Summary of Contents for MrCool Easy Pro EZPRO HP-WMAH-115D25-O Series
Page 1
Due to updates and constantly improving performance, the information and instructions within this manual are subject to change without notice. Version Date: April 22, 2025 Please visit www.mrcool.com/documentation to ensure you have the latest version of this manual.
8. For units with a wireless network function, the USB device access, replacement, and maintenance operations must be carried out by professional staff. 9. Refer to details further in this manual regarding installing the unit to its support. mrcool.com...
Page 4
Call your local dealer, or MRCOOL® tech support at (270) 366-0457, for further assistance. 2. If the air conditioner is used together with burners or other heating devices, thoroughly ventilate the room in order to avoid an oxygen deficiency.
Page 5
3. Service, maintenance, and repair of this unit must be performed by a certified technician. 4. Product un-installation and recycling must be performed by a certified technician. 5. When checking the unit for leaks, maintain proper record-keeping of all checks. mrcool.com...
Page 6
22. Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. mrcool.com...
Page 7
The following procedure should be adhered to: • safely remove refrigerant following local and national regulations; • evacuate; • purge the circuit with inert gas; • evacuate; • continuously flush or purge with inert gas when using flame to open circuit; • open the circuit mrcool.com...
Page 8
Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant. The label should be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. mrcool.com...
Page 9
This symbol shows that the operation manual should be read carefully. CAUTION This symbol shows that a service personnel should be handling this equipment with reference to the installation manual. CAUTION This symbol shows that information is available such as the operating manual or CAUTION installation manual. mrcool.com...
Page 10
Anvmin shall not be less than the following: • Height of Outlet/m Mc/kg Mmax/kg Anvmin/m 2.685 0.045 2.941 0.042 3.177 0.038 3.396 0.035 3.602 0.031 3.797 0.028 3.983 0.024 4.160 0.020 4.330 0.016 4.493 0.013 4.651 0.009 4.803 0.005 4.951 0.001 mrcool.com...
Oil traps in the rising gas pipe can prevent this. • An oil trap should be installed every 20ft (6m) of vertical suction line. • An oil trap should be installed every 32.8ft (10m) of vertical suction line. mrcool.com...
SYSTEM OVERVIEW 2.3 Air Velocity and Temperature Distributions EZPRO-09-HP-WMAH-115D-O: Cooling (Indoor: 80.6°F /27°C Outdoor: 95°F /35°C) Discharge angle 58° Airflow Velocity Distributions Temperature Distributions mrcool.com...
ODU Model ODU Wiring Diagram EZPRO-09-HP-WMAH-115D-O EZPRO-09-HP-C-115D-O 16022000040773 EZPRO-12-HP-WMAH-115D-O 16022000040253 EZPRO-12-HP-C-115D-O EZPRO-18-HP-WMAH-230D-O EZPRO-18-HP-C-230D-O 16022000040610 EZPRO-24-HP-WMAH-230D-O 16022000040232 EZPRO-24-HP-C-230D-O 16022000040790 Outdoor Unit Printed Circuit Board Diagram: Outdoor Unit ODU Model ODU Printed Circuit Board EZPRO-09-HP-C-115D-O 17122000062141 EZPRO-12-HP-C-115D-O EZPRO-18-HP-C-230D-O 17122000057661 EZPRO-24-HP-C-230D-O 17122000048064 mrcool.com...
Page 23
SYSTEM OVERVIEW Indoor unit wiring diagram: 16022000040253 mrcool.com...
Page 24
SYSTEM OVERVIEW Outdoor unit wiring diagram: 16022000040232 mrcool.com...
Page 25
SYSTEM OVERVIEW Outdoor unit wiring diagram: 16022000040773 mrcool.com...
Page 26
SYSTEM OVERVIEW Outdoor unit wiring diagram: 16022000040610 mrcool.com...
Page 27
SYSTEM OVERVIEW Outdoor unit wiring diagram: 16022000040790 mrcool.com...
Page 28
SYSTEM OVERVIEW Outdoor unit printed circuit board diagram: 17122000062141 mrcool.com...
Page 29
L_in: connects to L-line (115VAC input) CN1A N_in: connects to N-line (115VAC input) Earth Connects to compressor .0VAC (standby), 0-310VAC CN50 (running) CN4_2 REACTOR Connects to reactor, 115VAC when is ON CN4_3 Note: This section is for reference only. Please take practicality as standard. mrcool.com...
Page 30
SYSTEM OVERVIEW Outdoor unit printed circuit board diagram: 17122000057661 mrcool.com...
Page 31
CN16 S: connects to indoor unit communication L_in: connects to L-line (230VAC input) CN1A N_in: connects to N-line (230VAC input) Earth CN50 Connects to compressor (Output: 0-310VAC) Note: This section is for reference only. Please take practicality as standard. mrcool.com...
