V1.0 Archive Date: 2021/09/22 BOM Code: Shenzhen Megmeet Drive Technology Co., Ltd. provides full technical support for our customers,customers can contact local Megmeet offices or customer service centers, or directly contact Megmeet headquarters. Shenzhen Megmeet Drive Technology Co., Ltd. All rights reserved. The contents in this document are subject to change without notice.
The relevant precautions during the installation, wiring, parameter setting, troubleshooting and daily maintenance will be detailed in this manual. To ensure the correct installation and operation of the MV810J servo drive as well as its high performance, please read carefully this user manual before installing the equipment.
Page 3
·The grounding terminal of the drive must be reliably grounded, otherwise, electric shock may be caused. ·The cover must be properly closed before power-up, otherwise, electric shock and explosion may be caused. ·When powering up the drive that has been stored for over 2 years, the input voltage must be gradually increased with the voltage regulator, otherwise, electric shock and explosion may be caused.
Chapter 1 Introduction of MV810J Servo Drive Product model The description of the drive model on the nameplate indicates the information of the product, such as product series, voltage class of power supply, power class, the software/hardware code of customized product, etc.
Table 1-1 Name and model of drive Rated Rated output current Rated output power Rated input current (A) capacity (kW) Enclosure Product model model (kVA) (HD) MV810J-4T37 50.0 76.0 92.0 75.0 90.0 MV810J-4T45 60.0 92.0 113.0 90.0 110.0 MV810J-4T55 72.0 113.0...
Page 7
<10ms (vector control without PG) The torque control precision is 7.5% when vector control without PG, 5% when Torque control vector control with PG, and 5% when simple servo control 150% @ 0Hz (vector control without PG); 200% @ 0Hz (vector control with Startup torque Fast tracking, over torque / under torque detection, torque limit, multi-stage speed operation, multiple acceleration/deceleration time switching,...
12. Operation panel 13. Lower cover Fig.1-1 Drive structure (taking WR5 as an example) Outline, mounting dimensions and gross weight of drive There are two types of outlines as shown in Fig. 1-2: 1.WR4 is sheet metal enclosure (MV810J-4T37~ MV810J-4T45)
Chapter 2 Drive Installation Installation environment When selecting the installation environment, the following issues should be taken into account: ·The ambient temperature should be within -10℃~40℃. If the temperature exceeds 40℃, external forced cooling or derating is required. ·The humidity should be less than 95%RH, non-condensing. ·The vibration at the installation place should be less than 5.9m/s (0.6g).
Removal and installation of drive components Fig.2-2 Removal and installation of drive components (taking WR5 as an example) 2.3.1 Removal and installation of operation panel Removal: Insert your middle finger into the hole above the operation panel, gently press the top spring and then pull it out, as shown in Fig.2-2.
Page 14
2.3.3 Complete machine equipment installation Installation: The liquid cooling machine is installed through the wall, and the size of the wall is determined according to the size of the radiator of the complete machine. The complete machine is fixed inside the cabinet through the screw holes around the support plate, and the radiator is exposed outside the cabinet.
AC supply through a circuit breaker or a fuse. Wiring and configuration of main circuit terminals 3.1.1 Types of main circuit input/output terminals The main circuit terminals are detailed below. Terminal type Applicable models: MV810J-4T37~ MV810J-4T90...
Page 16
Terminal Function R/L1, S/L2, T/L3 Three-phase AC 380V input terminals +DC/B1, B2 Reserved for external braking resistor DC negative bus output terminals U/T1, V/T2, W/T3 Three-phase AC output terminals 3.1.2 Wiring for basic operation...
Page 17
Fig. 3-1 Wiring diagram for main circuit and control circuit terminals...
Note: 1. For AI1 and AI2, the input voltage signal or the current signal can be selected via the jumper. The function code P10.00 shall be changed after the hardware jumper finished selection to ensure the correct input signal. 2. For AO1 and AO2, the output voltage signal or the current signal can be selected via the jumper, and the output range is selected and determined by the function code P10.22.
Type Name Function Specification Terminal motor cable wire can be connected to this terminal. +10V power To provide +10V reference power for Allowable maximum output current: supply external load 10mA -10V power To provide -10V reference power for Allowable maximum output current: supply external load 10mA...
Page 20
Type Name Function Specification Terminal voltage/current is selected in the function code P10.22 (reference grounding: GND). Positive end of 485 differential signal Standard RS485 communication RS485+ RS485 (reference grounding: GND) interface. communication Please use twisted pair wire or Negative end of 485 differential interface RS485- shielded wire.
