P/N 51659:A4
ECN 04-259
BACnet Gateway
Installation/Operation Manual
Document 51659
A4
06/10/04
Rev:
www.PDF-Zoo.com
firealarmresources.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BACnet Gateway and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier BACnet Gateway

  • Page 1 P/N 51659:A4 ECN 04-259 BACnet Gateway Installation/Operation Manual Document 51659 06/10/04 Rev: www.PDF-Zoo.com firealarmresources.com...
  • Page 2 (especially in bedrooms), smoking in bed, and violent fessional fire alarm installers only. Adequate written records explosions (caused by escaping gas, improper storage of of all inspections should be kept. BACnet Gateway User’s Manual PN 51659:A4 06/10/04 Precau-L-4-2002.p65 www.PDF-Zoo.com firealarmresources.com...
  • Page 3 Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc.
  • Page 4: Table Of Contents

    2.5 P ....................... 12 OWER UPPLY ONNECTIONS Figure 2.5-1: 46175 Power Supply Specifications ....................12 Figure 2.5-2: BACnet Gateway Power Connection .................... 12 2.6 DB-9 NUP C NCM-W/F) ............... 13 ONNECTION ATEWAY TO Figure 2.6-1: DB-9 to NUP Connection ......................13 2.7 PC...
  • Page 5 4.2 FTP ..............................22 Figure 4.2-1: The BACnet Tab ..........................22 APPENDIX A: PIC STATEMENT ....................23 ) ........23 ROTOCOL MPLEMENTATION ONFORMANCE TATEMENT ORMATIVE GLOSSARY ............................26 INDEX ............................... 27 BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 6: Section One: Bacnet Gateway Features

    NOTI•FIRE•NET™ resident Fire Alarm Control Panels (FACPs). The BACnet protocol is an American National Standard (ANSI/ASHRAE 135-1995). This document describes the installation and configuration of the BACnet Gateway using the Serial Configuration Tool. The Gateway represents physical fire devices as BACnet objects. As events occur, the object properties are updated in realtime, and messages are sent to the appropriate BACnet report destination.
  • Page 7: Standards And Specifications

    YSTEM EQUIREMENTS The BACnet Gateway can monitor up to fifteen panels, but the combined object count across the monitored panels cannot exceed 15,000 objects. This includes all detectors, monitor modules, control modules, bell circuits, etc. The computer on which the Serial Configuration Tool resides must use Windows 98 or Window NT v4.0 or later. The computer must also have a non-dedicated serial port for communicating with the Gateway.
  • Page 8 Figure 1.7-2: Typical Wiring Diagram for CAB-3/CAB-4 Series Enclosures NOTE: All BACnet Gateway circuits are power limited. Route wiring per the power limited and non-power limited constraints defined in the pertinent Fire Alarm Control Panel manual.
  • Page 9: Network Architecture

    ETWORK RCHITECTURE The diagram below shows the end-to-end architecture of a system using the BACnet Gateway: For details on wiring the NCM or MIB to the network, refer to the NOTI•FIRE•NET™ BACnet/IP Workstation manual. Ethernet The BACnet Gateway, NCM, Power...
  • Page 10: Section Two: Bacnet Gateway Installation

    RJ45 to RJ45 standard Ethernet network cable (P/N 75585) - provides connection from BACnet PC board to PNET-1 surge suppressor • PC to PC connector cable - connects the BACnet Gateway to a PC or laptop. NOTE: These items must be •...
  • Page 11: Installing The Bac Net Gateway Assembly Into Acab-4 Series Cabinet

    HDD Power Connector connection to (P1) NOTI•FIRE•NET™. RJ45 Ethernet Connector PC-PC connector - used for (CN2) configuration (cable supplied by customer). Figure 2.4-1: PC Board Layout BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 12: Power Supply Connections

    ONNECTIONS The power supply for the BACnet Gateway is a 24VDC-to-5VDC unit (P/N 46175). When using an NCM-W/F, it can be powered by a Notifier Fire Alarm Control Panel (FACP) or an external power supply. For details on powering and connecting an NCM-W/F, refer to its Product Installation Document 51533.
  • Page 13: Ncm-W/F)

