TBB power Raython R Series User Manual

All-in-one standalone solar power system

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Raython R Series and is the answer not in the manual?

Questions and answers

Summary of Contents for TBB power Raython R Series

  • Page 2 Raython R System...
  • Page 3 Raython R System About TBB Renewable One-stop Power Solution Provider Found in 2007 with location in Xiamen city, TBB Renewable is specialized in providing off-grid, mini-grid and ESS solutions. With 16 years experience, TBB Renewable has become a global solution provider in the renewable market serving clients across more than 50 countries, committed to providing one-stop power solution, including power generation, power conversion, storage, system monitoring &...
  • Page 4 This chapter contains important safety and operation instructions. Read and keep this User Guide well for later reference. The RAYTHON R series needs to be installed by professionals and please pay attention to the following points prior to installation: 1> Please check the DC input voltage or battery voltage is the same to the nominal input voltage of this inverter.
  • Page 5: Table Of Contents

    Raython R System Content 1.0 General Safety Instruction ......................1 1.1 Safety Instruction........................ 1 1.2 Symbols Used in the Documentation .................. 1 1.3 General Precaution ......................1 1.4 Precaution Regarding Battery Operation ................2 2.0 System Description ........................3 2.1 Equipment layout........................ 4 2.2 Raython Cabinet Dimensions .....................
  • Page 6: General Safety Instruction

    Raython R System 1.0 General Safety Instruction 1.1 Safety Instruction As dangerous voltages and high temperature exist within the RAYTHON, only qualified and authorized maintenance personnel are permitted to open and repair it. This manual contains information concerning the installation and operation of the RAYTHON. All relevant parts of the manual should be read prior to commencing the installation.
  • Page 7: Precaution Regarding Battery Operation

    Raython R System 1.4 Precaution Regarding Battery Operation Only authorized and trained person who should be familiar to battery installation, preparation, charging, and maintenance is permitted to the operation for battery SHOCK HAZARD- DO NOT touch the uninsulated battery connectors or terminals. Be sure to discharge static electricity of tools and technicians by touching a grounded surface, but away from the cells and flame arresters.
  • Page 8: System Description

    Raython R System 2.0 System Description The Raython R system is an all-in-one standalone solar power system. It is an ideal solution designed for holiday houses or single-family houses that have no access to the grid power and the users often use generators as their power supply. Featuring low pollution and low fuel consumption, it is also a perfect solution for people who pursue a more sustainable lifestyle.
  • Page 9: Equipment Layout

    Raython R System 2.1 Equipment layout Raython R Functional unit Functional unit External antenna Anti-dust mesh cover Cabinet front door lock Battery compartment door Cabinet front door Caster...
  • Page 10 Raython R System Raython R No. Functional unit Functional unit Lithium battery Cooling fan Cooling fan temperature control switch Battery compartment door lock Solar hybrid inverter Internal battery circuit breaker External battery circuit breaker Ground copper bar (optional) Air inlet louvers Structural parts for cabinet fixing E4 LCD Monitor AC circuit breaker...
  • Page 11: Raython Cabinet Dimensions

    Raython R System 2.2 Raython Cabinet Dimensions Raython R3...
  • Page 12 Raython R System Raython R5&8...
  • Page 13: Riio Sun Ii Solar Hybrid Inverter

    Raython R System 2.3 RiiO Sun II Solar Hybrid Inverter RiiO Sun II series all-in-one solar inverter (hereinafter referred to as RiiO Sun II) is a low-frequency transformer-based inverter integrated with multiple functions like battery inverter, AC charger, and MPPT charger, suitable for backup power and off-grid applications. For more information about RiiO Sun II , please refer to its manual.
  • Page 14: Es100&Es100Ⅱ Ess Unit

    Raython R System 2.5 ES100&ES100Ⅱ ESS unit ES100 &ES100 Ⅱ is the latest 48V 105Ah lithium battery module provided by TBB POWER, designed for backup power system, solar grid system, and residential, industrial & commercial energy storage systems, with good compatibility, high energy density , fashionable design and safe long cycling life.
  • Page 15: Installation

    Raython R System 4.0 Installation Prior to Installation  Read the manual carefully and confirm the voltage and current input requirements of the load(s) are compatible with the unit’s output.  Also see the line voltage and current is compatible with the unit’s input requirements. ...
  • Page 16: Requirements Of Installation Angle

    Raython R System 4.3 Requirements of installation angle Equipment should be installed on a flat surface.  Do not place the unit in an inclined position.  Do not store the unit on its side or up-side down to avoid the damage of the unit.
  • Page 17: Requirements Of Installation Spacing

    Raython R System 4.4 Requirements of installation spacing Following minimum clearance are requested for the installation. Direction Minimum Clearance Front Left Side 0.3m Right Side 0.3m distance between cabinets 1m~2.5m 4.5 Fix the Cabinet  Rotate the four casters of the Raython cabinet counterclockwise so that the bottom plate of the casters will be overhanging.
  • Page 18: Wiring Recommendation

