Centrifugal liquid chillers with graphic control center for electromechanical starter, solid state starter, and variable speed drive. field reassembly for form 3, 7, 9, and form 10 shipment (28 pages)
Centrifugal liquid chillers styles a & b with microcomputer control center part 371-01200-004 for electro-mechanical starter & solid state starter (57 pages)
Form 160.73-O2 (425) Issue Date: 04/24/2025 Important Read before proceeding General safety guidelines This equipment is a relatively complicated apparatus. in which it is situated, as well as severe personal in- During installation, operation, maintenance or service, jury or death to themselves and people at the site. individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized...
Page 4
YK Centrifugal Time-based proactive services Liquid Chillers YORK Proactive Service Guide (Form A variety of factors, including unstable power, extreme 160.76-PSG1). ambient conditions, and chilled water system issues Nomenclature –...
System operation description (See Figure 3) The YORK Model YK MaxE Chiller is commonly ing the keys as labeled on the Control Center. The chiller applied to large air conditioning systems, but may be with the OptiView™ Control Center is compatible with used on other applications.
Description of System and Fundamentals of Operation Form 160.73-O2 (425) Issue Date: 04/24/2025 The major components of a chiller are selected to handle the refrigerant, which would be evaporated at full load design conditions. However, most systems will be called upon to deliver full load capacity for only a relatively small part of the time the unit is in operation.
System Operating Procedures Form 160.73-O2 (425) Issue Date: 04/24/2025 Section 2 - System operating procedures Oil heaters In the oil reservoir If the oil heater is de-energized during a shutdown period, Correct operating oil level – During operation, the oil it must be energized for 12 hours prior to starting com- level should fall to the Operating Range identified on pressor, or remove all oil and recharge compressor with...
Form 160.73-O2 (425) Issue Date: 04/24/2025 2. To start the chiller, press the COMPRESSOR 1. The OptiView Control Center display message will START switch. This switch automatically springs read SYSTEM PRELUBE for the first 50 seconds return to the RUN position. (If the unit was previ- of the starting sequence.
Condenser Water Temperature Control PERATURE setpoint. The Prerotation Vanes are modulated by an actuator under the control of the Mi- The YORK MaxE chiller is designed to use less power croprocessor Board. The vane control routine employs by taking advantage of lower than design temperatures proportional plus derivative (rate) control action.
An optional status printer is available for this purpose unit operating data that is outlined in the log. Use or Figure 7 shows a log sheet used by YORK Personnel this data for the following comparisons: for recording test data on chiller systems. It is available...
Page 14
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment. More frequent service may be required depending on local operating conditions.
• Perform a leak check and repair leaks as needed. YORK District Office. Failure to report constant troubles Refer to Form 50.40-O3. could damage the unit and increase the cost of repairs.
System Operating Procedures Form 160.73-O2 (425) Issue Date: 04/24/2025 Prolonged shutdown 3. On the SETUP Screen, disable the clock. This con- If the chiller is to be shut down for an extended period serves the battery. of time (for example, over the winter season), complete the following steps: 4.
Form 160.73-O2 (425) Issue Date: 04/24/2025 General The YORK Model YK MaxE Centrifugal Liquid Chiller is completely factory-packaged including evaporator, 1. Compressor Drive Shaft (Low Speed) condenser, compressor, motor, lubrication system, a. Shaft seal. OptiView Control Center, and all interconnecting unit b.
Page 21
The compressor motor is an open-drip-proof, squirrel arrangements. Stub-out water nozzle connections with cage, induction type constructed to YORK design spec- Victaulic grooves are welded to the water boxes. These ifications. 60 Hz motors operate at 3570 rpm. 50 Hz nozzle connections are suitable for Victaulic couplings, motors operate at 2975 rpm.
System Components Description Form 160.73-O2 (425) Issue Date: 04/24/2025 While the chiller is shut down, the orifice will be in the Changes in chilled water flow require fully open position causing the sensed level to be ap- readjustment of the hot gas control to proximately 0%.
Form 160.73-O2 (425) Issue Date: 04/24/2025 Section 4 - Operational maintenance 1. Shut the stop valves on the condenser gas line, oil Oil return system return line to rotor support and inlet end of the de- The oil return system continuously maintains the proper hydrator.
The oil should be charged into the oil will keep the concentration of refrigerant in the oil reservoir using the YORK Oil Charging Pump – YORK to a minimum. Part No. 070-10654. To charge oil into the oil reservoir,...
Form 160.73-O2 (425) Issue Date: 04/24/2025 Section 5 - Troubleshooting Table 2: Operational analysis chart RESULTS POSSIBLE CAUSE REMEDY 1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURE Temperature difference between conden- Air in condenser. sing temperature and water off condenser higher than normal. Condenser tubes dirty or Clean condenser tubes.
Page 26
Troubleshooting Form 160.73-O2 (425) Issue Date: 04/24/2025 Table 2: Operation analysis chart, continued RESULTS POSSIBLE CAUSE REMEDY 5. SYMPTOM: UNUSUALLY HIGH OIL PRESSURE DEVELOPS WHEN OIL PUMP RUNS Unusually high oil pressure is displayed High oil pressure. Trans- Replace low or high oil pressure when the oil pressure display key is ducer defective.
Section 6 - Maintenance Renewal parts Megging the motor - mechanical starter For any required Renewal Parts, refer to YORK Renewal While the main disconnect switch and compressor Parts Unit Components Manual 160.73-RP1. motor starter are open, meg the motor as follows: 1.
Maintenance Form 160.73-O2 (425) Issue Date: 04/24/2025 Megging the motor - VFD or solid state 2. Using a megohmmeter (megger), meg between phases starter and each phase to ground. See Figure 12. Use the graph in Figure 14 to interpret these readings. 1.
Page 30
Maintenance Form 160.73-O2 (425) Issue Date: 04/24/2025 Condenser and evaporators Maintenance of condenser and evaporator shells is im- Tube fouling portant to provide trouble free operation of the chiller. Fouling of the tubes can be due to deposits of two types The water side of the tubes in the shell must be kept as follows: clean and free from scale.
If acid cleaning is required, YORK Pressurize the dry system with 50 psig to 100 psig recommends the use of this type of organization. The (345 kPa to 690 kPa) of nitrogen.
Maintenance Form 160.73-O2 (425) Issue Date: 04/24/2025 Compressor Electrical controls Maintenance for the compressor assembly consists For information covering the OptiView Control Center of checking the operation of the oil return system and operation, refer to Form 160.54-O1. changing the dehydrator, checking and changing the oil, checking and changing the oil filters, checking the operation of the oil heater, checking the operation of the oil pump, and observing the operation of the compressor.
IMPORTANT – If a unit failure occurs due to re-lubricate anti-friction bearings periodically. See Table 3. to improper maintenance during the warranty period; YORK will not be liable for costs incurred to return the Table 3: Bearing lubrication system to satisfactory operation. Frame...
The major portion of maintenance on the condenser and (operation and safety) not be changed. If the settings evaporator will deal with the maintaining the water side are changed without YORK’s approval, the warranty of the condenser and evaporator in a clean condition. will be jeopardized.
Page 35
Form 160.73-O2 (425) Issue Date: 04/24/2025 The following factors can be used to convert from Imperial to the most common SI Metric values. Table 5 – SI Metric conversion Measurement Multiply Imperial Unit By Factor To Obtain Metric Unit Capacity Tons Refrigerant Effect (ton) 3.516 Kilowatts (kW)
Need help?
Do you have a question about the YK Series and is the answer not in the manual?
Questions and answers