    PNET-1 out to the BACnet front end. This is the connection that facilitates communication between the NOTI•FIRE•NET™ network and the BACnet network. Once the Gateway is on the network, it will appear as the NCS device type (network version 4.0) or BACnet Gateway device type (version 5.0 networks).
  • Page 14: Section Three: Configuration And Operation

    3. This will execute the install application. Simply follow the directions on screen to install the Serial Configura- tion Tool. 4. Once it is installed, it can be started from the Start Menu in the BACnet Gateway program group. 3.2 U...
  • Page 15: Serial Configuration Tool Com Settings

    COM settings must be configured first for the Gateway to begin communicating with the Serial Configuration Tool. The BACnet Gateway provides the user with four COM port options to use for connection to the Gateway. If your computer contains fewer than four COM ports, only the ones that exist on that computer will be options on this screen.
  • Page 16: Bac Net Gateway Configuration

    Leave the user name field blank to keep the default or current user logged in. Apply - Clicking Apply will implement any configuration changes made from this tab. Figure 3.4-1: The Gateway Tab BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 17: The Multi Tab

    Gateways offline, before they are ever connected to the network. Otherwise, the Gateway will find the first fifteen that come online and ignore the rest. NOTE: If you have fifteen or fewer panels, configuration settings on the Multi tab are unnecessary. Figure 3.5-1: The Multi Tab BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 18: Network Settings

    Gateway. Once the Gateway’s time has been synchronized, it will then synchronize all other NOTI•FIRE•NET™ devices at the next Network Update time and on the hour. Figure 3.6-1: The Network Tab BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 19: Bac Net Settings

    BBMD IP - Enter the IP address of the BBMD here. BACnet Port - Enter the port on which the BBMD communicates Register Time - Enter the frequency (in seconds) used by the BACnet Gateway to send the “Register Foreign Device” message to the specified BBMD.
  • Page 20: Bac Net Information Tab

    VxWorks: - This specifies the version number of the operating system running on the Gateway. Gateway Version: - This line displays the version number of the NOTI•FIRE•NET™ BACnet Gateway. Gateway IP Address: XXX.XXX.XXX.XXX - This is the user-assigned static network IP address of the BACnet Gateway.
  • Page 21: Section Four: Administrative Operations

    Telnet is used to monitor network traffic and other pertinent system information. Using Telnet as a diagnostic tool, you can determine which nodes are communicating with the BACnet Gateway. To begin a Telnet session, Click on Start, Run. Then, type Telnet in the Open field, and the Telnet screen will be displayed (see Figure 4.1-1).
  • Page 22: 4.2 Ftp

    • The destination drive letter can either be a hard drive or floppy drive on the current computer or a drive on another computer on the network. Figure 4.2-1: The BACnet Tab BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 23: Appendix A: Pic Statement

    BACnet Protocol Revision: 1.2 Product Description: This product presents Notifier Fire Panel and Annunciator nodes (operating as part of a NOTI•FIRE•NET™ network or stand-alone) and their associated objects as BACnet objects. Event notification for Alarms, Troubles and other states are sent to registered BACnet clients.
  • Page 24 EsNormal Normal EsFault Security Trouble, Fire Trouble, Non-Fire Trouble, Fire Device or Zone Disabled, Non-Fire Device Disabled EsOffNormal All statuses other than normal and fault. Reliability BACnet Enumeration BACnetReliability NFN State BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 25 If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: Notifier Fire and Annunciator nodes compatible with NOTI•FIRE•NET™ v4.0 and later operating in a network or stand-alone configuration. BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com...
  • Page 26: Glossary

    FTP - File Transfer Protocol, used to back up the BACnet Gateway database and download firmware for field upgrades. BACnet Gateway - A Notifier PC board interface that allows the NOTI•FIRE•NET™ network to communicate with a BACnet network.
  • Page 27: Index

    Database Backup 22 Gateway IP Address 16 Information Tab 20 Installation Hardware Cabinetry 11 Network Connection 13 NUP 13 Power Supply 12 IP Address 16 Multi Tab 17 Network Connection 13 BACnet Gateway User’s Manual PN 51659:A4 06/10/04 www.PDF-Zoo.com firealarmresources.com...
  • Page 28 ® manufacturing date-stamp control, the warranty ® is eighteen (18) months from date of original purchase by NOTIFIER 's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, ®...