Page 21
Type Name Function Specification Terminal It can be set as the digital output Opto-isolated output Open collector terminal with multiple functions and Maximum operating voltage: 30V output terminal also can be reused as DO pulse Maximum output current: 50mA Multi-function 1 / DO pulse output terminal, which is selected by The DO pulse output frequency range...
Chapter 4 Quick Operation Guide for Drive Drive operation panel 4.1.1 Introduction to drive operation panel Fig.4-1 Schematic diagram of operation panel 4.1.1.1 LED description Table 4-1 LED description LED symbol Name Meaning Color On: Current parameter displayed represents the running frequency Frequency LED Green Flash: Current parameter displayed represents...
Page 23
On: Current parameter displayed represents r/min Rotating speed LED Green the rotating speed On: In the stop status, it means the drive has forward running command Forward running LED In the running status, it means the drive is Green running forward Flash: The drive is switching from FWD to REV On: In the stop status, it means the drive has reverse running command...
Page 24
Name Function When pressing this key in the operation panel mode, the drive will Run key start to run STOP/RESET Stop/reset key Stop or fault reset Table 4-4 Useage of the Multi-functional key Multi-functional key (M key) Function Function meaning No function The M key is disabled.
Page 25
4.1.2 Indentification of LED display symbols The correspondence relation between the LED display symbols and the character/figure is as shown below:...
Chapter 5 Parameter List Explanation to the terms in the function code parameter table Table field Explanation Function code Representing the number of the function code, such as P00.00 number Function code Name of the function code, explaining it name Leave-factory The value of the function code after restoring the leave-factory settings value...
Page 27
0: Chinese display Language P00.02 × √ ○ language selection 1: English selection 0: All the data can be changed; 1: Only the main set frequency Parameter Parameter (digital setting P02.05) and this P00.03 protection protection √ √ ○ function code can be changed setting setting 2: Only this function code can be...
Page 28
copy copy 1: Uploading parameter 2: Downloading parameters 3: Downloading parameters (except the motor parameters) Note: The drive parameters will not be uploaded/downloaded Group P01: Status display parameters 0: Disabled 1: Digital reference 1: Keyboard ∧∨ reference 2: Digital reference 2: Terminal UP/DN reference 3: Serial port communication Main...
Page 29
current current Output Output P01.10 -300.0~+300.0% 0.1% 0.0% × √ torque torque Motor Motor 0.0~200.0% (relative to the rated P01.11 0.1% 0.0% × √ power power power of the motor) Estimated Estimated P01.12 frequency frequency -650.00~650.00Hz 0.01 0.00 × × of motor of motor Measured...
Page 30
AI2 input AI2 input P01.21 -10.00~10.00V 0.01V 0.00 × √ voltage voltage AI3 input AI3 input P01.22 -10.00~10.00V 0.01V 0.00 × √ voltage voltage 0.0~100.0% P01.23 AO1 output AO1 output 0.1% 0.0% × √ (percentage relative to the full range) 0.0~100.0% P01.24 AO2 output...
Page 31
selection selection 1: Motor 2 0: Keyboard control 1: Terminal control Running Command command 2: Communication control channel P02.02 √ √ ○ channel 3: Bus control (including bus selection selection communication card and PLC card) (reserved) Running Running 0: Forward running; P02.03 direction direction...
Page 32
1, 2 hundreds and thousands place are only applicable for P02.07=1, 2, 3 0: No auxiliary reference 1: Digital reference 1: Keyboard ∧∨ reference 2: Digital reference 2: Terminal Auxiliary UP/DN reference Auxiliary reference frequency 3: Serial port communication P02.07 frequency ×...
Page 33
frequency frequency Proportion adjustment Proportion P02.12 coefficient adjustment 0.0%~200.0% 0.1% 100.0% × √ ○ of set coefficient frequency 5.5~22:6S (Unit adopts Acceleratio Acceleratio that of P02.13 0.0~3600.0 √ √ ○ 45:20S n time 1 n time 1 P11.01) Others:30 5.5~ (Unit 22:6.0S adopts...
Page 34
of motor 1 Leakage inductance Leakage or direct Depending P03.07 inductance 0.0~2000.0 √ √ × axis on model inductance of motor 1 Rotator Rotator resistance resistance Depending P03.08 0.000~65.000 0.001 √ √ × back-EMF back-EMF on model constant of constant of motor 1 motor 1 Mutual...
