No claims can be derived f rom the inf ormation, illustrations and descriptions in this documentation. Any duplication, f urther processing and translation of this document as well as excerpts f rom it require the writt en approval of Indu-Sol GmbH. Indu-Sol GmbH expressly reserves all rights under copyright law. WARNING Commissioning and operation of this device may only be carried out by qualif ied personnel.
1.3.1 Operating personnel 1.3.2 Dealing with MULTIrep 1.3.3 Intended Use Connections and status displays on the device Device connections MULTirep X2 Device connections MULTirep X5 Device connections MULTirep X7 Status LED Installation Installation Power supply Connection to the PROFIB US network 3.3.1...
The PROFIBUS repeaters MULTIrep X2, X5 and X7 not only meet all the requirements f or modern, f lexible PROFIBUS cabling. Thanks to the integrated interf erence suppression f unction, they also ensure the greatest possible stability of data communication.
General information 1.3.3 Intended Use The devices are designed f or use in industrial areas with protection class IP20. These must theref ore not be connected directly to the public low-voltage network, the installation must be carried out in an industrial control cabinet.
Run / Power / Bus / Data X1 PROFIBUS – connections (D-Sub 9-pin) CH1 - Channel 1 CH2 - Channel 2 Illustration1: Device connections MULTIrep X2 Device connections MULTirep X5 X2 power supply Status - LED Run / Power / Bus / Data...
Connections and status displays on the device Device connections MULTirep X7 X2 power supply Status - LED Run / Power / Bus / Data X1 PROFIBUS connections (D-Sub 9-pin) CH1 - Channel 1 CH2 - Channel 2 CH3 - Channel 3 CH4 - Channel 4 CH5 - Channel 5 Illustration3: Device connections MULTIrep X7...
Installation 3 Installation Installation The MULTIrep is installed horizontally in the control cabinet on a 35 mm DIN rail according to DIN EN 60715. Danger:For correct installation, the f ollowing distances to other assemblies must be observed: • To the lef t and right: 20mm •...
Installation The PROFIBUS cable can be connected in dif ferent ways. All two options are shown and described below. 3.3.1 Installation at the beginning or end of a segment If the PROFIBUS segment begins or ends on a channel of the MULTIrep (connection X1) (only one line is connected to the PROFIBUS connector), then the terminating resis tor integrated in the PROFIBUS connector must be switched on (termination: "ON").
20% • Power Consumption: max. 300mA • Dimensions (H x W x D): MULTIrep X2 - 105 x 75 x 40 mm MULTIrep X5 - 105x145x40mm MULTIrep X7 - 105 x 212 x 40mm • Assembly: TS35 DIN rail (EN 50022) •...