    Raython R System  Push the Raython cabinet to align the slot on the fixed bracket with the pre-buried screw.  Rotate the four casters of the Raython cabinet clockwise, so that the bottom plate of the casters falls to the ground (Rotating the nut A clockwise as shown at the right picture with a spanner or other proper tool) ...
  • Page 19: Connection Terminal Description

    Raython R System 4.7 Connection Terminal Description Item Name Description Label Comments Upper computer RS485 communication Normally Open Connect to generator start Relay1 control port Common Line AC IN Connect to the grid AC input Protecting Earthing Neural Line General load without being AC OUT 1 Protecting Earthing protected by installed MCB...
  • Page 20: Wiring Instruction

    Raython R System 4.8 Wiring Instruction All of the cables should be inserted into the cabinet through the holes at the bottom of the cabinet as below picture shows. Cut off the power before installation for safety. Please make sure the inverter is switched off and DC MCB is turn off at front panel before installation.
  • Page 21: Connecting Ac Grid Cable

    Raython R System 4.8.2 Connecting AC Grid Cable For safety, please turn off the Main Input MCB before the installation Using correct cable gauge (refer to chapter 4.6), please connect the grid to the terminal labeled “AC IN”. Make sure the connection is correct and tightly screwed. 4.8.3 Connecting the Loads Do not connect the output of this equipment to the same line as other AC sources such as the 230V external mains or a generator.
  • Page 22: Connecting Pv In Cable

    Raython R System 4.8.4 Connecting PV in Cable For safety, please turn off the PV Input MCB before the installation. Using correct cable gauge (refer to chapter 4.6), please connect the PV to the terminal labeled “PV IN”. Ensure that the positive and negative poles are not reversed. Make sure the connection is correct and tightly screwed.
  • Page 23: Operation

    Raython R System 5.0 Operation 5.1 Double Checking  The system is installed correctly and steady.  Make sure the ground wire is properly connected firmly and reliably.  Make sure the cables are properly connected firmly and reliably.  The DC breaker AC breaker and PV switch is OFF before switching on the inverter ...
  • Page 24: Led Indicator

    Raython R System Invert Charge Fault LED Indicator DOWN ENTER Operation Button RiiO Sun II interface 5.4 Power OFF  Step 1: When the inverter is in the inverting mode or charging mode, press the On/Off button for 2 seconds to turn off the inverter into the standby mode. ...
  • Page 25: Configuration

    Raython R System 6.0 Configuration Standard Setting Setting Value Rated AC Voltage 230VAC Rated AC frequency 50Hz AC in source Selection Generator Input frequency range 45-55Hz Input voltage range 175-265VAC AC Wave Harmonic Adaption Weak AC Source Battery Type TBB Super-L SOC Low Protect SOC Low Warning SOC charge Enough...
  • Page 26: Specification

    Raython R System 7.0 Specification Model Raython R3 Raython R5 Raython R8 AC input Generator compatible AC input voltage range (VAC) 175~265 AC input Frequency range (Hz) 45~65 AC input Current (transfer switch) (A) Inverter Product Topology Transformer based Nominal battery voltage (VDC) Input voltage range (VDC) 42~68 AC output voltage (VAC)
  • Page 27 Raython R System Raython R3 Raython R5 Raython R8 Model Battery Battery Type LiFePO4 Li-ion battery 5.04-10.08kWh 10.08-20.16kWh 10.08-20.16kWh Nominal Energy Capacity General data General purpose com. Port Wi-Fi with E4 LCD monitor Inverter: -20˚C to 65˚C Operating temperature range Battery: discharge -20˚C to 55˚C, charge 0-40℃...
  • Page 28: Appendix 1: Battery Installation

    Raython R System Appendix 1: Battery Installation The battery compartment of Raython R System is designed according to two types of lithium batteries: ES100 and ES100Ⅱ, based on their respective dimensions. Raython R3 can accommodate a maximum of two ES100 or ES100II batteries, while Raython R 5 &8 can accommodate a maximum of four ES100 or ES100II batteries.
  • Page 29: Appendix 2: Introduction To Cabinet Parallel Connection

    Raython R System Appendix 2: Introduction to cabinet parallel connection Raython series support parallel connection of up to 3 cabinets of the same type in three-phase or single-phase parallel to expand the system capacity. Before conducting the parallel connection, it is necessary to purchase the accessories listed on the following table based on the actual need.
  • Page 30: Brief Intro To Ac Distribution Box

    Raython R System 1. Brief intro to AC distribution box 1.1 PDU-M2-3T is a customized AC distribution box for Raython Model 1&2 parallel and three-phase connection use, featuring wall mount, IP54, 400V/63A, and output surge protection level II. PDU-M2-3T External View PDU-M2-3T External Size Drawing 1.2 In the Raython parallel system, PDU-M2-3T AC distribution box is fixed on the right side of the host cabinet of Raython Model 1&2 with 4 M6*12 screws.
  • Page 31: Overview Of The Dc Parallel Kit