Page 35
Z pulse Synchrono Synchrono 0, SMPM (can not guarantee to us motor us motor enable REV) P03.28 √ √ × type type 1, IPM (can enable non-REV) selection selection Group P04: Encoder parameters Unit place: Encoder selection of motor 1 0: Local differential encoder 1: X7 &...
Page 36
signal enabled Hundreds place: Expansion PG2 Z pulse enabled Unit place: High-speed filtering of expansion PG1: 0~9 Tens place: Low-speed filtering of Expansion PG signal expansion PG1: 0~9 PG signal filtering P04.10 0030 × √ ○ filtering coefficient Hundreds place: High-speed coefficient filtering of expansion PG2: 0~9 Thousands place: Low-speed...
Page 37
ASR2 ASR2 P05.06 0~8 (corresponds to 0~2^8/10ms) × √ ○ output filter output filter switching P05.07 switching 0.0%~100.0% 20.0% × √ ○ frequency frequency 2 Proportion Proportiona al gain of l gain of special special speed P05.08 0.1~200.0 20.0 × √...
Page 38
Zero servo Zero servo P05.18 0~6.000 0.001 1.000 × √ ○ gain gain Zero servo Zero servo P05.19 initial initial 0.00~10.00Hz 0.01 0.30 × √ ○ frequency frequency Action selection Action upon 0: Decelerate to stop selection detection P05.20 upon ×...
Page 40
accordance with the current stop mode) 45: Auxiliary reference frequency reset 46: Pre-magnetizing command terminal (reserved) 47: Speed control and torque control switching terminal 48: Torque direction switching terminal for torque control 49: Torque offset selection terminal 50: AI torque offset retention 51: Pulse input terminal of the torque limit 1 (valid only for X7 or 52: Pulse input terminal of the...
Page 41
one terminal among X1~X8) Terminal Terminal UP/DN UP/DN P09.09 acceleratio acceleratio 0.01~99.99Hz/s 0.01 1.00 √ ○ × n/decelerat n/decelerati ion rate on rate Terminal Terminal P09.10 filtering filtering 0~500ms × √ ○ time time Maximum Maximum input pulse P09.11 input pulse 0.1~100.0 kHz 0.1kHz 10.0...
Page 42
BIT0~BIT3: X1~X4 Tens place of LED: BIT0~BIT3: X5~X8 Binary setting: 0: Disabled Virtual 1: Enabled Virtual input input terminal Unit place of LED: × √ ○ P09.16 terminal setting BIT0~BIT3: X1~X4 setting Tens place of LED: BIT0~BIT3: X5~X8 Output Output 0: Open collector output terminal selection of selection of...
Page 47
the flow the flow curve reference reference Actual value correspond Actual s to the value of P10.13 inflection The same as P10.07 0.1% 90.0% √ √ ○ inflection point 9 of point 9 the flow curve reference Inflection Inflection point 8 of point 8 of P10.14 the flow...
Page 48
curve reference Inflection Inflection point 5 of point 5 of P10.20 the flow the flow P10.22~P10.18 0.1% 50.0% √ √ ○ curve curve reference reference Actual value Actual correspond value s to the correspond P10.21 inflection The same as P10.07 0.1% 50.0% √...
Page 49
s to the s to the inflection inflection point 2 of point 2 the flow curve reference Inflection Inflection point 1 of point 1 of P10.28 the flow the flow P10.30~P10.26 0.1% 10.0% √ √ ○ curve curve reference reference Actual value Actual...
Page 50
inflection inflection point 16 of point 16 pressure curve reference Inflection point 15 of Inflection point 15 of P10.36 P10.38~P10.34 0.1% 60.0% × √ ○ the curve 1 pressure curve reference reference Actual value correspond Actual s to the value inflection correspond P10.37...
Page 51
curve reference Inflection point 12 of Inflection point 12 of P10.42 P10.44~P10.40 0.1% 48.0% × √ ○ pressure the curve 1 curve reference reference Actual value correspond Actual s to the value inflection correspond P10.43 The same as P10.33 0.1% 48.0% ×...
Page 52
the curve 1 pressure reference curve reference Actual value correspond Actual s to the value inflection correspond P10.49 The same as P10.33 0.1% 36.0% × √ ○ s to the point 9 of inflection point 9 pressure curve reference Inflection point 8 of Inflection point 8 of...
Page 53
Actual value correspond Actual s to the value inflection correspond P10.55 The same as P10.33 0.1% 24.0% × √ ○ s to the point 6 of inflection point 6 pressure curve reference Inflection point 5 of Inflection point 5 of P10.56 P10.58~P10.54 0.1%...
