EDUS371704-N Installation of Outdoor Units 1. Features and Benefits ................2 2. Center of Gravity ..................3 2.1 REYQ-TAYDU....................3 2.2 REYQ-TATJU....................5 3. Foundation Drawing ...................7 4. REFNET Pipe System................8 4.1 Layout Example.................... 8 4.2 REFNET Joints and Headers ..............10 5.
• Refrigerant cooled inverted technology to avoid influence from ambient temperatures • Corrosion resistant 1000hr salt spray tested Daikin PE blue fin heat exchanger • Heat exchanger coil wraps around on all 4 sides of the unit to increase the surface area / efficiency •...
EDUS371704-N Center of Gravity 2. Center of Gravity REYQ-TAYDU REYQ72TAYDU 4D090828A REYQ96TAYDU / REYQ120TAYDU 4D090829A Installation of Outdoor Units...
Page 6
Center of Gravity EDUS371704-N REYQ144TAYDU / REYQ168TAYDU 4D090830A Installation of Outdoor Units...
2. Special purpose REFNET pipe components must be used for all the pipe work. For further details concerning choosing components, see REFNET and Piping Selection Rules. 3. The Daikin REFNET kits are supplied with insulation intended to fit over the main body of the REFNET joint after installation of the REFNET kit is complete.
Page 11
EDUS371704-N REFNET Pipe System 4.1.2 Equivalent Piping Length of Joints and Headers (Reference) φ 1/4 in. φ 3/8 in. φ 1/2 in. φ 5/8 in. φ 3/4 in. φ 7/8 in. φ 1 in. φ 1-1/8 in. φ 1-1/4 in. φ...
REFNET Pipe System EDUS371704-N REFNET Joints and Headers 4.2.1 REFNET Joints For gas and liquid branch pipes Make sure that all branch pipes are fitted such that they branch either horizontally or vertically. When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below.
Page 13
EDUS371704-N REFNET Pipe System When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches. When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below.
Installation Manual EDUS371704-N 1. Installation Manual Safety considerations WARNING Read these Safety considerations for Installation carefully be- work. Installation must be done in accordance with this fore installing an air conditioner or heat pump. After complet- installation manual. Improper installation could result in ing the installation, make sure that the unit operates properly during the startup operation.
EDUS371704-N Installation Manual CAUTION Corroding copper pipes or soldered parts may result in refrigerant leakage. (c) Near machinery emitting electromagnetic waves. Do not allow children to play on or around the unit or it the control system and cause the unit to malfunction. may result in injury.
EDUS371704-N Installation Manual 1. Introduction 1.1. General information inverter driven, heat pump system. Outdoor unit Refrigerant piping Branch Selector unit VRV indoor unit Cool/Heat selector (single Branch Selector unit only) User interface (dedicated depending on indoor unit type) To install the outdoor unit, the following accessory parts are also User interface (wireless, dedicated depending on indoor unit type) required.
EDUS371704-N Installation Manual It is therefore recommended to install the equipment and electric wires 3.2. keeping proper distances away from stereo equipment, personal computers, etc tions. 3.3. Main components For main components and function of the main components, refer to 4.
Installation Manual EDUS371704-N 4.3. Selecting a location in cold climates 5. Dimensions and service space 5.1. Dimensions of outdoor unit NOTE REYQ72T When operating the unit in a low outdoor ambient temperature, be sure to follow the instructions described below. The following images are for reference only.
EDUS371704-N Installation Manual 5.2. Service space <Front side> <Suction side> The space around the unit is adequate for servicing and the minimum Service and choose one of the possibilities). space or more or more 59 in. (1500 mm) 19-5/8 in. (500 mm) In case of an installation site where sides A+B+C+D have obsta- cles, the wall heights of sides A+C have no impact on service space of sides B+D on service space dimensions.
Installation Manual EDUS371704-N 6. Inspecting, handling and unpacking the unit 6.3. Unpacking 6.1. Inspection CAUTION At delivery, the unit must be checked and any damage must be re- ported immediately to the carrier’s claims agent. Remove the unit from its packing material. 6.2.
