Ijinus LOG03V4 User Manual

Autonomous logger
Table of Contents

Advertisement

Quick Links

LOG03V4
Autonomous logger
User guide
IJINUS - 25 ZA de Kervidanou 3, 29300 MELLAC - France – SAV / After-sales service : +33 2 98 09 03 32 / sav@ijinus.fr

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LOG03V4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Ijinus LOG03V4

  • Page 1 LOG03V4 Autonomous logger User guide IJINUS - 25 ZA de Kervidanou 3, 29300 MELLAC - France – SAV / After-sales service : +33 2 98 09 03 32 / sav@ijinus.fr...
  • Page 2 User guide: Version 01 Publication date 08/12/2024 Documentation valid for version 7.2 of Avelour software...
  • Page 3: Table Of Contents

    6.2.1. Modbus flowmeter wiring ....................7. Installation  ........................ 7.1. Installing a clamp ........................7.2. Installation with mounting kit ....................7.2.1. Installing a remote antenna ....................8. Configuration on Avelour ..................8.1. Equipment required ....................... 8.2. Installing the Avelour software .................... www.ijinus.com LOG03V4...
  • Page 4 Integration of a logger on THE THINGS ..................8.6.9. Configure an alarm ......................8.6.10. Sending an alert SMS to an operator ................www.ijinus.com LOG03V4...
  • Page 5 9.4.4. Hide the display of data on the graph ................9.4.5. Display values in table form .................... 9.5. Export retrieved data ......................9.6. Delete data recorded on the logger ................... 10. Maintenance  ......................10.1. Replacing the battery ......................10.2. Firmware update ........................ 10.3. Remote firmware update ....................www.ijinus.com LOG03V4...
  • Page 6: Document Information

    1.1. Background This user guide contains all the information required to install, connect and commission the unit, as well as impor- tant notes concerning maintenance. It is therefore essential to read it before commissioning any Ijinus equipment. 1.2. Symbols used This symbol indicates a situation or use that may result in damage, fault or equipment malfunction.
  • Page 7: Chapter 2. Safety

    This document presents a number of operations and programming to be performed on a data logger, a sensor or an accessory supplied by Ijinus. These operations must only be performed by personnel qualified to use Ijinus products. The information provided in this user guide only ensures operational safety if the equipment is used correctly.
  • Page 8: Chapter 3. Product Description

    Chapter 3. Product description 3.1. Principle of operation Ijinus loggers are designed to be standalone units powered by a lithium battery. They log data transmitted by the equipment to which they are connected. A mobile programming unit (M0C00001) or a Wiji USB dongle (WIJIKEY-8) can be used to connect to the logger by radio (Wiji protocol), configure it and retrieve data locally.
  • Page 9: Description

    M12 8-pin connector (B). 3.6 V 34 Ah non- LOG03 data logger rechargeable lithium battery Programming antenna Mounting kit: 2 x mounting plates Remote antenna (optional) + 1 x bracket + 4 nuts and bolts Connection cable (if required) www.ijinus.com LOG03V4...
  • Page 10: Technical Specifications

    -20 to 70°C Sensor material PA12 Ingress protection IP68: 1 bar for 1 month (only if using Ijinus mounting kit; PN: H0T00053 or H0T00060) Power Lithium battery: 3.6 V - 34 Ah Configuration Wireless programming kit (PN: M0C00001) with AVELOUR software, cable and antenna...
  • Page 11: Dimensions

    User guide 3.3.2. Dimensions 63,80 www.ijinus.com LOG03V4...
  • Page 12: M12 8-Pin Connector

      supply 4 - 20 mA 4 - 20 mA Digital Digital drain output (1A/30V) * Maximum 1.8 W on V if the connected sensor is powered by the internal battery (voltage adjustable via soft- ware). www.ijinus.com LOG03V4...
  • Page 13: Chapter 4. Commissioning

    If the logger does not have a communication PCB, there is no need to open the housing as the internal battery is already connected to the PCB. The logger is therefore operational immediately. Ijinus loggers do not require activation, as they listen for a radio connection request from a radio access point or another logger every 10 seconds.
  • Page 14 Check the color of the desiccant bags and replace them if they are green. ● Replace the cover as far as it will go, taking care to fit the insertion notch into the coded hole (B). ● Retighten the clamping ring (A). www.ijinus.com LOG03V4...
  • Page 15: Chapter 5. Power Supply

