Switch Setup - Outputs, Ranges, Units/Response
Always follow the Auto-Zero procedure after changing settings.
Mounting
1. Attach the unit to its mounting surface with the four self-tapping #10x3/4" sheet metal screws through the holes
in the mounting feet. The preferred mounting orientation is with the pressure ports facing down to prevent
condensation from entering the pressure transducer. Do not mount to a vibrating surface as vibration may cause
issues with the accuracy of the sensing element. See page 3 for an actual size mounting template for the unit.
The two cover latch screws must be installed to achieve an IP66 rating.
2. After Auto-Zeroing, remove the deadhead tubing and push the system tubing onto the port nipple without
creating any kinks or holes.
If a hole must be cut into the plastic plugs in the ½" NPSM threaded ports of the BBox enclosure, it's
recommended to use a Clean-Cut Tool. Not using this tool could cause damage to the electronics of the sensor.
Specifications subject to change without notice.
1150 Roberts Boulevard, Kennesaw, Georgia 30144
770-429-3000 Fax 770-429-3001 | www.automatedlogic.com
High Range ZPM - Zone Pressure Sensor
Installation and Operation