Summary of Contents for Beijer Electronics GT-449F
Page 1
User Manual GT-449F Analog Output Module 16 ch, 0 - 10 V, 16 bit resolution, cage clamp, 18 pt removable terminal Doc ID: 140783 2025-02-20...
Page 2
The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document.
10.1. Space Requirements ................17 10.2. Mount Module to DIN Rail ..............18 10.3. Mount Removable Terminal Block ............20 10.4. Connect Cables to Removable Terminal Block ..........21 10.5. Field Power and Data Pins ..............22 Beijer Electronics, Doc ID: 140783 2025-02...
About This Manual 1. About This Manual This manual contains information on the software and hardware features of the Beijer Electronics GT-449F Analog Output Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product. 1.1. Symbols Used in This Manual This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information.
Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product. The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc. • Expansion Module - Expansion module types: Digital IO, Analog IO, and Special modules. • Messaging - The system uses two types of messaging: Service messaging and IO messaging. Beijer Electronics, Doc ID: 140783 2025-02...
Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data. 2025-02 Beijer Electronics, Doc ID: 140783...
Voltage range: 18 - 30 VDC Power dissipation: 140 mA @ 24 VDC, Load (2K) Wiring Connector type: Up to AWG22 Module connector: HIF3BA-20D-2.54DSA Weight 63 g Module size 12 mm x 109 mm x 70 mm Beijer Electronics, Doc ID: 140783 2025-02...
±0.3 % full scale @ -40 °C, 60 ℃ Load resistance Min. 2 kΩ Diagnostic Field power off: LED blinking Conversion time 0.4 ms / all channels Calibration Not required Common type 2 common, field power 0 V is common (AGND) 2025-02 Beijer Electronics, Doc ID: 140783...
Analog output channel 9 Analog output channel 10 Analog output channel 11 Analog output channel 12 Analog output channel 13 Analog output channel 14 Analog output channel 15 Output channel common (AGND) Output channel common (AGND) Beijer Electronics, Doc ID: 140783 2025-02...
LED function / description LED color Status LED Green 6.1. LED Channel Status Status Indication G-bus status No connection Green Connection Field power error All channel repeat the green and off Field power is not connected 2025-02 Beijer Electronics, Doc ID: 140783...
Data Value / Voltage 7. Data Value / Voltage Voltage range: 0 - 10 VDC Voltage 0.0 V 2.5 V 5.0 V 10.0 V Data (Hex) H0000 H1FFF H3FFF H7FFF Beijer Electronics, Doc ID: 140783 2025-02...
Analog output Ch 13 high byte Byte 28 Analog output Ch 14 low byte Byte 29 Analog output Ch 14 high byte Byte 30 Analog output Ch 15 low byte Byte 31 Analog output Ch 15 high byte 2025-02 Beijer Electronics, Doc ID: 140783...
Page 15
Analog output Ch 7 Analog output Ch 8 Analog output Ch 9 Analog output Ch 10 Analog output Ch 11 Analog output Ch 12 Analog output Ch 13 Analog output Ch 14 Analog output Ch 15 Beijer Electronics, Doc ID: 140783 2025-02...
Fault action for channel 15 channel 14 channel 13 channel 12 00: Fault value / 01: Hold last state / 10: Low limit / 11: High limit Byte Fault value low byte Byte Fault value high byte 2025-02 Beijer Electronics, Doc ID: 140783...
Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion. CAUTION NOT following the space requirements may result in damaging the product. Beijer Electronics, Doc ID: 140783 2025-02...
• GT-5XXX • GT-7XXX GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module. Mount to DIN rail Dismount from DIN rail 2025-02 Beijer Electronics, Doc ID: 140783...
Page 19
10.2.2. Mount GN-9XXX Module To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions: Mount to DIN rail Dismount from DIN rail Beijer Electronics, Doc ID: 140783 2025-02...
Hardware Setup 10.3. Mount Removable Terminal Block To mount or dismount a removable terminal block (RTB), see the instructions below. Mount a removable terminal block Dismount a removable terminal block 2025-02 Beijer Electronics, Doc ID: 140783...
To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below. WARNING Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance. Connect cable Disconnect cable Beijer Electronics, Doc ID: 140783 2025-02...
Token output port of processor module Serial output Transmitter output port of processor module Serial input Receiver input port of processor module Reserved Reserved for bypass token Field GND Field ground Field VCC Field supply voltage (24 VDC) 2025-02 Beijer Electronics, Doc ID: 140783...
Need help?
Do you have a question about the GT-449F and is the answer not in the manual?
Questions and answers