EDUS371704-N Installation Manual The height of the foundation must be at least 5-7/8 in. (150 mm ) 6.5. Method for removing shipping plates The shipping plates installed over the compressor legs for protecting In heavy snowfall areas, this height should be increased, depending the unit during transport must be removed.
Installation Manual EDUS371704-N 7. Refrigerant pipe size and allowable pipe length 7.3. Selection of piping size Determine the proper size referring to following tables and reference NOTE When installing the VRV outdoor unit in combination with the VRV DVS DOAS air handling unit, refer to the DVS DOAS Installation manual. 7.1.
EDUS371704-N Installation Manual 7.3.2. Piping between refrigerant branch kits or refrigerant branch kits and Branch Selector units: D joint b - see 7.3. Selection of piping size), select the proper branch kit model based on the total capacity of all indoor units connected Choose from the following table in accordance with the indoor unit after the refrigerant branch.
Installation Manual EDUS371704-N 7.5. Outdoor unit : Branch Selector unit (multi) : Indoor units (cooling/heating First outdoor unit Outdoor unit selectable) : Branch Selector unit (single) multi connection : Indoor unit (cooling only) piping kit (*1) (*3) REFNET joint (A-E) (*1) “...
Page 103
EDUS371704-N Installation Manual Actual piping length 7 : a+b+c+ From outdoor unit (*4) to indoor unit (1000 m) allowable length multi connection pip- Actual piping length Outdoor unit ing kit to outdoor unit (in a multi system) From outdoor unit to Height difference indoor unit Actual piping length X Height difference between indoor units (H2)
Page 104
Installation Manual EDUS371704-N Necessary conditions Upsize the liquid pipes b, c, d, e, f and g in the refrigerant branch kit for the indoor unit beyond 130 ft. (40 m). lows: If upsizing is impossible, the condi- 3/8 in. (9.5 mm) 1/2 in.
EDUS371704-N Installation Manual 8. Precautions on refrigerant piping Do not allow anything other than the designated refrigerant to get refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away. Use R410A only when adding refrigerant. 1 Refrigerant piping Installation tools: Make sure to use installation tools (gauge manifold, charge hose, 2 Part to be brazed...
Page 106
Installation Manual EDUS371704-N Use the following procedure to remove the pinched piping: WARNING 1 Remove the valve cover and make sure that the stop valves are fully closed. the stop valves mounting plate with a protective plate to prevent from 1 Service port and service port cover 2 Stop valve...
Page 107
EDUS371704-N Installation Manual Only proceed with piping work after considering the limitations on Remove the knockout hole on the bottom frame and lead out the installing listed here and in the chapter 8.2. Connecting the refriger- piping from the bottom frame. delivered with the kit.
Installation Manual EDUS371704-N 2 Installation of the multi connection piping kit. create a rise of 8 in. (200 mm) or more in the suction gas and high/ low pressure gas line within a length of 6.5 ft. (2 m) from the kit. To indoor units Piping between outdoor units >...
EDUS371704-N Installation Manual 8.3.2. How to use the stop valve After handling the stop valve, make sure to tighten the stop valve cover securely. For the tightening torque, refer to 8.3.2. How to use Tightening torques the stop valve. Stop Check for refrigerant leaks after tightening the stop valve cover.
Installation Manual EDUS371704-N 9.2. Wiring connection example for whole system parts (terminal for power wiring, terminal for transmission wiring and ground terminal). mentary blackout or the power goes on and off while the product is operating, attach a reverse-phase protection circuit locally. Running the product in reverse-phase may break the compressor and other parts.
EDUS371704-N Installation Manual 9.3. Leading wire procedure 9.4. Transmission wiring connection procedure The power wiring and ground wiring are passed out from the power wiring hole on the front (knock hole). tween outdoor unit and indoor unit, outdoor unit and outdoor unit of The transmission wiring is passed out from the wiring hole (knock other system, outdoor unit and outdoor unit of same system.