Page 54
inflection inflection point 3 of point 3 pressure curve reference Inflection point 2 of Inflection point 2 of P10.62 P10.64~P10.60 0.1% 8.0% × √ ○ the curve 1 pressure curve reference reference Actual value correspond Actual s to the value inflection correspond P10.63...
Page 55
output output 1: 2~10V (4~20mA) The current and voltage depend on the hardware Tens place of LED: AO2 selection 0: 0~10V (0~20mA) 1: 2~10V (4~20mA) The current and voltage depend on the hardware 0: Output frequency (0~maximum frequency) 1: Set frequency (0~maximum frequency) 2: Set frequency (after acceleration/deceleration) (0~...
Page 56
compensation) 25: Reserved (constant current source output for motor temperature measurement) 26: Percentage of communication card (0~4095) Only the following function No. will be shown in shortcut menu: 0~9 P10.70 AO1 gain AO1 gain 0.0%~200.0% 0.1% 100.0% × √ ○ AO1 zero AO1 zero P10.71...
Page 57
1: Three-phase modulation Thousands place: Low frequency carrier limit 0: Disable 1: Enable 0: Manual selection Current Current P12.04 loop gain loop gain × √ × 1: Calculate automatically (after selection selection tuning) Current Current loop loop P12.05 proportiona 1~5000 1000 ×...
Page 58
Note: It will keep running for 3 minutes after power-off P12.15 Reserved Reserved ~P12.17 Unit place: Temperature detection device types 0: PTC Motor Motor 1: KTY84 temperatur temperatur P12.18 e detection e detection × √ × Tens place: Number of device device temperature detection device...
Page 59
Unloading Unloading -100.0%~100% pressure pressure Note: The maximum output P14.10 0.1% -10.0% × √ ○ reverse reverse frequency is 100% speed limit speed limit Unit place: Hydraulic sensor fault detection selection 0: Continue to run, no alarm 1: Continue to run and display “AL.FbL”...
Page 60
exceeding limit limit detection detection time time Group P15: Reserved Group P16: Keyboard display setting parameters Binary setting: 0: No display; 1: Display Unit place of LED: BIT0: Output frequency (Hz) BIT1: Preset frequency (Hz flashing) BIT2: Output current (A) Tens place of LED: BIT0: Running rotating speed display...
Page 61
BIT1: Running speed (r/min) BIT2: Preset speed (r/min) BIT3: DC bus voltage Tens place of LED: BIT0: Running line speed (m/s) BIT1: Preset line speed (m/s) BIT2: Analog closed loop feedback (%) BIT3: Analog closed reference Hundreds place of LED: BIT0: AI1 (V) BIT1: AI2 (V) BIT2: AI3 (V)
Page 62
frequency × motor rated rotating speed/motor rated frequency × P16.04 Non-VF: Running rotating speed = measured/ estimated rotating speed × P16.04 Preset rotating speed = Preset frequency × motor rated rotating speed/motor rated frequency × P16.04 0.1%~999.9% Close loop Closed analog loop Note: The close loop analog...
Page 63
to set the parameters yourself. Pressure Pressure 0.1kg/cm P25.01 sensor sensor 0.0~255.0 250.0 × √ ○ range range 0: 1~5V output Output Output 1: 4~20mA output (reserved) signal signal mode of 2: 1~10V P25.02 mode of the × √ ○ 3: 0~10V pressure pressure...
Page 64
Unit place of LED: Action upon communication fault 0: Activate protection and coast to stop 1: Alarm and keep running 2: Alarm and stop in the stop mode (only in serial port control mode) 3: Alarm and stop in the stop mode (in all control modes) Tens place of LED: Action upon Fault...
Page 65
2: Alarm and keep running Thousands place of LED: Action upon analog input (AI1, AI2, AI3) fault 0 : Activate protection and decelerate to stop 1 : Activate protection and coast to stop 2 : Alarm and keep running Unit place of LED: Action upon temperature sampling disconnection 0 : Activate temperature...
Page 66
pre-alarm detection selection 0: Always detect 1: Detect only at constant speed Hundreds place of LED: Overload pre-alarm action selection 0: Alarm and keep running 1: Activate protection and coast to stop Thousands place of LED: Overload detection level selection 0: Relative to rated current of the motor (Er.oL1) 1: Relative to rated current of the...
