Display on
Fault Name and
GS20(X)
ID No.
Description
Keypad
Internal communication
error (EoL3)
EoL3
134
Electronic thermal relay
3 protection� The drive
coasts to stop once it
activates�
Internal communication
error (EoL4)
EoL4
135
Electronic thermal relay
4 protection� The drive
coasts to stop once it
activates�
DURApulse GS20 & GS20X AC Drive User Manual – 1st Edition, Rev D
Chapter 6: Maintenance and Troubleshooting
Fault Codes (continued)
Action, Reset, and Corrective Action
Action Level
Start counting when output current > 150% of the motor 3 rated current�
P14�81 (If the output current is larger than 105% of the motor 3 rated
Action Time
current again within 60 sec�, the counting time reduces and is less than
P14�81)
Fault setting
N/A
parameter
Reset method
Manual reset
Reset condition Reset in five seconds after the fault is cleared
Record
Yes
1) Reduce the load�
2) Increase the setting value for P01�12–P01�19 (accel�/decel� time)
3) Adjust the settings for P01�54–P01�61 (V/F curve), especially the
setting value for the mid-point voltage (if the mid-point voltage is set
too low, the load capacity decreases at low speed)� Refer to the V/F
curve selection of P01�43�
4) If the EoL3 only occurs during low-speed operations:
a) Replaced the drive with a dedicated VFD model�
b) Increase the motor capacity�
Corrective
5) If using a VFD dedicated motor, verify P14�80=1: Standard motor
Actions
(motor with fan on the shaft)�
6) Verify motor rated current and reset if needed�
7) Verify motor rated frequency and reset if needed�
8) If using one drive to run multiple motors, set P14�80=2: Disable, and
install thermal relay on each motor�
9) Set stall prevention to the proper value�
10) Adjust P07�73 torque compensation gain until the current reduces
and the motor does not stall�
11) Check the status of the fan, or replace the fan�
12) Replace the motor�
Start counting when the output current > 150% of the motor 4 rated
Action Level
current�
P14�83 (If the output current is larger than 105% of motor 4 rated current
Action Time
again within 60 sec�, the counting time reduces and is less than P14�83)
Fault setting
N/A
parameter
Reset method
Manual reset
Reset condition Reset in five seconds after the fault is cleared
Record
Yes
1) Reduce the load�
2) Increase the setting value for P01�12–P01�19 (accel�/decel� time)
3) Adjust the settings for P01�62–P01�70 (V/F curve), especially the
setting value for the mid-point voltage (if the mid-point voltage is set
too low, the load capacity decreases at low speed)� Refer to the V/F
curve selection of P01�43�
4) If the EoL4 only occurs during low-speed operations:
a) Replaced the drive with a dedicated VFD model�
b) Increase the motor capacity�
Corrective
5) If using a VFD dedicated motor, verify P14�82=1: Standard motor
Actions
(motor with fan on the shaft)�
6) Verify motor rated current and reset if needed�
7) Verify motor rated frequency and reset if needed�
8) If using one drive to run multiple motors, set P14�82=2: Disable, and
install thermal relay on each motor�
9) Set stall prevention to the proper value�
10) Adjust P07�75 torque compensation gain until the current reduces
and the motor does not stall�
11) Check the status of the fan, or replace the fan�
12) Replace the motor�
(continued next page)
Page 6–49