Installation Manual EDUS371704-N 9.5. Power wiring connection procedure Between outdoor unit and Branch Selector (indoor) unit Between outdoor unit and outdoor unit of other systems Be sure to connect the power supply wiring to the power supply ter- Between outdoor unit and DOAS unit minal block and hold it in place using the included clamp as shown The L1, L2 and L3 phases of the power wiring should be secured separately to the hook using the included clamp (1).
EDUS371704-N Installation Manual 9.6. Procedure for Wiring Inside Units CAUTION Be sure to use crimp-style terminal with insulating sleeves for con- mission wiring using the included clamp (1), (2) and (3). Wire so that the ground wiring does not come into contact with the Power wire Crimp-style terminal compressor lead wiring.
Installation Manual EDUS371704-N Precautions when knocking out knockout holes To punch out a knockout hole, hit it with a hammer. Open an appropriate hole as needed. After knocking out the holes, trim off the burr, then we recommend you to paint the edges and areas around the edges using the repair paint to prevent rusting.
EDUS371704-N Installation Manual If there is a pressure drop, check for leaks, make repairs and perform 12. Checking of device and installation conditions the air tight test again. Be sure to check the followings. For those doing electrical work 1 Make sure there is no faulty transmission wiring or loosening of a nut.
Installation Manual EDUS371704-N 1 Front panel 2 Inspection door 3 Main printed circuit board with 3 seven-segment display and 3 push buttons When no trouble occurs: lighted as indicated (8-10 minutes). Operate the switches and push buttons with an insulated stick (such as a closed ballpoint pen) to avoid touching of live parts.
EDUS371704-N Installation Manual 13.2.2. Operating the DIP switches By operating the DIP switches it is possible to: nected to the system. What to do with DIP switch DS1 Result: mode 1 setting 10 is addressed and selected, return value is Cool/Heat selector (refer to the manual of the Cool/ monitored information.
Installation Manual EDUS371704-N 14.2. Calculating the additional refrigerant charge Parameter [D] Indoor unit FXMQ type NOTE capacity The refrigerant charge of the system must be less than 210 lbs. type (100 kg). This means that in case the calculated total refrigerant Refrigerant charge is equal to or more than 209 lbs.
EDUS371704-N Installation Manual 14.3. Method for adding refrigerant 14.3.1. Flow chart Step 1 Calculate additional refrigerant charge amount: R (lbs. (kg)) Step 2+3 Close valves C and A Open valve B to the liquid line Disconnect the manifold from the suction gas line and the high/low pressure gas line Step 4a Refrigerant overcharge happened, recover...
Page 120
Installation Manual EDUS371704-N << Continuation of previous page Heating charging Cooling charging (“ 22” startup control) (“ 02” startup control) (“ 23” waiting for stable heating) (“ 03” waiting for stable cooling) “ 23 “ 03 Push BS2 within 5 minutes Push BS2 within 5 minutes Open valve A Open valve A...
Page 121
EDUS371704-N Installation Manual If the additional refrigerant amount is smaller than 22 lbs. (10 kg), NOTE If the power of some units is turned off, the charging procedure can- below. If the additional refrigerant charge is larger than 22 lbs. (10 kg), In case of a multiple outdoor system, turn on the power of all out- perform step 3 till the end of the procedure.
Page 122
Installation Manual EDUS371704-N - If the unit indicates , or , the ambient conditions are NOTE The refrigerant charging port is connected to the piping inside the automatic charging procedure. unit. The unit’s internal piping is already factory charged with refrig- INFORMATION erant, so be careful when connecting the charge hose.
EDUS371704-N Installation Manual Perform the test procedure as described in 15.4.2. Test operation on 14.3.4. Checks after adding refrigerant Are all stop valves open? Is the amount of refrigerant, that has been added, recorded on the INFORMATION refrigerant charge label? When a malfunction is detected during the procedure (e.g., in case of closed stop valve), a malfunction code will be displayed.
Page 124
Installation Manual EDUS371704-N 9 Stop valves Low noise operation can be set in mode 2. There are two Be sure that all stop valves are open. methods to activate low noise operation of the outdoor unit system. 10 Damaged equipment Check the inside of the unit on damaged components or squeezed pipes.