    Chapter 5. Power supply 5.1. Using a mains power supply Ijinus loggers can be powered from an external mains supply. The voltage delivered to the logger must be between 8 V and 30 V. You must use a transformer (e.g. 220 V / 24 V) that is correctly grounded. In the absence of a ground connection, several malfunctions may occur (metering problems, measurement disturbances, etc.)
  • Page 16: Chapter 6. Connections

    Current 1 Current 2 Contact * (internal Grounding battery) or Switch Vout = Vin Type Power Power Modbus Modbus 4 - 20 mA 4 - 20 mA Open supply in- supply drain (1 A / output 30 V) www.ijinus.com LOG03V4...
  • Page 17: Modbus Flowmeter Wiring

    * Maximum 1.8 W on V if the connected sensor is powered by the internal battery (voltage adjustable via soft- ware) 6.2.1. Modbus flowmeter wiring For correct operation of the flowmeter in MODBUS mode, you need to connect the ground wire. www.ijinus.com LOG03V4...
  • Page 18: Chapter 7. Installation

    Chapter 7. Installation 7.1. Installing a clamp To fit the Ijinus clamp: ● Position the clamp so that the Ijinus logo is aligned with the logger logo. ● To remove the clamp, insert a screwdriver into the notch (A) and pry the clamp loose.
  • Page 19 User guide Assembled kit version 1 Assembled kit version 2 Example of installation with a mounting plate Example of installation with two mounting plates www.ijinus.com LOG03V4...
  • Page 20: Installing A Remote Antenna

    The use of a remote antenna is useful if the logger is installed in a manhole with a buffer. In this case, connection to the logger may not be possible. You must use an Ijinus remote antenna. Three lengths are available as standard: 1, 3 or 5m. In exceptional cases, a length of 10m may be proposed.
  • Page 21 User guide ● Test positioning and data transmission using the Avelour software. This test should be carried out before and after installation (closed plug in the case of a manhole). Drilling into the manhole Inserting antenna under the base www.ijinus.com LOG03V4...
  • Page 22: Chapter 8. Configuration On Avelour

    A Wiji radio antenna in “long range” or “USB device” format. 8.2. Installing the Avelour software www.ijinus.com The Avelour software can be downloaded from the Ijinus website ( ) in the “Download” section. ● To install it in the background, open the Avelour software via the command line interface using space + / S after its name.
  • Page 23 User guide Location of serial number -> The logger configuration window opens. Configuration window for logger S/N: IJA0102-00002718 -> A configuration file is automatically created. -> A folder is created in the following directory:  C:\ProgramData\Ijinus\Avelour_Main_7.1.2\SavedSen- sors\IJA0102-00002718 www.ijinus.com LOG03V4...
  • Page 24: General Information About Measurement Configuration

    The OVERFLOW detector takes into account elements in physical contact with the housing and up to a few centimeters away from it. The detector is highly insensitive to fouling. It is possible to adjust the overflow recording threshold to take account of restrictive external conditions in particularly congested networks. www.ijinus.com LOG03V4...
  • Page 25: Configuration

    Cumulate the time spent in overflow all the: Define a recording frequency for cumulative time spent in overflow. External sensor acceleration on overflow (advanced parameter) Configuration summary To view the configuration summary: Click  to display a summary of the configuration. ● www.ijinus.com LOG03V4...
  • Page 26: Measurement Via Di/Co Input

    By default, when the logger's memory is full, data is deleted in chronological order of recording, from oldest to most recent. ● If Fifo memory is disabled, define a maximum number of timestamps. Configuration summary To view the configuration summary: ● Click  to display a summary of the configuration. www.ijinus.com LOG03V4...
  • Page 27: Timestamping Bucket Rain Gauge Tips

    If Fifo memory is disabled, change the maximum number of timestamps for the main memory (used for sending data via Internet) and the auxiliary memory (used for sending data via SMS) if necessary. Configuration summary To view the configuration summary: ● Click to display a summary of the configuration. www.ijinus.com LOG03V4...
  • Page 28: Measurement Using The Modbus Protocol : Slave Mode

