ATS320AC ATS CONTROLLER USER MANUALV 1.1...
Page 2
ATS320AC ATS CONTROLLER USER MANUAL Software Version Version Date Note V1.0 2021-06-01 Original release. V1.1 2022-06-01 Increase gear toggle function. Chongqing Mebay Technology Co.,Ltd Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing. Tel:+86-23-6869 3061 Fax:+86-23-6765 8207 Web:http://www.mebay.cn http://www.cqmb.cn E_mail:sales@mebay.cn...
Page 3
ATS320AC ATS CONTROLLER USER MANUAL Symbol Description Symbol Description Remind operators to operate correctly, otherwise it may cause the equipment not to work correctly. Note It is indicated that potential hazards can damage equipment without proper precautions. Be care It is indicated if appropriate preventive measures are not taken,...
Page 4
ATS320AC ATS CONTROLLER USER MANUAL Warning 1.The installation of this equipment must be carried out by professionals. 2.When installing and operating the controller, please read the entire instruction manual first. 3.Any maintenance and commissioning of the equipment must be familiar with all the equipment.
1. All rights reserved. No part of this duplication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or others) without the written permission of the copyright holder. 2. MEBAY Technology reserves the rights to change the contents of this document without prior notice.
ATS320AC ATS CONTROLLER USER MANUAL Summary The controller is a mains/gens ATS controller, which can automatically or manually control the ATS dual power switch, suitable for the application of one mains and one power generation. The LCD screen can display various faults at the same time.
ATS320AC ATS CONTROLLER USER MANUAL Parameters Options Parameters Working voltage AC 90V-450V(L1N1/L2N2) Standby:MAX 1W Power consumption Working:MAX 2W Gens Voltage Input 1P2W 90VAC-450VAC (ph-N) Mains Voltage Input 1P2W 90VAC-450VAC (ph-N) MAX Accumulating Time 99999.9Hours (Min Store time:6min) Closing gens output...
Page 8
ATS320AC ATS CONTROLLER USER MANUAL 36.2 36.2 Descriptions of terminal connection Cable cross Function Description sectional area Non-contact normally close output 1.0mm Gens remote start Capacity: 250V/3A 1.0mm 1.0mm Gens closing Engagement brake feedback signal feedback input 1.0mm Gens close output 2A 1.0mm...
Page 9
ATS320AC ATS CONTROLLER USER MANUAL closing output 1 act at the same time. Gens close output 1A Non-contact normally close output Capacity: 1.0mm 250V/5A Gens closing output 1 and Gens Gens close output 1B closing output 2 act at the same time.
ATS320AC ATS CONTROLLER USER MANUAL Installation instruction The controller is fixed by two special fixing members and screws, and the screws of the metal fasteners cannot be too tight. Panel Cutout: W78mm*H66mm. Note: If the controller is installed directly in the genset shell or other fluctuated equipment, the rubber pad must be installed.
ATS320AC ATS CONTROLLER USER MANUAL Input /Output Description Description Mans closed Gens closed Remote start output Gens output Mans output Key Function Description KEYS NAME Main Function Active in Manual mode. Press this key, mains closing Mains forced output or mains open.
ATS320AC ATS CONTROLLER USER MANUAL Alarm records checking ATS 320 controller can save 12 group of alarm records which contains the alarm record data includes detailed data such as alarm time,prompt status information, etc. How to check the alarm records: 1.
ATS320AC ATS CONTROLLER USER MANUAL again to cycle through different parameter rows, and then press the confirm key to confirm the operation. 1.Return 2.Stop Genset Disconnect the start signal, i.e. stop the running genset. 3.Start Genset Output the start signal, i.e. start the genset.
ATS320AC ATS CONTROLLER USER MANUAL Current mode is Manual mode. Show in status bar STOP Current mode is Stop mode. Show in status bar TEST Current mode is Test mode. Show in status bar Gens/Mains Voltage status Item Description Gens start...
ATS320AC ATS CONTROLLER USER MANUAL Parameter setting Enter the edition page Please set the parameters according to below steps: 1) Press the key for 3 seconds to enter the parameter setting interface; 2) Under the parameter browsing interface, press...
Page 16
ATS320AC ATS CONTROLLER USER MANUAL When the genset is ready to stop, stop delay Gen stop delay 0-9999.0S(5.0S) begins, after the stop delay has expired, stop signal will be initiated. Mains and Gens loading and unloading pulse Load /Unload 1.0-60.0s(10.0s)
Page 17
ATS320AC ATS CONTROLLER USER MANUAL closing relay. When selecting a gear toggle: 1. The button gear is invalid. 2. The test gear is invalid. 3. The closing feedback function is disabled. 4. Switch input validity combination to switch gears, an external switch can be connected;...
ATS320AC ATS CONTROLLER USER MANUAL Fault finding Symptoms Possible Solutions Controller no Check mains or gens AC power supply. response with power Check the connection line between the controller and the Genset Start generator set self-starting control interface; Abnormal Check whether the remote start function setting is normal;...