Page 32
SYSTEM OVERVIEW Outdoor unit printed circuit board diagram: 17122000048064 & 17122000048066 mrcool.com...
Page 33
Used for testing FAN_IPM IPM501 IPM for DC fan COMP_IPM IPM1 IPM for compressor CN27 CN28 Connects to compressor (Output: 0~310VAC) CN29 EE_PORT CN505 EEPROM programmer port Note: This section is for reference only. Please take practicality as standard. mrcool.com...
Preheating is automatically activated when T4 sensor is lower than setting temperature. Sensor redundancy and automatic shutoff • If one temperature sensor malfunctions, the air conditioner continues operation and displays the corresponding error code, allowing for emergency use. • When more than one temperature sensor is malfunctioning, the air conditioner ceases operation. mrcool.com...
The indoor fan speed can be set to 1%-100%, or auto. • The louver operations are identical to those in cooling mode. • Auto fan: In fan-only mode, AC operates the same as auto fan in cooling mode with the temperature set at 75°F (24°C). (Tsc=75°F (24°C)). mrcool.com...
For AC Fan Motor Units: a configured value, the compressor ceases operation. Evaporator Temperature Protection: • Off: Compressor stops. • Decrease: Decreases the running frequency to lower level per 1 minute. • Hold: Keep the current frequency. • Resume: No limitation for frequency. mrcool.com...
Page 37
T1 and indoor unit coil temperature T2. Outdoor Fan Control: • The outdoor unit will be run at different fan speeds according to T4 and compressor running frequency. • For different outdoor units, the fan speeds are different. mrcool.com...
• In condition 1~5 if any of the following heating, auto-drying, or fan-only mode on conditions are satisfied the defrost cycle ends the basis of T1, Ts, T4 and relative humidity. and the machine switches to normal heating mode. mrcool.com...
• Timer on • Timer off • The timer setting is available in this mode. • Sleep mode • Follow me • Changes in: • Mode • Fan Speed • Setting temperature mrcool.com...
Silence Press "Silence" on the remote control to enable the SILENCE function. While this function is active, the indoor unit will run at a faint breeze (1% fan speed), which reduces noise to the lowest possible level. mrcool.com...
11. Use a torque wrench to tighten the caps to a scale and record the starting weight. torque spec of 13.28ft. lbs (18Nm). 7. Fully open the Handle Lo manifold valve, 12. Check for any leaks. 2-way and 3-way valves. mrcool.com...
After maintenance is completed, insert the female end back into the port. Note: This picture is for reference only. Actual appearance may vary. LED Flash Frequency: mrcool.com...
Test the unit using the remote control. If the unit does undefined by the service manual. Ensure that this code is not respond to the remote, the indoor PCB requires not a temperature reading. replacement. If the unit responds, the display board requires replacement. mrcool.com...
Page 44
Code of Outdoor Error Code of Indoor Unit Unit does not start Remote Control does not work Indoor display shows nothing No Cooling or Heating at all Less Cooling or Heating Unit Starts but Stops Shortly High noise High Vibration mrcool.com...
Page 45
Compressor Current Outdoor AC Voltage Indoor Capacity Test Reserve Outdoor Fan Speed EXV Opening Steps Indoor Fan Speed Indoor Humidity Adjusted Setting Temperature Reserve Reserve Reserve GA algorithm Frequency Approval From Manufacture □ Approved □ More Proof Needed □ Rejected mrcool.com...
Temperature can be memorized when the remote control is power on and TP Temperature power lost; and press "ON/OFF" for 2s to exit. When the remote control does not burn any parameters, the max. set temperature will not be memorized. (Set within 1 minute after power is on) mrcool.com...
Page 47
Indoor Target Frequency press the UP/DOWN key to select the cooling frequency threshold, press "OK" to confirm; and press "ON/OFF" for 2s to exit. (Range: 40, 41,... 83, 84,--, "--" cancels the settings) (set within 1 minute after power is on) mrcool.com...
Page 48
When the setting is successful, "CS" will be displayed; When the setting fails, "CF" will be displayed. Exit of Engineer Mode: 1. In engineer mode, press the key combination of "ON/OFF + Air Speed" for 2s. 2. The engineer mode will be exited if there are no valid key operations for continuous 60s. mrcool.com...
Page 49
ODU main control board DC bus high voltage protection PC 12 ODU main control board DC bus low voltage protection/341 MCE error PC 02 Compressor top (or IPM) temp. Protection PC 40 Communication error between outdoor main chip and compressor driven chip mrcool.com...
