Page 1
1/2024 MTP200ia-TE-SIL Operating instructions MTP200ib-TE-SIL WINSMART support MODBUS-RTU communication Mütec Instruments GmbH Tel.: +49 (0) 4185-80 83-0 e-Mail: muetec@muetec.de Bei den Kämpen 26 Fax: +49 (0) 4185-80 83-80 Web: www.muetec.de D-21220 Seevetal...
Page 2
1/2024 Operating instructions for MTP200ia-TE-SIL, MTP200ib-TE-SIL WINSMART support from MTP200 version 4.0 MODBUS-RTU communication Publication no.: BA 125 Date of issue: 1/2024 Manufacturer: Mütec Instruments GmbH Bei den Kämpen 26 21220 Seevetal Germany Tel: +49 (0) 4185 8083-0 Fax: +49 (0) 4185 808380 e-mail: info@muetec.de...
1/2024 Table of content Table of contents ............................Safety regulations and instructions..................installation Classification of the safety instructions ....................... General information ............................Introduction ..............................1.0 General information for installation and operation ................2.0 Technical features ............................ 3.0 ATEX relevant data ..........................
1/2024 Safety regulations and instructions Follow the instructions for installation: Note: Installation, operation and maintenance may only be carried out by qualified personnel. The applicable safety guidelines (including the national safety guidelines), accident prevention regulations and general technical regulations must be observed when installing and operating the appliance.
1/2024 Classification of the instructions This manual contains instructions that you must observe for your personal safety and to prevent damage to property. The instructions are highlighted by a warning triangle and shown as follows, depending on the degree of danger. DANGER means that death or serious bodily injury will occur, if the appropriate precautions are not taken.
1/2024 General information This appliance has left the factory in a technically safe condition. In order to maintain this condition and to ensure safe operation of the appliance, the instructions and warnings given in these operating instructions must be observed by the user. NOTE For reasons of clarity, these instructions do not contain all detailed information on all types of the product and cannot take into account every conceivable case of installation, operation or...
1/2024 General information for installation and operation Labeling according to Directive 2014/34/EU: 0158 II (2) G Checkpoint Device group Associated equipment with external circuits for connection to category 2 devices for explosive mixtures of air and flammable substances Gases, vapors or mists Marking of the type of protection: [Ex ia Ga] IIC associated electrical operating...
1/2024 The Pt100/resistance transmitter input at terminals KL21, KL22, KL23 and KL24 and, in parallel, the temperature reference junction input at terminals KL19 and KL20 correspond to the "intrinsic safety" type of protection of category "ia" or "ib". The thermocouple/mV input at terminals KL17 and KL18 corresponds to the "intrinsic safety" type of protection of category "ia"...
24V AC/DC supply with undervoltage cut-off 3.0 ATEX relevant data Ex certificate BVS 08 ATEX E 043 1st addendum II (1) G [Ex ia Ga] IIC for MTP200ia-TE-SIL II (2) G [Ex ib Gb] IIC for MTP200ib-TE-SIL Conformity EN IEC 60079-0:2018...
1/2024 Analog output: Alarm value lim-prio, parameterizable: Signal deviation Permanent automatically from 0.2 % light Instantaneous from value limit A/D converter: Alarm value lim-prio , parameterizable: Signal deviation Permanent automatically from 0.2 % light Instantaneous from value limit mA measuring Alarm value lim-prio, parameterizable:...
Page 13
1/2024 Resistance remote sensor/potentiometer (DIN 43822) AE3 Connection: 2-, 3- and 4-Lt. technology 0 ... 600 or 0 ... 5000 Measuring range: min. 3 , max. 600 or 5000 Measuring span: Measuring current: 1/0.2 mA 0,01/0,1 Measured value resolution: 100 ...
Page 14
1/2024 Contact outputs REL1/REL2 Contact: Normally closed or normally open contact (according to jumper position) Switching capacity: max. 62.5 VA or max. 30 W Switching voltage: max. 125 V AC or 110 V DC Switching current: max. 1 A Minimum contact voltage: 10 mVDC Minimum contact current: 10 µA...
Page 15
1/2024 Temperature coefficient Maximum: < 0,01 %/K Typical: < 0,005 %/K Galvanic isolation Input/output/supply: 300 Vrms (rated insulation voltage, overvoltage protection) category II, pollution degree 2, safe isolation according to EN 61010, EN 50178); 2.5 kV AC test voltage (50 Hz, 1 min.); Input/output: 375 V (peak value according to EN 60079-11) Input/supply:...
1/2024 Technical data: 5-pin connector with 3.81 mm pitch; 8 A maximum contact load; High contact quality due to gold plating; Mounting in NS 35/7.5 or NS 35/15 top-hat rails; Only connect/disconnect the device to/from the TBUS connector without power! 5.1 Configuration protocol ...
1/2024 Calculation of the max. line resistance for the analog output Data of the analog output (AA) for constant current: Max. Range: 0...22 mA Standard range: 0/4-20 mA Load: max. 500 Ohm at 20 mA Accuracy: 0.02 % of the final value Burden influence: <0,005 % The maximum load for the analog output is the sum of the resistances of the forward and return...
Page 18
1/2024 Cable lengths as a function of diameter and input resistance: (shunt (diameter cross section length length [Ω] [mm] [km] 0,283 3179 3,18 0,385 4325 4,33 0,502 5640 5,64 0,636 7146 7,15 0,785 8820 8,82 (shunt (diameter cross section length length [Ω] [mm]...
1/2024 For the resistance measurement (input KL21 - KL24), the terminal block KL17 - KL20 must be removed! The parallel connection of the resistance to be measured and the Pt100 in the terminal block would otherwise falsify the measured value. 5.7 Jumper settings Jumpers JP1 and JP2: Jumper JP1 for relay contact REL-1 or jumper JP-2 for relay contact REL-2 determines the contact...