Cabinet and Rack Installation
•
•
Cabinet and Rack Requirements
This section provides the Cisco MDS 9000 Family requirements for the following types of cabinets and racks,
assuming an external ambient air temperature range of 0 to 40°C:
• Standard perforated cabinets
• Solid-walled cabinets with a roof fan tray (bottom to top cooling)
• Standard open racks
• Telco racks
Note
General Requirements for Cabinets and Racks
The cabinet or rack must be one of the following rack types:
• Standard 19 in. four-post EIA cabinet or rack, with mounting rails that conform to English universal hole
• Standard two-post telco rack, with mounting rails that conform to English universal hole spacing per
The cabinet or rack must also meet the following requirements:
• The minimum vertical rack space per chassis should be 1 RU (rack unit), equal to 1.75 in. (4.4 cm).
• The width between the rack-mounting rails must be at least 17.75 in. (45.1 cm). For four-post EIA racks,
Cabinet and Rack Requirements, on page 1
Cisco MDS 9000 Family Telco and EIA Shelf Bracket, on page 3
If you are selecting an enclosed cabinet, we recommend one of the thermally validated types listed above:
standard perforated or solid-walled with a fan tray.
spacing per section 1 of ANSI/EIA-310-D-1992. See the
and
Requirements Specific to Solid-Walled Cabinets
section 1 of ANSI/EIA-310-D-1992. See the
this is the distance between the two front rails.
Requirements Specific to Perforated Cabinets
sections.
Requirements Specific to Telco Racks
Cabinet and Rack Installation
section.