Page 125
EDUS371704-N Installation Manual 15.2.2. Mode 2 If the system needs to be running under low noise opera- value is possible. tion or under power consumption limitation conditions when In general, normal operation can be resumed without special interven- changed. This setting will only be effective when the optional Default value=0.
Page 126
Installation Manual EDUS371704-N consumption limitation) Default value=2. If the system always needs to be running under power Value Start time automatic low noise consumption limitation conditions, this setting activates and [2-26] 8:00 p.m. applied continuously. The level is according to the table. 10:00 p.m.
Page 127
EDUS371704-N Installation Manual Default value=1. Default value=1. In case the outdoor unit is installed in the lowest position Value Cooling comfort setting (indoor units are installed on a higher position than outdoor [2-81] units) and the height difference between the highest indoor Mild (default) Other changes/limitations to the circuit apply, for more information see 7.5.
Page 128
Installation Manual EDUS371704-N much heating under high outdoor ambient temperatures (e.g., 59°F To activate the powerful comfort setting under heating opera- (15°C)) as under low outdoor ambient temperatures (e.g., 23°F (–5°C)). Using this idea, the system automatically starts decreasing its re- frigerant temperature, automatically reducing the delivered capacity Quick Overshoot (during heating operation) or undershoot (during cooling...
Page 129
EDUS371704-N Installation Manual Example: Automatic mode during cooling Example: Automatic mode during cooling 100% 100% 120°F (49°C) 115°F (46°C) 43°F (6°C) 37°F (3°C) 95°F (35°C) 36°F (2°C) A Actual load curve A Virtual load curve (default automatic mode peak capacity) B Virtual load curve (initial capacity automatic mode) B Load curve C Virtual target value (initial evaporation temperature...
Installation Manual EDUS371704-N No matter which control is selected, variations on the behavior of the INFORMATION system are still possible due to protection controls to keep the unit operating under reliable conditions. The intentional target, however, put may be higher. This phenomenon originates from the compressor that requires a 50 hour run elapse before reaching smooth operation consumption and comfort, depending on the application type.
EDUS371704-N Installation Manual The test operation is automatically carried out, the outdoor unit 15.4.3. Correcting after abnormal completion of the test display will indicate and the indication Test operation and operation Under centralized control will display on the user interface of The test operation is only completed if there is no malfunction code indoor units.
Page 132
Installation Manual EDUS371704-N Malfunction code Contents Solution Main Sub code code Master/sub 1/sub 2 01/02/03 Reverse connection of high/low pressure gas pipe and Check connection of high/low pressure gas pipe and suction gas pipe of Branch Selector unit. suction gas pipe. 01/03/05 Discharge temperature too high (R2T/R21T/R22T): Open stop valves.
Page 133
EDUS371704-N Installation Manual Malfunction code Contents Solution Main Sub code code Master/sub 1/sub 2 06/08/10 Low pressure sensor malfunction: open circuit Check connection on printed circuit board or actuator. (S1NPL)-A1P (X31A) 07/09/11 Low pressure sensor malfunction: short circuit Check connection on printed circuit board or actuator. (S1NPL)-A1P (X31A) 14/15/16 Transmission trouble.
Page 134
Installation Manual EDUS371704-N Malfunction code Contents Solution Main Sub code code Master/sub 1/sub 2 Connection malfunction over indoor units or type Check if other indoor units have malfunction and con- mismatch (R407C, Mini-split, etc). Correct the units combination. Assembly defect of indoor, Branch Selector and Check and modify the number of indoor units that outdoor units (e.g.
EDUS371704-N Installation Manual For details refer to the wiring diagram labelled on the back of the 16. Operation of the unit Once the units are installed and test operation of outdoor units, Pay attention to the fan. It is dangerous to inspect the unit while the the system can start.
Installation Manual EDUS371704-N the refrigerant from the system). Pay special attention to places, such as basements etc., where refrigerant can stay, since refrigerant is heavier than air. Procedure for checking maximum concentration 2 below and take whatever action is necessary to comply. 1 Calculate the amount of refrigerant (lbs.
Page 140
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Need help?
Do you have a question about the REYQ-TAYDU and is the answer not in the manual?
Questions and answers