Table Of Contents ABOUT THIS MANUAL ..................Purpose ......................Scope ......................SAFETY INSTRUCTIONS..................INTRODUCTION....................Features ......................Basic System Architecture .................. Product Overview ..................... INSTALLATION....................Unpacking and Inspection ................. Preparation ....................Mounting the Unit .................... Battery Connection ................... AC Input/Output Connection ................
ABOUT THIS MANUAL Purpose This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference. Scope This manual provides safety and installation guidelines as well as information on tools and wiring. The following cases are not within the scope of warranty: (1) Out of warranty.
INTRODUCTION This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications. Features Pure sine wave inverter Configurable input voltage range for home appliances and personal computers via LCD setting...
Product Overview NC C NO NC C NO 4KW single model 1. LCD display 2. Status indicator 3. Discharging/Charging indicator 4. Fault indicator 5. Function buttons 6. Power on/o ffswitch 2.2-3KW single model 7. AC input 8. AC output 9. PV input 10.
INSTALLATION Unpacking and Inspection Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package: The unit x 1 User manual x 1 USB cable x 1 Preparation Before connecting all wirings, please take o ffbottom cover by removing two screws as shown below.
Install the unit by screwing two screws. 150.00 194.00 2.2-3KW Battery Connection CAUTION: To safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to have over-current protection installed.
Inverter 2.2KW/3KW/4KW 3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.
Page 9
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
5. Make sure the wires are securely connected. CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are working in parallel operation. CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits.
3. Make sure the wires are securely connected. Recommended PV module configuration PV Module Spec. (reference) Solar Input Q’ty of modules Inverter Model -250W -Vmp:30.9Vdc -Imp:8.42A MPPT-60A 3S3P 9PCS -Voc:37.7Vdc -Isc:8.89A -Cells:60 MPPT-60A Final Assembly After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
Communication Connection Please use supplied communication cable to inverter and PC. Download the software by link on the last page of this manual into computer and follow on screen instruction to install the monitoring software. For the detailed software operation, please consult the seller if you have any questions. CAUTION: Only the CAN prot can be used to communicate with the smart battery pack.You need to use CAN-L,CAN-H and GND to establish a connection.
OPERATION Power ON/OFF Once the unit has been properly installed and the batteries are connected well, simply press On/O ff switch (located on the button of the case) to turn on the unit. Operation and Display Panel The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
LCD Display Icons Icon Function description Input Source Information and Output Information Indicates the AC information. Indicates the DC information. Indicate input voltage, input frequency, PV voltage, battery voltage and charger current. Indicate output voltage, output frequency, load in VA, load in Watt and discharging current.
LCD Setting After pressing and holding "ENTER" button for 2 seconds, the unit will enter setting mode. Press "UP"or "DOWN" button to select setting programs. And then, press "ENTER" or "MENU" button to confirm the selection and exit. Setting Programs: Program Description Selectable option...
Page 17
If selected, acceptable AC input Appliances (default) voltage range will be within 90- 280VAC. If selected, acceptable AC input voltage range will be within AC input voltage range 170-280VAC. If selected, acceptable AC input voltage range will conform to VDE4105(184VAC-253VAC). When the user uses the device to connect the generator, select the generator mode.
Page 18
Only Solar Solar energy will be the only charger source no matter utility is available or not. If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
Page 19
default setting: 20.4V "User-Defined" "LI" is selected in program 14, this program can be set up. Setting range is from 20V to 24.0V for 24Vdc model. Increment of each click is 0.1V. Low DC cut o ffbattery SOC 10% (default) voltage setting ﹪...
Page 20
Solar power balance If selected, the solar input power will be the same to max. Battery disable (default) charging power no matter how much loads are connected. The max.battery charging power will be based on the setting current in program 11 ( Max. solar power = Max.battery charging power ).
when the communication between (default) BMS and converter is faulted ,the converter still charge or discharge from the battery BMS communication when the communication between BMS and converter is faulted ,the converter stop charging or discharging from the battery Setting range is from 0 to 31 lncrement of each click is 1 lf Ll is selected in program 14, program 41 can be set.
