Det-Tronics modules that might be damaged by static electricity are carefully wrapped in a static protective A warning label is placed on the packaging, identify- material before being packaged.
Table of Contents SECTION I Auxiliary Gateway ............10 Faceplate Description ............10 SYSTEM OVERVIEW LEDs ................11 Relays ................11 APPLICATION .................1 Automatic Diagnostics ...........11 FEATURES ................1 Fault Tolerant Communication ........12 System Capacity ............12 SYSTEM DESCRIPTION ............1 Installation ..............12 Detector ................1 Communication Gateway – EA2100CG ......2 SECTION V Communication Module –...
Page 4
Figure 12 Basic Eagle System with One Gateway ...13 SECTION VIII Figure 13 Expanded System with Two Network SYSTEM STARTUP Extenders ............14 Figure 14 Eagle System with Two Gateways ....14 STARTUP PROCEDURE ............28 Figure 15 Recommended Grounding for Cable Shields ..17 SYSTEM CONFIGURATION ..........28 Figure 16 Wiring Configuration for Communication Module...
While this manual cov- ers general practices and procedures for installa- tion and wiring of the Eagle 2000 system, always refer to the instruction manual provided with each device for specific instructions.
The communication module circuit board is identical to the circuit board used in the communication module described Refer to Section IV of this manual for a complete above. The DCU enables the use of Det-Tronics basic description of gateway operation. sensor/transmitters, which attach directly to the DCU...
sive calibration. Unlike the communication module, the NETWORK OPERATION DCU allows the operator to view three status indicating DURING A FAULT CONDITION LEDs through a viewing window on the enclosure cover. The Eagle system utilizes a unique method for detecting an open or short in the communication network wiring.
In the event of a single wiring fault, normal communica- The Eagle communication module is compatible with tion will continue between all communication modules most Det-Tronics flame detection, gas detection or envi- and the main gateway. However, if the system uses a ronmental monitoring devices.
OUTPUTS— The red LED indicates the various steps of the calibra- Digital communication, transformer isolated (78.5 tion process. When the calibration begins, the red LED Kbps). Calibrated 0 to 4095 digital output corresponds flashes at a 1 Hz rate. When the zero part of the cali- to 0 to full scale current input from transmitter.
OUTPUTS Calibration Log A 5 ampere SPDT relay is provided. When the commu- A log is kept for each calibration. This information can nication module is used with a U8700 or U8800, the be used by the operator to evaluate the remaining life of relay output is used to reset the transmitter.
The Eagle 2000 Digital Communication Unit (DCU) digi- energized or during startup. tizes a 4 to 20 ma analog signal from a basic Det-Tronics gas sensor/transmitter and transmits the value as a pro- DCU with transmitter and combustible gas sensor: cess variable to the Eagle communication gateway.
4.5 (11.4) ENCLOSURE 0.3 DIA. 4.1 (10.4) (0.8) 3.38 (8.4) The explosion-proof, watertight aluminum enclosure is designed for use in Class I, Division 1, Groups B, C and D hazardous locations. It is designed to meet CEN- ELEC requirements for EEx d IIC T5 hazardous loca- tions, and is IP66 and NEMA 4 rated.
APPLICATION DIMENSIONS— The gateway provides the communication link between a See Figure 9. Det-Tronics addressable detector and the host device. Registers in the gateway are used for passing information DESCRIPTION between the host and communication modules. The gate- way communicates with the host device through a serial The Eagle gateway transmits information from the com- interface port (RS232 or RS422) using Modbus protocol.
AUXILIARY GATEWAY Digital Display Auxiliary gateways are used to connect additional host The digital display is a three digit “seven segment” dis- devices to the loop for data acquisition purposes. play. During normal operating conditions, the display Additional host devices are not able to modify configu- indicates “000.”...
Table 1—Detector Type Codes LEDs Five faceplate LEDs are provided for indicating the sta- tus of the gateway relays. The LEDs correspond to the active state of the relay, not the coil condition. When the relay is reset, the corresponding LED is also reset. RELAYS The gateway is provided with five relays.
–49°F to +185°F (–45°C to +85°C). INSTALLATION Operating: Refer to the “System Capacity” section (under General Application Information) The Eagle Communication Gateway is rack mountable for temperature limitations. and occupies two spaces in a standard Det-Tronics Q4004 Mounting Rack (in a non-hazardous area).
HUMIDITY— GENERAL INFORMATION 0 to 95% RH at 70°C. SYSTEM CAPACITY WIRING— Eagle system technology allows the main gateway to The communication network requires 22 AWG level 4 support a communication loop consisting of up to 60 shielded twisted pair wire. Other wiring should be 18 detection nodes, with up to 2000 meters of connecting AWG minimum.
RESPONSE TIME VERSUS SYSTEM SIZE put actuation are met. The Eagle 2000 is a highly versatile system that allows The specific status conditions to which the relay module up to 250 detection points to operate on a single com- will respond are selected at the time of configuration.
Table 4—Status Conditions Capable of Actuating Relay OUTPUTS— One SPDT sealed relay, rated 5 amperes resistive at 30 Communication Module Condition vdc, programmable for normally energized or normally Status Word Bit de-energized operation. Com 1 Fault Com 2 Fault POWER CONSUMPTION— Sensor Fault 60 ma nominal, 80 ma maximum at 24 vdc during nor- Calibration...
ADDRESSABILITY All external wiring is connected to screw terminal con- nectors on the terminal wiring board that is factory Relay module identification is accomplished by setting mounted inside the enclosure. The electronic module is rocker switches on an eight position DIP switch located on mounted inside the enclosure above the terminal wiring board and is connected to the terminal wiring board the electronic module.
