 31 CONTROL E- SEAT and one CAPTUR E-SEAT. Communication speed: 9600 baud No parity, 1 bit stop, No flow control MODBUS Link wiring: CONTROL E-SEAT...
Wiring rules: The 0-10V links between the controller and the drive or motorized damper must be made with shielded cables. All low-voltage control cables (0-10V, linear sensor, probe, HMI, MODBUS link, etc.) must not run next to the power cables (230V, 400V power supply and motor and inverter cable). Cables connecting drives to motors can generate electromagnetic disturbances, these cables must be shielded, and the shield must be connected to the drive's grounding bracket.
A long press on will exit the installation menus. 4.2. Level 1 Menu (Code 100) POWER On/Off Btn (default) Push-button on/off MODE Forced/Time Forced Mode or Programmed Duration Then choose the operating time (OPERAT. TIME) 0 min => Forced mode Other duration =>...
4.3. Level 2 Menu (Code 200) MISC. CTRL VERSION Displays the hard and soft version HMI VERSION Displays the HMI version DEFAULT CFG Allows you to reset settings to factory configuration SAVE->SSTICK Allows you to save settings in a SmartStick MANUAL SETUP Warning ! setting using parameter number.
The potentiometer is not used in this mode of operation. The probe allows you to monitor the frontal speed and alert the user in case of insufficient speed. The speed display in this mode is simplified: SEAT SEAT SEAT SEAT <0,50 m/s...
Page 15
The low speed (LoSp) is set first (window at minimum height): 0,67 m/s LoSp:20 %V The speed measured by the sensor is displayed at the top and the output voltage SA1 is displayed at the bottom. Press the button to adjust the output voltage to get enough frontal velocity on your anemometer.
When the glass is raised, a higher extraction flow rate is activated to ensure sufficient frontal velocity. The speed sensor allows you to monitor the frontal speed and alert the user in case of insufficient speed. Speed and flow rate display are available: SEAT SEAT SEAT 0,50 m/s 920 m3/h...
Page 17
When the frontal speed given by the anemometer is correct, confirm your choice by pressing the red button Then press the Up button to switch to the high-speed setting (HiSp) and mount the window up to the working height (400 or 500mm). 0,43 m/s HiSp:80 %V Press the button...
The speed sensor allows you to monitor the frontal speed and alert the user in case of insufficient speed. Speed and flow rate display are available: SEAT SEAT SEAT 0,50 m/s 920 m3/h...
Page 19
The question mark will be displayed and you can change the output voltage with the Up and Down buttons . 20% corresponds to an output voltage of 2.0V. When the frontal speed given by the anemometer is correct, confirm your choice by pressing the red button Then press the Up button to switch to the High Speed (HiSp) setting and mount the...
The extraction rate can be chosen according to the height of the glass measured at 4 operating points. The speed sensor allows you to monitor the frontal speed and alert the user in case of insufficient speed. Speed and flow rate display are available: SEAT SEAT SEAT 0,50 m/s 920 m3/h...
Page 21
The question mark will be displayed and you can change the output voltage with the Up and Down buttons . 20% corresponds to an output voltage of 2.0V. When the frontal speed given by the anemometer is correct, confirm your choice by pressing the red button Then press the Up button to switch to the next speed setting and mount the glass to the...
5.6 B modes The 2 Speed EC2 B, 2 Speed AI1 B, Linear AI1 B and Multi-Speed B modes follow the operation of the modes described in paragraphs 5.2 to 5.5 but have an additional functionality: If the front speed measured by the sensor is 0.1 m/s lower than the setpoint, then the controller automatically switches the 0-10V output to high speed (HiSp or Sp4) for a duration of 30 seconds.
Diagnostic 6.1 Key Combination The following key combinations are used to check the operation of the controller and to view the different analog speeds and outputs. Touches Display Description Ref: Setpoint speed entered in the Ref:0.50 m/s installation menu. Dsp:0.48 m/s Dsp: Displayed speed (corrected) Long press Ssp: Sensor Measured Velocity...
If the emergency is activated by the CAPTUR E-SEAT card, it must first be stopped on the CAPTUR E-SEAT card. This error is communicated by the CAPTUR E-SEAT card, which The HMI indicates a problem of indicates that the total flow rate extracted is too high.
Page 25
Indicates a guillotine overshoot (window too high). This height The HMI displays "SASH HIGH" can be adjusted by adjusting the thresholds. or "SASH OPEN" Choose the Adjustd Spd measurement display mode. Then enter The displayed speed is incorrect the set value given by your anemometer at working height SPEED REF.
Guarantee SEAT Ventilation guarantees that its equipment, products and parts are free from manufacturing defects under normal conditions of use for a period of two years after delivery to the first user. If a factory return is required within the two-year period from the date of purchase, contact your distributor.
Notes Company / Site Laboratory Extractor CAPTUR E-SEAT MODBUS Address Installation date Power Control Display Buzzer delay Purge delay Fume Hood width Min Height Max Height Emergency speed SA1 Factor SA2 Factor Control Mode Measurement display Speed reference...
Page 28
SEAT VENTILATION SAS PARC TECHNOLOGIQUE DELTA SUD 09340 VERNIOLLE France E-mail: info@seat-ventilation.com Site Web: www.seat-ventilation.com...