Page 50
Voltage freq. limited LC 03 Current freq. limited LC 06 IPM module temp. freq. limited LC 30 High pressure freq. limited LC 31 Low pressure freq. limited LH 07 Remote control frequency limitation in effect IDUs mode conflict (multi-zone) mrcool.com...
Compressor short-cycles due to overload TS17-TS18 High suction pressure TS17-TS18 Low discharge pressure TS17-TS18 High suction pressure TS17-TS18 Low suction pressure TS17-TS18 Unit runs continuously but insufficient cooling TS17-TS18 Too cool TS17-TS18 Compressor is noisy TS17-TS18 Horizontal louver cannot revolve TS17-TS18 mrcool.com...
Page 52
Unit runs but shortly √ √ √ stops The unit startup and √ √ √ stops frequently Unit runs continuously but √ √ √ √ √ insufficient cooling/ heating Cool cannot change to heat Unit is noisy Test method/ remedy mrcool.com...
Page 53
Unit is on but the air is not cold/hot Unit runs but shortly stops The unit startup and √ stops frequently Unit runs continuously but √ √ √ insufficient cooling/ heating Cool cannot change to heat Unit is noisy √ √ Test method/ remedy mrcool.com...
Page 54
Condenser fan will not start Unit runs but √ √ √ √ √ √ shortly stops Compressor short-cycles √ √ √ due to overload High discharge √ √ √ √ √ √ pressure Low discharge √ √ pressure Test method/ remedy mrcool.com...
Page 55
√ √ √ √ √ √ √ √ √ √ √ insufficient cooling Too Cool X X X Compressor is X X X √ √ √ √ √ noisy Horizontal louver X X X cannot revolve Test method/ remedy mrcool.com...
Page 56
Air handler fan will √ √ √ √ not start Condenser fan will √ √ √ √ √ not start Unit runs but √ √ shortly stops Compressor short-cycles due to √ √ overload High discharge pressure Low discharge pressure Test method/ remedy mrcool.com...
Page 57
TROUBLESHOOTING 2. Field Electrical Circuit Maintenance Possible causes of trouble High suction pressure Low suction pressure Unit runs continuously but insufficient cooling Too cool √ √ Compressor is noisy Horizontal louver √ √ √ can not revolve Test method/ remedy mrcool.com...
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a puled voltage. The location of the EEPROM chip on the indoor PCB is shown in the following image: Note: These pictures are for reference, actual appearance may vary. mrcool.com...
Page 60
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a puled voltage. The location of the EEPROM chip on the outdoor PCB is shown in the following image: Note: This picture is for reference only, actual appearance may vary. mrcool.com...
Page 61
TROUBLESHOOTING TS02-S-INV: IDU & ODU communication error diagnosis and solution Description: Indoor unit can not communicate with outdoor unit Recommended parts to prepare: • Indoor PCB • Outdoor PCB • Short-circuited component Troubleshooting and repair: mrcool.com...
Page 62
Use a multimeter to test the resistance of the reactor which does not connect with the capacitor. • The normal value should be around zero ohms. Otherwise the reactor has a malfunction. Note: The picture and the value are for reference only, actual appearance and values may vary. mrcool.com...
Page 63
Recommended parts to prepare: • Connection wires • Indoor main PCB Troubleshooting and repair: Note: Zero crossing detection error is only valid for the unit with AC fan motor, for other models, this error is invalid. mrcool.com...
Page 64
Description: When the indoor fan speed keeps too low or too high for a period of time the LED displays the failure code and the AC turns off. Recommended parts to prepare: • Connection wires • Fan assembly • Fan motor • Indoor main PCB Troubleshooting and repair: mrcool.com...
Page 65
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V (208~240V power supply) or 50V (115V power supply) the PCB has problems and will need to be replaced. mrcool.com...
Page 66
Description: When the outdoor fan speed keeps too low or too high for a certain time, the LED displays the failure code and the system turns off. Recommended parts to prepare: • Connection wires • Fan assembly • Fan motor • Outdoor main PCB Troubleshooting and repair: mrcool.com...
Page 67
If the value of the voltage is not in the range showing in below table the PCB has a problem and needs to be replaced. Color Signal Voltage Vs/Vm 192V~380V Black White 13.5-16.5V Yellow 0~6.5V Blue 13.5-16.5V mrcool.com...
Page 68
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure code. Recommended parts to prepare: • Connection wires • Sensors • Indoor main PCB Troubleshooting and repair: Note: The picture and the value are for reference only, actual appearance and values may vary. mrcool.com...
Page 69
• Outdoor main PCB Troubleshooting and repair: Note: For certain models the outdoor unit will use a combination sensor, T3, T4 and TP are the same sensor. This picture and value are for reference only, actual appearance and value may vary. mrcool.com...