Page 22
Main relay failed Inverter output voltage sensor error Inverter grid voltage sensor error Inverter output current sensor error Inverter grid current sensor error Inverter load current sensor error Inverter grid over current error Inverter radiator over temperature Solar charger battery voltage class error Solar charger current sensor error Solar charger current is uncontrollable Inverter grid voltage is low...
Warning Indicator Fault Code Fault Event Icon on Fan is locked when inverter is on. Fan 2 is locked when inverter is on. Battery is over-charged. Low battery. Overload. Output power derating. Solar charger stops due to low battery. Solar charger stops due to high PV voltage. Solar charger stops due to over load.
Inverter power loads from PV energy Off-Grid state The inverter will provide output power from battery and PV power. Inverter power loads from battery and PV energy Inverter power loads from battery only Stop mode The inverter stop working if you turn o ffthe inverter by the soft key or error has occurred in the...
SPECIFICATIONS Table 1 Line Mode Specifications INVERTER MODEL 2.2KW Input Voltage Waveform Sinusoidal (utility or generator) Nominal Input Voltage 230Vac 90Vac±7V(APL,GEN); 170Vac±7V(UPS) Low Loss Voltage 186Vac±7V(VDE) 100Vac±7V(APL,GEN);180Vac±7V(UPS) Low Loss Return Voltage 196Vac±7V(VDE) 280Vac±7V(APL, UPS,GEN) High Loss Voltage 253Vac±7V(VDE) 270Vac±7V(APL,UPS,GEN) High Loss Return Voltage 250Vac±7V(VDE) Max AC Input Voltage 300Vac...
Table 2 Inverter Mode Specifications 2.2KW INVERTER MODEL Rated Output Power 2200W 3000W 4000W Output Voltage Waveform Pure Sine Wave Output Voltage Regulation 230Vac±5% Output Frequency 60Hz or 50Hz Peak Efficiency 5s@≥150% load; 10s@110%~150% load Overload Protection Nominal DC Input Voltage 24Vdc Cold Start Voltage 23.0Vdc...
Page 27
Table 3 Charge Mode Specifications Utility Charging Mode INVERTER MODEL 2.2KW Charging Current 40A( 4A) 60A( 4A) @Nominal Input Voltage AGM / Gel/LEAD Floating 27.4Vdc Battery charging voltage Flooded Battery 27.4Vdc AGM / Gel/LEAD Bulk charging 28.8Vdc Battery voltage (C.V voltage) Flooded Battery 28.4Vdc Charging Algorithm...
Page 28
Charging algorithm for Lithium battery Joint Utility and Solar Charging INVERTER MODEL 2.2KW MPPT-60A CHARGER MODEL Max Charging Current 100A( 4A) 120A( 4A) Default Charging Current 80A( 4A) 90A( 4A) Table 4 General Specifications INVERTER MODEL 2.2KW Safety Certification Operating Temperature Range -10°C to 50°C Storage temperature -15°C~ 60°C...
TROUBLE SHOOTING LCD/LED/Buzzer Explanation/Possible cause What to do Problem Unit shuts down LCD/LEDs and buzzer automatically will be active for 3 The battery voltage is too low. 1. Re-charge battery. during startup seconds and then (<1.91V/Cell) 2. Replace battery. process. complete off.
Appendix: Approximate Back-up Time Table Load (W) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24Vdc 200Ah (min) Model 1610 1000 2.2KW 1200 1400 1600 1800 2000 1100 1200 1500 1800 2100 2400 2700 3000 3500 Note: Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
WARRANTY CARD DATE OF PURCHASE SHIPPING ADDRESS SIGNATURE / STAMP DAMAGE DESCRIPTION SERVICE COMMENTS FILL IN IF NEEDEED (*) Cross incorrect I agree to pay the cost of inverter repair due to: * expiration of the warranty period / * warranty void Before proceeding with the repair, service will inform by phone about the exact costs of the repair.