    Raython R System 1.5 In the Raython parallel system, PDU-M2-3S AC distribution box is fixed on the right side of the host cabinet of Raython Model 1&2 with 4 M6*12 screws. 1.6 Please refer to the information package delivered with the distribution box or the electronic files provided by the manufacturer after-sale division for the detailed electrical schematic diagram of PDU-M2-3S AC distribution box.
  • Page 32 Raython R System Note: The items might not conform to the ones listed above with regard to the actual need of cabinet parallel connection and will subject to change without prior notice. 2.3 KIT-M2-2P Raython Model 2 DC parallel kit for two cabinets parallel connection: Quantity Item DC MCB, NDB6Z-125C125/4, 4P, Type C...
  • Page 33: Parallel Connection

    Raython R System 3. Parallel connection 3.1 Partial layout diagram of the electrical components and connecting terminals location in the Raython R5 for cabinet parallel connection:...
  • Page 34 Raython R System 3.2. Brief intro to the connection of power cable for Raython R5orR8 cabinets parallel connection: 3.2.1 Diagram on AC & DC power cables wiring connection for two Raython R5orR8 parallel connection in single-phase.  The electrical components, installation accessories, and DC distribution cables for the parallel connection of 1#RAYTHON and 2#RAYTHON are enclosed in the KIT-M1-2P installation package.
  • Page 35 Raython R System 3.2.2 Diagram on AC & DC power cables wiring connection for three Raython R5orR8 parallel connection in single-phase.  The electrical components, installation accessories, and AC power cables for the parallel connection of 1#RAYTHON, 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M1-3P installation package.
  • Page 36 Raython R System 3.2.3 Diagram on AC & DC power cables wiring connection for two Raython R5orR8 parallel connection in single-phase  The electrical components, installation accessories, and AC power cables for the parallel connection of 1#RAYTHON, 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M1-3P installation package.
  • Page 37 Raython R System 3.3 Brief intro to the connection of communication cable for Raython R5orR8 cabinet parallel connection: 3.3.1 Diagram on two Raython R5orR8 parallel connection in single-phase.  The communication cables for the parallel connection of 1#RAYTHON and 2# RAYTHON are enclosed in the KIT-M1-2P installation package.
  • Page 38 Raython R System 3.3.2 Diagram on three Raython R8orR5 parallel connection in single-phase or three-phase.  The communication cables for the parallel connection of 1# RAYTHON, 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M1-3P installation package.  Please refer to information package delivered with the distribution box, the electronic files provided by the manufacturer after-sale division, or the relevant websites for the detailed communication diagram for cabinets in parallel connection.
  • Page 39 Raython R System 3.4 Partial layout diagram of the electrical components and connecting terminals location in the Raython R3 for cabinet parallel connection: 3.5 Brief intro to the connection of power cable for Raython R3 cabinets parallel connection: 3.5.1 Diagram on AC & DC power cables wiring connection for two Raython R3 parallel connection in single-phase...
  • Page 40 Raython R System  The electrical components, installation accessories, and DC distribution cables for the parallel connection of 1#RAYTHON and 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M2-2P installation package.  The AC cables connecting the input/output terminals of PDU-M2-3S AC distribution box to the AC IN and AC OUT ports of two Raython R3 cabinets connected in parallel will be provided by distributors or prepared by owners.
  • Page 41 Raython R System 3.5.3 Diagram on AC & DC power cables wiring connection for three Raython R3 parallel connection in three-phase.  The electrical components, installation accessories, and DC distribution cables for the parallel connection of 1# RAYTHON, 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M2-3P installation package.
  • Page 42 Raython R System 3.6 Brief intro to the connection of communication cable for Raython R3 cabinet parallel connection: 3.6.1 Diagram on two Raython R3parallel connection in single-phase.  The communication cables for the parallel connection of 1# RAYTHON and 2# RAYTHON are enclosed in the KIT-M2-2P installation package ...
  • Page 43: Description Of Precautions

    Raython R System 3.6.2 Diagram on three Raython R3 parallel connection in single-phase or three-phase.  The communication cables for the parallel connection of 1# RAYTHON, 2# RAYTHON, and 3# RAYTHON are enclosed in the KIT-M2-3P installation package.  Please refer to information package delivered with the distribution box, the electronic files provided by the manufacturer after-sale division, or the relevant websites for the detailed communication diagram for cabinets in parallel connection.
  • Page 44: Parameters Setting For Parallel Connection

    Raython R System  The self-made cables for cabinet parallel connection should be from the same batch with the same diameter and length and the same specification of copper jointing sleeve for cable crimping, in order to make cables with consistent internal resistance. The red cable should be used for the positive pole of the battery pack, while the black one for the negative pole.
  • Page 45 Raython R System 5.2 Parameters setting for parallel connection of three Raython Model 1&2 cabinets in three-phase:  E4 parameters setting is listed as follow: Description Settings You should set the actual number of Model 1&2 that are connected to the system Parallel number Setting method: Advanced Setting →...
  • Page 46 Raython R System  Solar Mate parameters setting is listed as follow: Settings Description When setting the address for Solar Mate, if there are 3 Solar Mate connecting SYS_ Module_ to the host inverter, address 1,2, and 3 should be set for these three Solar Mate Address respectively.
  • Page 47 Raython R System...