Page 70
Description: Judging the abnormality of the refrigeration system according to the number of compressor as well as the changes in the operating parameters caused by excessive exhaust temperature. Recommended parts to prepare: • Indoor PCB • Additional refrigerant Troubleshooting and repair: mrcool.com...
Page 71
TROUBLESHOOTING TS07: Indoor PCB/Display board communication error diagnosis and solution Description: Indoor PCB does not receive feedback from the display board. Recommended parts to prepare: • Communication wire • Indoor PCB • Display board Troubleshooting and repair: mrcool.com...
Page 72
Description: The indoor unit receives a fault signal for 10s or the indoor unit does not receive feedback from the refrigerant sensor for 150s. Recommended parts to prepare: • Connection wires • Sensors • Indoor main PCB Troubleshooting and repair: mrcool.com...
Page 73
APP, and so on to eliminate the alarm) and any other non- refrigerant leakage fault the indoor unit will only display ECC1 and the buzzer will not make a sound. Recommended parts to prepare: • Additional refrigerant Troubleshooting and repair: mrcool.com...
Page 74
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal the LED displays a fault code and the system turns off. Recommended parts to prepare: • Connection wires • IPM module board • Outdoor fan assembly • Compressor • Outdoor PCB Troubleshooting and repair: mrcool.com...
Page 75
TS10-S: ODU voltage protection diagnosis and solution Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit. Recommended parts to prepare: • Power supply wires • IPM module board • PCM • Reactor Troubleshooting and repair: mrcool.com...
Page 76
Description: If the temperature of the IPM module is higher than a certain value the LED displays a fault code. Recommended parts to prepare: • Connection wires • Outdoor PCB • IPM module board • High pressure protector • System blockages Troubleshooting and repair: mrcool.com...
Page 77
Description: An abnormal inverter compressor drive is detected by a special detection circuit including communication signal detection, voltage detection, compressor rotation speed signal detection, etc. Recommended parts to prepare: • Connection wires • Outdoor PCB • IPM module board • Outdoor fan assembly • Compressor Troubleshooting and repair: mrcool.com...
638 PSI.(4.4MPa)). Or the outdoor pressure switch cut off the system due to low pressure (if the pressure is lower than 18.85 PSI.(0.13MPa) the LED will display a fault code. Recommended parts to prepare: • Connection wires • Outdoor PCB • Refrigerant • Pressure switch • Outdoor fan Troubleshooting and repair: mrcool.com...
Page 80
When the compressor is on and the outdoor ambient temperature (T4) is lower than -40°F (-40°C) for 10s the system will stop and display the fault code. When the outdoor ambient temperature (T4) is no lower than -25.6°F (-32°C) for 10s, the unit will exit protection. mrcool.com...
1. Disconnect the temperature sensor from the PCB. 2. Measure the resistance value of the sensor using a multi-meter. 3. Check corresponding temperature sensor resistance value table. Note: The picture and the value are for reference only, actual condition and specific values may vary. mrcool.com...
Page 83
(at 68°F (20°C)) (at 68°F (20°C) Red-Black Resistance Value KSK75D33UEZD3 DTN210D54UEZ3 Blue-Red 2.14±5%Ω 2.53±5%Ω Blue-Black (at 68°F (20°C)) (at 68°F (20°C) Red-Black Note: The picture and the value are for reference only, actual condition and specific values may vary. mrcool.com...
∞ ∞ (Several M±5%Ω) (Several M±5%Ω) Or test the conductivity of IPM with diode mode: Needle-type Tester Needle-Type Tester Normal Value Normal Value Black Black Open-Circuit 0.3-0.5V Needle-type Tester Needle-Type Tester Normal Value Normal Value Black Black 0.3-0.5V Open-Circuit mrcool.com...
Page 85
1. Power on and use a digital tester to measure the voltage. When the unit operates in cooling it is 0V, when the unit operates in heating it is about 230VAC. If the value of the voltage is not in range the PCB has problems and needs to be replaced. mrcool.com...
Page 86
TROUBLESHOOTING 2. Turn the power off and use a digital tester to measure the resistance. The value should be 1.8~2.5 K±5%Ω. mrcool.com...
Page 87
1. Disconnect the connector from the outdoor PCB. 2. Measure the resistance value of each winding using a multi-meter. 3. Check the resistance value of each winding in the following table. Color of Lead Winding Normal Value Red-Blue Red-Yellow About 50Ω Brown-Orange Brown-White mrcool.com...
Page 92
Advantage Series The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.
Need help?
Do you have a question about the Easy Pro EZPRO HP-WMAH-115D25-O Series and is the answer not in the manual?
Questions and answers