Page 2
8.1 in (206 mm) 8.1 in (206 mm) 3.5 in (90 mm) 6.3 in (160 mm) 3.5 in (90 mm) 6.3 in (160 mm) Elexant 3500i Pipe Mount Electronic Thermostat Elexant 3500i Wall Mount Electronic Thermostat Figure 1: Dimensions Elexant 3500i...
Page 3
Hazardous area approvals nVent RAYCHEM Elexant 3500i Class I, Division 2, Group A,B,C,D T4 Type 4X Class II, Division 2 Group F, G nVent.com/RAYCHEM...
Power cable gland and hubs for MI cold lead glands are not included. The kits can be used to connect one or two heating cables to power. The Elexant 3500i power terminals are rated for a single copper...
Elexant 3500i units comprise of either a temperature controller or a safety temperature limiter that can be set via programming. The controllers can be installed in any position on a stable structure by means of the 4 mounting holes. The Elexant 3500i unit can be mounted directly on a pipe up to a pipe temperature of 205°C (401°F).
Electrical installation Elexant 3500i units must be installed in accordance with local wiring regulations. Figure 3 shows the electrical connection diagram of the Elexant 3500i electronic thermostat. The optional second Pt100 temperature sensor for the control unit is omitted for clarity.
Page 8
W R R PE W R R PE Li Ni PE PE PT100 Temperature Sensor N/L2 Ground Figure 3: Electrical connection diagram Elexant 3500i nVent.com/RAYCHEM...
Page 9
Elexant 3500i to fail on, while setting the dipswitch down towards the empty circle will program the Elexant 3500i to fail off. By default, the Elexant 3500i is shipped with a fail off setting, meaning in the event of a sensor failure, the Elexant 3500i will not energize the heat trace circuit.
Need help?
Do you have a question about the Elexant 3500i and is the answer not in the manual?
Questions and answers