Residential central heat recovery ventilator (28 pages)
Summary of Contents for SummerAire NUWAVE Series
Page 1
® NUWAVE SERIES Residential Central Heat Recovery Ventilator Product Specifications Installation and User Manual NuWave Series Models NW85T - NW125T APPLICATION WARNING It is always important to assess how the operation of any Heat Recovery Ventilator (HRV) may interact with vented combustion equipment (i.e.
HRV LED function indicators Note: a flashing LED is an indication that an external timer or dehumidistat has initiated a high speed ventilation sequence. OpERATiNg FEATuREs Any of the following operating functions may be selected at the push button located at the left hand side of the HRV immediately below the illuminated leds, or at the optional Shepherd Digital control if installed.
During this cycle ventilation is ON for a period of 20 minutes in low speed. However, should an optional timer be activated, ventilation will turn on to high speed until the timer expires or is turned off. This intermittent cycle of 20 minutes ventilation ON followed by 40 minutes of ventilation OFF repeats automatically until another selection is made.
Page 7
Continue to press the select button until the desired fearture is highlighted. The HRV will then assume the selected mode of operation. Install using 18/2 thermostat wire or telephone wire up to two may be installed per HRV. No electrical box is required. Refer to wiring diagram in this manual.
Page 8
ECPBT1W Control This 20-Minute Touch Pad MUST be connected to the PBT & COM terminals on the HRV exterior. Install using 18/2-thermostat wire or telephone wire. No electrical box is required. Maximum number of ECPBT controls per HRV is six (6). Maximum cumulative lead length is 2000 lineal feet.
Model NW85T/NW125T Illustrated Warm Exhaust Warm Supply Cold Supply Cold Exhaust 1. Selecting a location Typically the HRV is located in the mechanical room with close proximity to an outside wall. Other installation locations are acceptable provided that the ambient air temperature does not fall below freezing.
Page 10
2. Mounting the HRV Included with the HRV are four (4) laminated rubber hanging straps. These are to be secured at each of the four corners of the HRV using the screws provided. The other ends of the straps should be secured to the floor joists using large head screws. To ensure proper condensate flow, HRV must be installed level in both directions.
Page 11
OPTIONAL CONCENTRIC VENT 25-3/16” 20-34” 4-1/2” 1” 16” Step 1 Cut a 6” diameter hole in the exterior wall of the building. The top of the hole should be a minimum of 1” from the bottom of the floor above (if applicable). Step 2 Install the round foam gasket (provided) around the 6”...
Page 12
Seal the backplate with exterior weatherproof sealant and screw into place Step 3 Insert the 6” galvanized duct through the hole cut in the exterior wall. Slide in until the back plate is flush with the exterior wall. Level the backplate and drill 4 holes in the exterior wall.
Page 13
Cut to length as required Securing screw Step 6 Measure from the interior wall to the duct Y transition. Line up the 2 halves of the duct insulator to fit together and using a sharp knife, cut both halves of the duct insulator to the measured distance.
installationClearances • Minimuim 6’ (2m) away from dryer vents, furnace exhaust (medium or high efficiency furnaces), driveways, oil fill pipes, gas meters, or garbage containers • At least 18” (457 mm) above the ground, or above the depth of expected snow accumulation.
Page 15
Weather hoods should be installed: Separate air intake and exhaust outlet openings, when located on the same wall or roof, shall be installed so as to avoid contamination of the ventilation air by the exhaust air. Intake openings shall be located so as to avoid contamination of the ventilation air from other local sources such as automobile exhausts and exhaust from adjacent buildings.
Stale Air 5. installation Methods Exhaust Direct (Simplified) Installation The Direct (Simplified) Installation method Minimum 36" requires that the forced air system circulation fan be operated when the HRV is in use. Fresh Air Supply Please refer to fig. I. safety Warning Some Building Code and Combustion Appliance Installation Codes do not allow...
Page 17
Leaving a gap in the ventilation supply duct in place of the breather ‘T’ is acceptable. In this installation, a grill is placed in the furnace return air duct and the HRV/ERV supply duct is pointed at this grill at a minimum distance of 100mm (4”) but not greater than 300mm (12”).
Stale Air Exhaust indirect partially Dedicated installation This method of installation permits localized Minimum 36" exhaust of indoor air and uses the existing forced air system to distribute fresh air. This method of installation requires that Fresh Air Supply the forced air circulation fan be operated fig.
Fresh air supply grills may be either wall or ceiling mounted. Avoid locating these grills where room occupants may be exposed to the fresh air supply as this air temperature may be slightly less than the room air temperature. Also, it is recommended that adjustable grills such as round “Tech Grills” be used to permit balancing of the ventilation by room application.
Page 20
Clothes dryer off, (if vented to the outdoors) g) Furnace, hot water heater, (non direct vent) are turned off. h) All other exhaust fans are off. Ensure that HRV filters and core are in place and integral balancing dampers are wide open. Power up HRV and set to high speed.
AiR FLOW BALANCiNg READ THE AppLiCATiON WARNiNg AT THE FRONT OF THis MANuAL. upon completion of the installation it is necessary that the Ventilation system be balanced. This is necessary to ensure that the volume of air being exhausted from the dwelling is equal to the volume of air being supplied. Balancing will also ensure that the HRV is operating at it’s maximum efficiency.
Page 22
Fig. 5 MODEL NW85T ONLY AT HigH spEED Refer to the following conversion chart to determine CFM flow. Mag Reading Mag Reading Mag Reading Mag Reading inches Wg inches Wg Equivalent inches Wg inches Wg Equivalent supply Air supply Air Exhaust Air Exhaust Air stream...
Page 23
A positive pressure situation within the dwelling may drive moist air into the external walls where, in cold weather it may condense, potentially causing structural damage. A negative pressure situation within the dwelling may have severe undesirable effects. In some geographic locations, radon gas may be drawn into the living space.
Page 24
Summeraire HRV Air Flow Balancing Models: NW85T/NW125T A. Preliminary Procedures: 1. Seal all the unit’s ductwork with foil tape. 2. Close all windows and doors and fireplace damper, turn off all exhaust devices (range hoods, clothes dryer, bath fan, etc.), make sure all filters are clean.
Page 32
DIGITAL W 20 MIN LED W DEHUMIDISTAT COMMON THERM Y THERM C THERM W RELAY N/O RELAY C RELAY N/C...
Core Summeraire Mfg. warrants the “Core” of the Heat Recovery Ventilator to the original purchaser if the core has become defective by reason of defective material and/or faulty workmanship. This warranty applies to the original purchaser of the Heat Recovery Ventilator for as long as they own the dwelling.
Need help?
Do you have a question about the NUWAVE Series and is the answer not in the manual?
Questions and answers