TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Table of Contents 024-060 Model Nomenclature Electrical: Power Wiring Attentions, Cautions, and Warnings Electrical: Low Voltage Wiring General Information Blower Performance Data Minimum Installation Area Example Wiring Diagram Refrigerant System Servicing Unit and System Checkout Tranquility SA Dimensional Data Maintenance Installation...
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Model Nomenclature 024-060 PRODUCT NAME STANDARD S = R-454B Refrigerant S = Standard MODEL TYPE BLOWER MOTOR A = Tranquility (SA) Premier Air Handler V = Constant Volume (CV) EC FUTURE FUTURE N = Not Applicable N = Not Applicable...
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Attentions, Cautions, and Warnings 024-060 SAFETY WARNING All refrigerant discharged from this unit must be recovered WITHOUT Warnings, cautions, and notices appear EXCEPTION. Technicians must follow industry accepted guidelines and throughout this manual. Read these items carefully all local, state, and federal statutes for the recovery and disposal of refrigerants.
Page 5
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Attentions, Cautions, and Warnings 024-060 CAUTION DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life.
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: General Information 024-060 INSPECTION PRE-INSTALLATION Upon receipt of the equipment, carefully check the Installation, Operation, and Maintenance instructions shipment against the bill of lading. Make sure all units are provided with each unit. Horizontal equipment have been received.
Page 7
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: General Information 024-060 Work Procedure Checks to the Refrigeration Equipment Work shall be undertaken under a controlled procedure The following checks shall be applied to installations so as to minimize the risk of a flammable gas or vapor using FLAMMABLE REFRIGERANTS: being present while the work is being performed.
Page 8
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: General Information 024-060 REPAIR TO INTRINSICALLY SAFE COMPONENTS AIR HANDLER DESCRIPTION Intrinsically safe components must be replaced. ClimateMaster Tranquility® Premier Air Handlers are designed for use with Tranquility indoor/outdoor split CABLING units and are available for vertical upflow or downflow, and horizontal-left or horizontal-right airflow.
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Minimum Installation Area 024-060 MINIMUM INSTALLATION AREA Minimum area where the unit can be installed if it has a blower so that you do not need mechanical/natural ventilation. Minimum Installation Minimum area where unit is installed Charge Area ft Model...
Page 10
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Minimum Installation Area 024-060 When the openings for connected rooms or natural ventilation are required, the following conditions shall be applied: The area of any openings above 11.8 inches (300 mm) from the floor shall not be considered in determining compliance with Anv At least 50% of the required opening area Anv shall be below 7.8 inches (200 mm) from the floor.
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Refrigerant System Servicing 024-060 REFRIGERANT SYSTEM Charging Procedures Verify that air- and water-flow rates are at proper levels before servicing the refrigerant circuit. To maintain In addition to conventional charging procedures, the sealed-circuit integrity, do not install service gauges following requirements shall be followed: unless unit operation appears abnormal.
Page 12
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Refrigerant System Servicing 024-060 Leak-detection equipment shall be set at a Before attempting the procedure, ensure that: percentage of the lower flammability limit of the Mechanical-handling equipment is available, refrigerant and shall be calibrated to the refrigerant if required, for handling refrigerant cylinders employed, and the appropriate percentage of gas All personal protective equipment is available...
Page 13
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Refrigerant System Servicing 024-060 RECOVERY When removing refrigerant from a system, either for In addition, a set of calibrated weighing scales servicing or decommissioning, it is recommended shall be available and in good working order. good practice that all refrigerants are removed safely.
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Physical Data 024-060 Tranquility SA Physical Data Model Water Connection Size Liquid I.D. (in.) Suction I.D. (in.) Refrigerant Leak Detection System Number of Sensors Fan Motor - CV EC Filter Standard 1” Throwaway 16 x 20 20 x 20 20 x 24...
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Installation 024-060 The SA Air Handler(s) are designed for upflow, Isolate the plenum box and unit from the horizontal, and downflow applications. The coils foundation using a suitable isolating material. have a dry-nitrogen holding charge and are 4.
Page 17
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Installation 024-060 Horizontal Right Installation Horizontal Left Installation For horizontal installations where access to For horizontal installations where access to the factory-provided air filter is limited, it is the factory-provided air filter is limited it is recommended to remove the factory filter and use recommended to remove the factory filter and use a properly sized remote filter grille/box to maintain...
Page 18
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Actual area is 3.5313” w x 8.875”h Models: Installation Guides indicate .125” bleed all around 024-060 Figure 1: Mounting Installation Options Duct Connections Connect the supply- and return-air ducts to the unit with flame-retardant duct connectors. NOTES: No sheetmetal screws may be used to attach return ductwork on the side.