Page 67
circuit detection power) detection upon upon power-up power-up 0: No function 1~100: Auto reset times Auto reset Auto reset Note: Auto reset is not available P97.13 × √ × times times for module protection, external device fault and AI over-current fault Auto reset Reset...
Page 68
21: PID feedback lost (Er.FbL) 22: External reference command lost (Er. EGL) 23: Keyboard parameter copy error (Er.CoP) 24: Poor auto-tuning (Er.TUn) 25: Local PG fault (Er.PG1) 26: Reserved 27: Reserved 28: Parameter setting error (Er.PST) 29: Control board 24V power short circuit (Er.24v) 30: Reserved 31: Expansion card fault (Er.oPT)
Page 69
later; if it is more than 3 times, it can not be reset until 200s later; 3. The keyboard displays AL.xxx in case of any fault (e.g. in case of the contactor fault, keyboard displays Er.xxx if there is protection action, and displays AL.xxx if continuing running with alarm) The second...
selection selection 2: 400V setting 3: 415V 4: 440V 5: 460V 6: 480V Servo oil pump control parameters (Group P14) P14.00 Hydraulic control mode 0~3 (0) 0: Non-hydraulic control mode 1: Drive hydraulic control mode 1 CAN provides pressure, flow command, AI1 analog channels provide hydraulic feedback command, drive performs hydraulic control.
Page 71
Corresponding to hydraulic control integral gain Ki1(P14.03). P14.07 Hydraulic control differential gain Kd2 0.000~30.000(0.000) Corresponding to hydraulic control differential gain Kd1(P14.04). Note 1. In the servo oil pump control, the first is to control the response of servo motor, the second is to control the response of system pressure and flow, therefore, control and adjust the servo motor response firstly and then control and adjust the system response.
When the hydraulic sensor feedback signal is greater than the detection value set by P14.28 and its time exceeds the time set by P14.29, then hydraulic sensor feedback is considered as “exceeding limit”. Servo oil pump selection parameters (Group P25) P25.00 Servo pump model 0~FFFFH (0000)
Note: When you select "0", representing that motor type is not formulated, you need to set the parameters yourself. P25.05 Maximum speed 0~6000 (1800) Corresponding to the system output flow set the maximum speed of the motor, the set value should be less than 140% of the motor rated speed (P03.04), the value must be less than the maximum speed of the motor.
6.2 Servo oil pump debugging steps 1. Motor commissioning After properly installing EC-PGRLV card, set operation as follows : 1) Set the motor parameters according to the motor nameplate parameters: P03.00 Rated power of motor, P03.01 Rated voltage of motor, P03.02 Rated current of motor, P03.03 Rated frequency of motor, P03.04 Rated rotating speed of motor, P03.08 Back-EMF constant of motor 2) Set drive to non-hydraulic control mode: P14.00=0;...
Page 76
P14.00=4: Drive hydraulic control mode 3. AI4 analog channels provide hydraulic feedback command, AI2 analog channels provide flow reference command, AI3 analog channels provide pressure reference command. 2) Servo pump selection parameter settings: Set P25.01 (pressure sensor range), P25.02 (pressure sensor output signal mode) according to pressure sensor specifications.
In control process of injection molding machine, due to the response requirements of the different action is inconsistent, it generally use different PID parameter settings, but in order to debug conveniently, only "Injection packing action" and "other actions" are distinguished and switched. Note ...
Page 78
Servo motor characteristic curve According to above figure, with the upgrading of the motor speed, motor torque will gradually decline. But when the speed exceeds 150% of rated speed, servo motor gradually saturated, motor torque will decline rapidly, so the speed stage can not be used as servo motor speed period. Therefore: We recommend the selected maximum motor speed is 140% of rated speed Motor rated speed: V (rpm)=Vmax(rpm)/140% Note: To get better control effect, select the maximum motor speed is 130% of rated speed...
Page 79
After the servo motor selection is completed, you can ask motor suppliers for corresponding motor torque constant value Kt (Nm / A). Note: The torque constant value Kt (Nm / A) is related to the servo motor technology, materials and motor rated speed V (rpm).
Displaying exception and solutions All possible fault types for MV810J are summarized as shown in table 7-1. The number of the fault code is 41. Before consulting the service department, the user can perform self-check according to the hints of the table and record the fault symptoms in detail.
Page 81
Fault code Fault type Possible fault cause Solutions The deceleration time is too short Lengthen the deceleration time Deceleration (compared with regeneration energy). Er.oU2 over-voltage of There is potential energy load or the the drive Select appropriate dynamic braking components load inertial torque is large.
