Akytec MBC-24 User Manual

Modbus rtu-ascii-tcp gateway (rs485 / ethernet)

Advertisement

Quick Links

MBC-24
MBC-24 Modbus RTU-ASCII-TCP Gateway (RS485 / Ethernet)
User guide
MBC-24_3-EN-145737-1.1
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MBC-24 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MBC-24

  • Page 1 MBC-24 Modbus RTU-ASCII-TCP Gateway (RS485 / Ethernet) User guide MBC-24_3-EN-145737-1.1 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    Appendix A. Examples of conversion from Modbus RTU/ASCII to Modbus TCP protocols ........................31 Appendix B. Modbus register map ..................34 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3: Introduction

    Manual or in violation of the current regulations and technical standards. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4: Safety

    1 hour before powering on. The device should be mounted in a specialized cabinet access to which is limited to qualified personnel. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5: Overview

    ModbusRTU / ASCII via RS485 and Modbus TCP via Ethernet interfaces. Master and Slave modes are supported. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Specifications

    IP code IP20 Weight approx. 150 g Average service life 10 years 80000 hours Mean time between failures (MTBF) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7: Galvanic Isolation

    10…95 %( non-condensing) up to 2000 m ASL Altitude Vibration / shock resistance conforms to IEC 61131-2 EMC emission / immunity akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Startup

    7. Connect the gateway to a PC and configure it using akYtec Tool Pro (see Section 8.1). 8. Disconnect the gateway from the PC. 9. Power on. The gateway is ready for operation. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Design And Operation

    (to reset the gateway and restore factory settings) 2 — 4 DIP switches 3 — Micro-USB connector Fig. 5.2 Under the front cover akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Indication And Control

    120 Ω terminating resistor is connected Only for akYtec service staff. DIP switches 2, 3 and 4 must be turned off during normal operation. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11 5 Design and operation Description DIP switch akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Installation

    The gateway is equipped with plug-in terminal blocks which enable quick replacement of the device without disconnecting the existing wiring. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13 4. Plug the terminal blocks with existing wiring into mating connectors of the gateway installed. 5. Power on the gateway. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14: Connection

    “logical one” at the output. The pull-up resistors are built into the gateway and are enabled when the gateway is configured in akYtec Tool Pro (see Section 8.2.2). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Configuration

    – Click the Find button. The gateway with the address will be displayed in the right part of the window. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16: Connection Over Ethernet

    8.2 Configuration using akYtec Tool Pro 8.2.1 RS485 To configure the RS485 interface, open the RS485 port settings node in the parameter tree: akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17 Table 8.2 Supported parameter combinations Modbus RTU Modbus ASCII 8-N-1 8-N-1 8-N-2 8-N-2 8-O-1 8-O-1 8-O-2 8-O-2 8-E-1 8-E-1 8-E-2 8-E-2 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18 – Modbus ASCII doesn’t support combinations 7-N-1 and 7-N-2. Parameter Parity must be set to value О or Е. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19: Ethernet

    The gateway supports the following network topologies: – Daisy – Star. The gateway operation mode is configured depending on the network topology. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20 Fig. 8.6 Using the gateway with Master in the Ethernet network Fig. 8.7 Using the gateway with Master in Ethernet interface Fig. 8.8 Star topology akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21 Ethernet (Master) — RS485 (Slave) The Ethernet (Master) — RS485 (Slave) mode assumes that the Master device is in the Ethernet network. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22 RS485 (Master) — Ethernet (Slave) The RS485 (Master) — Ethernet (Slave) mode assumes that the Master device is in the RS485 network. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 23 RS485 (Master) - (Ethernet) Slave mode is 31. To add a new device, click the Add device button. To apply the settings, click the Save button. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 24 – If a packet matches a routing rule, the packet is forwarded according to the routing table. – The first record 27:0:1:0:0:S:P is a system record and cannot be changed. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 25 Table 8.10 Value of the Slave ID field of an outgoing packet Slave ID Value Device address (ID) (Hex) 0x00–0xFF Do not change the Slave ID of the incoming packet akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 26 – In the Gateway settings / Mode settings node, set the routing value to 10:0:G:40:0:S:N (10 is the MBC-24 Ethernet port in the server mode). Fig. 8.16 Routing settings akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 27: Firmware Update

    3. Select a firmware update file. 4. Wait for the file to upload in the gateway and firmware update to complete. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 28: Factory Settings Restoration

    The gateway settings and RS485 port settings will be reset to default factory settings. Routing settings and network settings will not be reset to defaults, with the exception of DHCP mode — OFF. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 29: Maintenance

    The device should be cleaned with a dry or slightly damp cloth only. No abrasives or solvent-containing cleaners may be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 30: Scope Of Delivery

    — Short guide 1 pc. NOTE The manufacturer reserves the right to make changes to the scope of delivery. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 31: Transportation And Storage

    Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH! akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 32: Appendix A. Examples Of Conversion From Modbus Rtu/ Ascii To Modbus Tcp Protocols

    Slave Subnet mask 255.255.0.0 The routing rule record has the format 40:0:10:0A0219D2:1F6:1:P and it is explained in the table: akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 33 Slave 2 IP address – 0A0219D2) Gateway 10.2.1.1 Address 9600 kbps Baud rate Subnet 255.255.0.0 – Data bits 8 bits akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 34 NOTE To convert the Modbus TCP protocol to the Modbus ASCII protocol, set the Protocol сode field to A. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 35: Appendix B. Modbus Register Map

    String 256 1312 0x0520 String 256 1328 0x0530 String 256 1344 0x0540 String 256 1360 0x0550 String 256 1376 0x0560 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 36 Unsigned New subnet mask 0x0016 New gateway IP Unsigned 0x0018 address DHCP 0x0020 Enum 3 NOTE * Unchangeable parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...