Page 19
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Actual area is 3.5313” w x 8.875”h Models: Installation Guides indicate .125” bleed all around 024-060 Figure 3: Air Handler Orientation CAUTION Discharge Return R-454B systems operate at higher pressures than R-22/ HFC-410A systems.
Page 20
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Installation 024-060 Installing the Indoor Coil and Lineset Air Coil Figure 4 shows line set and TXV bulb installation to Clean all newly manufactured coils before startup a typical indoor coil. Braze the copper line set to to ensure maximum performance.
Page 21
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Actual area is 3.5313” w x 8.875”h Installation 024-060 Guides indicate .125” bleed all around Figure 6: SP Brazing Instructions Ensure the unit is level or pitched slightly toward the primary drain connection so that water drains completely from the pan (see Figure 8).
Page 22
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Installation 024-060 Test the condensate drain pan and drain line after Connect the auxiliary drain line to a separate drain installation is complete. Pour enough water into line and terminate according to local codes (no trap drain pan to fill drain trap and line.
Page 23
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Installation 024-060 AXM Communicating Controls Low Air Temperature Sensor Installation The Tranquility Premier Air Handler is equipped SA Premier Air Handlers are shipped with LT2 (Low with a AXM Communicating Controls to allow Air Temperature) sensor installed in the air handler communication with the communicating and connected to the AXM.
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Electrical Data 024-060 Table 12: SA Standard Total Voltage Rated Voltage Model Motor Unit Circ Fuse/ Code Voltage Min/Max HACR SA024 208/230-1-60 187/252 4.20 4.20 SA036 208/230-1-60 187/252 5.90 5.90 SA048 208/230-1-60 187/252 5.90 5.90...
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Electrical: Power Wiring 024-060 POWER CONNECTION WARNING Electrical shock hazard - Lock unit disconnect switch in open position The line-voltage connection is made by connecting before servicing unit. Failure to follow this warning could result in the incoming line-voltage wires to the “L”...
Page 26
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Electrical: Power Wiring 024-060 WIRING INSTRUCTIONS FOR 115V CONVERSION FROM 230V Figure 11: Remove Harness Plug Disconnect all power to the unit. 2. Disconnect the transformer primary orange wire from power block T2 and insulate the open end of the wire.
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Electrical: Low-Voltage Wiring 024-060 THERMOSTAT INSTALLATION When a non-communicating thermostat is used to control the system, an AWC Thermostat must be Locate the thermostat on an interior wall in a larger installed to maintain proper system communications room away from supply duct drafts.
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Blower Performance Data 024-060 Table 13: SA Digital Standard Unit Aux/ Cooling Mode Dehumid Mode Heating Mode Fan Only Max ESP Model Motor Range Emerg (in. wg) Mode Stg 2 Stg 1 Stg 2 Stg 1 Stg 2...
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Example Wiring Diagram 024-060 w w w. c l i m a t e m a s t e r. c o m P a r t # : 9 7 B 0 1 74 n 0 1 | r e v i s e d : M a y 2 , 2 0 2 5 PA G E : 2 9...
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Unit and System Checkout 024-060 Drain Lines: Check drain lines and ensure all joints WARNING are tight. Electrical shock hazard - Lock unit disconnect switch in open position before servicing unit. Failure to follow this warning could result in Drain Pan: Ensure that the unit drain pan and ...
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Maintenance 024-060 MAINTENANCE Filters Air Coil Filters must be clean to obtain maximum Clean the air coil to obtain maximum performance. performance. Inspect filters every month under Check once a year under normal operating conditions normal operating conditions and replace when and, if dirty, brush or vacuum clean.
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Sample Warranties Models: Standard 024-060 PA G E : 3 2 P a r t # : 9 7 B 0 1 74 n 0 1 | r e v i s e d : M a y 2 , 2 0 2 5 w w w.
Page 33
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Sample Warranties Models: Optional 10-Year Labor Coverage 024-060 w w w. c l i m a t e m a s t e r. c o m P a r t # : 9 7 B 0 1 74 n 0 1 | r e v i s e d : M a y 2 , 2 0 2 5 PA G E : 3 3...
Page 34
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Notes 024-060 PA G E : 3 4 P a r t # : 9 7 B 0 1 74 n 0 1 | r e v i s e d : M a y 2 , 2 0 2 5 w w w.
Page 35
TranquiliTy® 30 (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Notes 024-060 w w w. c l i m a t e m a s t e r. c o m P a r t # : 9 7 B 0 1 74 n 0 1 | r e v i s e d : M a y 2 , 2 0 2 5 PA G E : 3 5...
TranquiliTy® (Sa) PrEMiEr air HanDlEr SEriES– iOM Models: Revision History 024-060 Date Section Description Updated factory charge values in the Line Set Diameters and Charge Information table 05/02/25 Installation Added graphics that detail brazing instructions for the Tranquility SJ and SP. Updated figure references Minimum Install Area Updated data and removed unnecessary tables...