Page 82
Fault code Fault type Possible fault cause Solutions over-temperature The fan is damaged. Replace the fan The inverter module is abnormal. Seek for service support The ambient temperature is too high. Lower the ambient temperature Rectifier heatsink Er.oH2 The duct is blocked. Clean the duct over-temperature The fan is damaged.
Page 83
Fault code Fault type Possible fault cause Solutions The fault alarm parameters are set Modify the P15.03 and P97.00 settings improperly. Check if the host device is working and if the wiring The host device does not work. is correct. The grid voltage is too low.
Page 84
Fault code Fault type Possible fault cause Solutions The operation panel parameters are Refresh the operation panel data and version, use incomplete or the operation panel P00.06=1 for uploading the parameters first and Operation panel version is inconsistent with main control then use P00.06=2 or 3 for downloading.
Page 85
PID upper limit set value All the possible alarm types for MV810J are summarized as shown in table 7-2. For details, please refer to the group P97 function code setting. If the fault disappears automatically during the running process, the drive will also automatically reset to the status before the alarm (except AL.SC1, for details, please refer to the group...
Table 7-2 Alarm code table Alarm Alarm type Possible alarm causes Solutions code The motor parameters are incorrect. Perform the parameter auto-tuning of the motor The load is too large. Adopt the drive with higher power Reduce the DC braking current and lengthen the The DC braking amount is too large.
Alarm Alarm type Possible alarm causes Solutions code The power-up buffer resistance is Replace the buffer resistance, seek for service damaged. support The control circuit is damaged. Seek for service support Input phase loss Check the input R.S.T wiring The parameters for feedback loss are Modify the P14.26 setting set improperly.
Page 88
Symptoms Conditions Possible causes Solutions Completely power off the drive and then power it up The wires of the operation panel Check the wires and perform the hot plug have poor contact. again The keys of the operation panel are Replace the operation panel or seek for damaged.
Symptoms Conditions Possible causes Solutions is on (running at zero The set frequency is 0. Check the set frequency frequency). The startup frequency is higher Check the startup frequency than the set frequency. There is something wrong with the Check the skip frequency setting skip frequency setting.
Page 90
Symptoms Conditions Possible causes Solutions When the Since the thyristor or the contactor drive is The thyristor or the is not closed, when the drive runs started, the contactor disconnects with large load, the DC bus voltage Run the drive after the thyristor or the report -LU- and the drive load is of the main circuit will drop;...
Appendix 1 CAN Communication Applications 1.Introduction The full range products of MV810J support that CAN communication, CAN communication card and resolver card are combined into a card, the communication protocol is compatible with CAN2.0B and CANOPEN. · Only supports standard frame (11 ID) ·...
Page 92
CAN interface as shown on the right: Ports are defined as follows: 1.CANH 2.CANL 3.CND (Shield ground) 4. Empty 5.L1+ 6.L1- Note L1 +, L1- on the CAN card are motor temperature detection interfaces, considering that some of the servo motors temperature detection terminal and encoder terminals are connected to X1 interface, then, you need connect L1 +, L1- on the CAN card board to L1 +, L1- terminals on the control board.
Appendix 2 Servo Oil Pump Parallel Control Program Parallel pumps include "multiple pumps parallel flow" and "multi-pump bypass / parallel flow" . Multi-pump parallel flow means: a servo pump as the master drive, and the rest working together as slave drive in parallel, action and start-stop are consistent, working mode is the same as standard single servo pump.
Page 94
2. Multi-pump bypass / parallel flow The following is a multi-pump bypass / parallel flow control structure diagram: Note Wiring mode for master, slave drive and standard single servo pump is the same, slave drive and the master drive are connected via the CAN bus (or pulse mode), the master, slave drive do a corresponding parameters adjustment respectively.
Appendix 3 Braking Components 1.Braking resistor configuration: Attached Table 3-1 Braking resistor accessories Motor rated power (kW) Braking resistor model Braking torque (%) 3700W/15Ω 4500W/15Ω 5500W/10Ω 9600W/13.6Ω*2 9600W/13.6Ω*2 Note The drives of 90kW or below have internal braking units. The user only needs to configure external braking resistor when the dynamic braking is required.
(such as unsatisfactory performance and function), please contact your product agent or Shenzhen Megmeet Drive Technology Co., Ltd.. 2). In case of any abnormality, please timely contact your product provider or Shenzhen Megmeet Drive Technology Co., Ltd. for help.
Need help?
Do you have a question about the MV810J and is the answer not in the manual?
Questions and answers