“breathing.” Moisture in the air can condense at the NODE GATEWAY NODE base of vertical conduit runs and equipment enclosures, and can build up over a period of time. This can be detrimental to electronic devices. To eliminate this con- dition, explosion-proof drains and breathers should be installed to automatically bleed off accumulated water.
Page 22
Temperature. Resistance increases as operating tem- Example B: perature rises. Calculate resistance at a worst case How many combustible gas DCUs can operate at temperature of 75˚C. See Table 5. the end of a 1000 foot length of 14 AWG wire? Type of device.
The recom- conduit is being used). mended lubricant is a silicone free polyalphaolefin grease, available from Det-Tronics. If the installation 6. Set the node address for the communication mod- uses catalytic type combustible gas sensors, it is ule.
GATEWAY/ COM MOD CHASSIS GROUND ALARM DETECTOR POWER NETWORK IN (24 VDC) – ALARM CALIBRATE 4 TO 20 MA IN NETWORK OUT CALIBRATE IN 2 DIGITAL INPUT 2 FAULT FAULT IN 1 DIGITAL INPUT 1 24 VDC POWER INPUT – POWER –...
DETECTOR POWER POWER NETWORK IN – (24 VDC) – WHITE SENSOR 4 TO 20 4 TO 20 MA IN NETWORK OUT BLACK IN 2 DIGITAL INPUT 2 GAS TRANSMITTER IN 1 DIGITAL INPUT 1 24 VDC POWER INPUT – – RELAY RELAY COMMON COMMUNICATION MODULE/DCU...
RACK PART NUMBER CONTROLLER TYPE 005269-XXX POSITIONS FOR: DIM. (A) DIM. (B) DIM. (C) DIM. (D) DIM. (E) WEIGHT FIRE INCH INCH INCH INCH INCH –001 19.00 482.6 18.30 464.8 17.36 440.9 4.00 101.6 6.97 177.1 –002 15.06 382.6 14.36 364.7 13.42 340.9 –003...
For complete information regarding system configuration, refer to the Det-Tronics EagleVision Software manual for systems equipped with the Det-Tronics Operator Interface System. For other systems, refer to form 95-8433 for con-...
CALIBRATION ALGORITHM A If the calibration is not completed within 12 minutes, the (Type Codes 1, 2, 3, 4) for Gas Detectors previous calibration values are restored and the calibra- tion is logged as aborted. The calibrate LED flashes at Normal Calibration a 4 Hz rate, the calibrate bit in the status word is reset and the calibration fault bit is set.
CALIBRATION ALGORITHM A Calibration After Sensor Replacement (Type Codes 1, 2, 3, 4) for Environmental Monitors 1. Open the communication module junction box cover and press the sensor replacement switch. Normal Calibration 2. The calibrate LED on the communication module 1.
CALIBRATION ALGORITHM B (Type Codes 5, 6) If the calibration is not completed within 10 minutes, the previous calibration values are restored and the calibra- Normal Calibration tion is logged as aborted. The calibrate LED blinks at a 4 Hz rate, the calibrate bit in the status word is reset, 1.
CALIBRATION ALGORITHM C Calibration After Sensor Replacement – (Type Codes 7, 8, 9, 10) Combustible Gas 1. Open the junction box cover and press the sensor Normal Calibration replacement switch for about 1 second. 1. Apply the zero gas. (See Figure 31.) 2.
Calibration After Sensor Replacement – Toxic Gas CALIBRATION ALGORITHM D (Type Codes 11, 12, 13, 14) 1. Open the junction box cover and press the sensor replacement switch for about 1 second. Normal Calibration 2. The calibrate LED on the communication module 1.
ACCEPT ZERO ACCEPT SPAN A1555 UNCONTROLLED ANALOG SIGNAL 3 SEC 3 SEC 3 SEC REED SWITCH ANALOG IN FRESH AIR ACCEPT ZERO A1555 UNCONTROLLED ANALOG SIGNAL Figure 32—Calibration Algorithm "D" 3 SEC 3 SEC 3 SEC CALIBRATION ALGORITHM E 3. Apply the zero input (4 ma). IN ONE (Type Codes 23 and 24) 4.
Section IX Calibration After Sensor Replacement System Maintenance 1. Open the junction box cover and press the sensor replacement switch. ROUTINE MAINTENANCE 2. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating it is ready for the To ensure reliable protection, it is important to check zero input.
CAUTION DEVICE REPAIR AND RETURN The O-ring should be lubricated with a silicone free Prior to returning devices or components, contact the polyalphaolefin grease. The use of other lubri- nearest local Detector Electronics office so that an RMI cants is not recommended, since they can (Return Material Identification) number can be assigned.
Page 41
FRANCE RUSSIA Telephone 33 1 3497 0650 Telephone 7 (095) 135 5389 Facsimile 33 1 3497 0648 Facsimile 7 (502) 222 1276 Det-Tronics Deutschland Det-Tronics Scandinavia AB Deugra GmbH Box 81 Postfach 1457 S-260 83 Vejbystrand Harkortstrasse 3 SWEDEN D-4030 Ratingen 1...
ORDERING INFORMATION REFERENCE LIST For assistance in ordering or designing an Eagle sys- Additional information on Eagle 2000 products is avail- tem, contact the nearest Detector Electronics office. able in the following publications: Specification Data Sheets: When ordering, please specify:...
Page 43
DETECTOR ELECTRONICS CORPORATION 6901 West 110th Street Minneapolis, Minnesota 55438 USA Telephone (612) 941-5665 or (800) 765-FIRE Facsimile (612) 829-8750 Telex 6879043 DETEL UW Cable Detronics Printed in USA...
Need help?
Do you have a question about the Eagle 2000 and is the answer not in the manual?
Questions and answers