meitav-tec PYROCON19-TRACE Owner's Manual & Technician Settings

Controller and user interface panel

Advertisement

Quick Links

PYROCON19-TRACE
Controller and User Interface panel
Owner's manual & Technician Settings
Rev.1.3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PYROCON19-TRACE and is the answer not in the manual?

Questions and answers

Summary of Contents for meitav-tec PYROCON19-TRACE

  • Page 1 PYROCON19-TRACE Controller and User Interface panel Owner’s manual & Technician Settings Rev.1.3...
  • Page 2: Table Of Contents

    Index Introduction…………………………………………………………………...……. 3 Wiring diagram for stand alone configuration……………………………….. 4 Connecting PYROCON19-TRACE slaves (option) ……….…………………. 5 Operating instructions……………………………………………………………. 6 Turning the system ON and OFF………………………………………………. 6 Selecting temperature scale…………………………………………………….. 6 Selecting Automatic or Manual mode …………………………………………. 6 Heaters indication………………………………………………………………... 6 Snow flake icon and digital time indication…………………………………….
  • Page 3: Introduction

    Introduction The PYROCON19-TRACE offers smart and simple control for HEAT TRACING SYSTEMS. It can operate up to 4 heating zones and one auxiliary zone, with selectable sequencing method. Typical applications include pipes, valves and gutters. The backlit LCD screen provides full interface and information to the system status.
  • Page 4: Wiring Diagram For Stand Alone Configuration

    Wiring diagram for stand alone configuration Important! Supply To contactors The PYROCON19-TRACE does not include an integral EGFPD 120VAC EGFPD (Equipment Ground External transformer Fault Protection Device). 120/24VAC,25VA EGFPD needs to be provided 24VAC in the end application. PYROCON19-TRACE Slaves (option)
  • Page 5: Connecting Pyrocon19-Trace Slaves (Option)

    Up to 3 1-63 14-16 These slaves can be connected directly to A2,B2 terminals on the PYROCON19-TRACE or through multiple PYRO-JBOX junction boxes with built in 50VA, 110~24VAC transformer - Allowing connection and powering up to 3 slaves. A2 B2...
  • Page 6: Operating Instructions

    The digital clock will count down the remaining time until the heaters are turned off. The snow flake icon will disappear from display as long as the heaters are turned off. Pg. 6 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings...
  • Page 7: Technician Settings

    Use the [+] and [-] buttons to adjust the temperature set point. Range: 14...77°F / -10…+25°C, Default: 37°F / 3°C As long as the ambient temperature is lower than the temperature Temperature set point P01, the PYROCON19-TRACE will turn ON. set point Pg. 7 Tel: (856) 2882882...
  • Page 8: P02 - Lower Limit Temperature For Heating

    Note 1. The time delay countdown will start when the ambient temperatures (minutes) rises above the set point temperature. Note 2. The staggering sequence will continue during the time delay period. Cont’ Pg. 8 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 9: P04 - Manual Mode On Time

    ON for 2.5 minutes (10/4=2.5). Use the [+] and [-] buttons to adjust the splitting time. Range: 1...600 minutes Default: 120 minutes. Cont’ Pg. 9 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 10: P07 - Heater Outputs Logic (By Temperature Sensor Or By Aquastat)

    Use the [+] and [-] buttons to define the logic of output 1-5 as follows: Temperature Sensor Aquastat Sensor Option Linked heaters Note: If option 2 is selected, the temperature display will remain blank. Cont’ Pg. 10 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 11: P08 - Modbus Mac Address For Bms And For Master-Slave

    SLAVE #1 SLAVE #2 SLAVE #3 Address Address Address PYRO-JBOX A2 B2 PYROCON19 -TRACE MASTER (Up to 3 PYROCON19-TRACE slaves) MAC Address for BMS 1...63 Default 1 WiFi Module Cont’ Pg. 11 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual &...
  • Page 12: P09 - Test Conditions Mode

    Press the [SELECT] and [+] buttons simultaneously. “P11” will appear on display. Use the [+] and [-] buttons to select between: - “ΠA” - Master (When using one PYROCON19-TRACE or when controlling other PYROCON19-TRACE devices connected to A2,B2 Master Slave as slaves) - default - “SL”...
  • Page 13: Save Changes And Return To Normal Display

    Move DIP switch S1 to ON position. Press and hold the [ON] button for 10 seconds. The thermostat will beep. Move DIP switch S1 back to OFF position. Pg. 13 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 14: Short Measuring Times (Test Only) - Dip Switch S2

    Note: if output 5 is set to work together with outputs 1-4, (see “Heater output no. 5 logic” in the technician settings), it will operate the same as output 4. Pg. 14 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings...
  • Page 15: Enable/Disable Zones

    [+] & [-] [+] & [-] (10 sec.) [Select] [Select] [Select] [Select] (5 sec.) Black icon – Zone enabled White icon – Zone disabled Pg. 15 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 16: Select Critical Zones

    Until end of time delay of each critical zone Zone 1 Zone 2 Zone 1 Zone 2 Zone 3 Zone 4 Pg. 16 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 17: Bms - Bacnet/Modbus

    “SensErr 2” Will appear on display. Temperature Slaves – Communication error Sensor error Aux1 - Slaves communication error “Aux1” and “00” Will appear on display. Slaves communication error Pg. 17 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 18: Object List Modbus

    Baud rate: 9600, n, 8, 1 Supported Commands: Vendor Url = “meitavtec.com” 0x03 = Read Holding Registers (for all). VendorName = "Meitav-Tec". 0x06 = Preset Single Register (For R/W registers only), ProductCode = "20420801" Command 0x2B is used to identify controller MajorMinorRevision = "V 20420801.3119”...
  • Page 19: Object List Bacnet

    Heater 5 BinaryOutput_#5 1-On,0-Off InternalHeater BinaryValue_#0 1-On,0-Off OnOff 0-Off BinaryValue_#2 1-On,0-Off C_F_Scale 0-Off BinaryValue_#4 1-On,0-Off CommissioningMode 0-Off BinaryValue_#5 1-On,0-Off RestoreDefaults 0-Off BinaryValue_#14 1-On,0-Off GroundFault 0-Off Pg. 19 Tel: (856) 2882882 PYROCON19-TRACE Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 20: Tel: (856) 2882882

    Tel: (856) 2882882 Tel: +972-3-9626462 Fax: +972-3-9626620 support@meitavtec.com www.meitavtec.com...