1. Overview
Network gateway GE-24-Cloud is designed to connect the network
devices working with the Modbus protocol over RS485 interface to the
cloud service akYtec Cloud via Ethernet.
The detailed user guide is available for download at www.akytec.de.
2. Specifications
Table 1 Specifications
Parameter
Power supply
Power supply
24 (10...48) VDC
Power consumption, max.
Galvanic isolation
Network interface
Interface
Protocols
Modbus RTU, Modbus ASCII, akYtec*
Baud rate
1200...115200 bps
Cable length, max.
Cloud interface
Interface
Protocols
TCP, DNS, DHCP
Baud rate
10 Mbps, 100 Mbps
Cable length, max.
Configuration interface
Interface
USB 2.0 (Micro-USB);
Ethernet 10/100 Mbps
Mechanical
Dimensions
55 × 96 × 58 mm
IP code
Average service life
Weight
approx. 0.15 kg
NOTE
Only devices listed in the library can be connected via the
akYtec protocol.
GE-24-Cloud_3-EN-136835-1.2
© All rights reserved. Subject to technical changes and misprints.
3. Environmental conditions
The device is designed for natural convection cooling which should be
taken into account when choosing the installation site.
The following environmental conditions must be observed:
• clean, dry and controlled environment, low dust level;
• closed non-hazardous areas, free of corrosive or flammable gases.
Table 2 Environmental conditions
Condition
Ambient temperature
Relative humidity
Value
Altitude
EMC emission / immunity
Vibration / shock resistance
6 W
4. Dimensions
1770 V
RS485
1000 m
Еthernet
100 m
IP20
10 years
GE-24-Cloud
Network gateway
Permissible range
−40...+55 °C
10...95 % (non-condensing)
up to 2000 m above sea level
conforms to IEC 61131-2
Fig. 1 Dimensions
5. Indication and control
There are 4 LEDs on the front cover.
Table 3 LED indicators
LED
State
ON
Power is on
flashing
Data transfer over RS485
interface
flashing
Command transfer from
akYtec Cloud
OFF
No error
ON
Error (see Table 4)
Table 4 Error indication and remedy
LED
State
Description
Hardware /
ON
software error
Cannot establish
flashing (short
connection to
ON, long OFF)
cloud server
No internet
flashing (ON
access. DNS or
and OFF of the
DHCP server
same length)
failure if DHCP is
enabled
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Description
Remedy
Contact akYtec
service staff
Check the
network settings
of the device and
the Internet
access point.
Check the
integrity of the
Ethernet cable

Advertisement

loading
Need help?

Need help?

Do you have a question about the GE-24-Cloud and is the answer not in the manual?

Questions and answers

Summary of Contents for Akytec GE-24-Cloud

  • Page 1 Only devices listed in the library can be connected via the akYtec protocol. GE-24-Cloud_3-EN-136835-1.2 akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany © All rights reserved. Subject to technical changes and misprints. Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
  • Page 2 DIP switch positions are read in ascending order starting from 1. Fig. 4 Connection to RS485 interface GE-24-Cloud_3-EN-136835-1.2 akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany © All rights reserved. Subject to technical changes and misprints. Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...