    A document can be displayed by clicking on the "More information here" link. This document, called "Modbus Tables", describes the address, offset, size and encoding (integer, inverted integer, etc.) for each item of data measured by an Ijinus logger. www.ijinus.com...
  • Page 29 Click on the "View resume" button to display the summary of the recording configuration. Depending on the settings selected, the remaining recording time before the memory is full is given as well as an average of the number of sms sent per day. www.ijinus.com LOG03V4...
  • Page 30: Rainfall Measurement

    Principle The purpose of this application is to be able to use a rain gauge connected to an Ijinus logger with a digital input. It is possible to connect many different brands of tipping bucket rain gauges provided that it is equipped with an output signal based on the closure of a "normally open"...
  • Page 31 Depending on the selected settings, the remaining recording time before the memory is full is shown, as well as an average of the number of SMS text messages sent per day. www.ijinus.com LOG03V4...
  • Page 32: Measurement For Pump Station Management

    (P1 and P2 com- bined) Period 'volume[0]' (m 'volume[1]' (m 'volume[2]' (m 'volume[3]' (m ). Q1 ( t' + t' ). Q volume[0] + t' ). Q1 + t'') . Q1 ( t' + t''). Q t'' . Q volume[1] volume[2] www.ijinus.com LOG03V4...
  • Page 33: Configuration

    Pulse generation on pump start, pump operating time or volume transited in the pump station Wiring Pulse output device choice of "Open-drain output" or "Direct external supply" voice (see paragraph) Specified pump : Pump 1, Pump 2 or any pump. www.ijinus.com LOG03V4...
  • Page 34 Pulse duration (ms) : 500 ms by default Information ● Enter nominal flow rates for pump 1, pump 2 and operating together. Configuration summary To view the configuration summary: ● Click to display a summary of the configuration. www.ijinus.com LOG03V4...
  • Page 35: Measurement With A 4-20 Ma Piezoresistive Sensor + External Speed Sensor

    This measure is used to configure data retrieval from a piezoresistive sensor to a data logger via a 4-20 mA signal. Configuration Connecting to Prerequisites: In Avelour, the Wiji connection to the logger must be established, see a logger ● Click to add a measurement configuration and select "Piezo 4-20mA + external velocity -> flow". www.ijinus.com LOG03V4...
  • Page 36 The default value has been set at 250 ms, as this period is used to power the 4-20 mA piezometers sold by Ijinus. For the inclinometer sold by Ijinus, the minimum power supply period is 500 ms. First 4-20 mA channel ●...
  • Page 37 Sampler enslaving If a height / flow relationship and an "infinite" volume calculation have been entered, then it is possible to acti- vate  the transmission of pulses to a sampler connected to an Ijinus logger. ● Select the pulse output device.
  • Page 38 If required, select the recording channel (between 0 and 15 ) and the logged event ID (20 = overflow or 0 = Boolean). Fifo Memory (Advanced Setting) By default, when the logger memory is full, data are deleted in chronological order of recording, from oldest to newest. www.ijinus.com LOG03V4...
  • Page 39 Click to display a summary of the configuration. Depending on the settings selected, the remaining recording time before the memory is full is given, as well as an average of the number of text messages sent per day. www.ijinus.com LOG03V4...
  • Page 40: Measurement Via 4-20 Ma Input

    Whether the sensor is powered by the internal battery or via an external battery, it is essential to determine the power supply duration. This is the time during which the sensor will be powered by the logger before measuring the 4-20 mA signal emitted by the external sensor. www.ijinus.com LOG03V4...
  • Page 41 The default value has been set at 250 ms, as this period is used to power the 4-20 mA piezometers sold by Ijinus. For the inclinometer sold by Ijinus, the minimum power supply period is 500 ms. First 4-20 mA channel ●...
  • Page 42 4-20 mA signal into water height is presented below. Example of water height conversion In the example below, the 4-20 mA sensor is a 0-10 m (10,000 mm) range piezometer. www.ijinus.com LOG03V4...
  • Page 43 Sampler enslaving If a height / flow relationship and an "infinite" volume calculation have been entered, then it is possible to acti- vate  the transmission of pulses to a sampler connected to an Ijinus logger. ● Select the pulse output device.
  • Page 44 ) for the first 4-20 mA sensor. Set threshold 1 In this example, the threshold is based on the conversion of channel 1 to "rising edge" for the direction. The delay can also be set for activation and/or deactivation. www.ijinus.com LOG03V4...
  • Page 45 Click to display a summary of the configuration. Depending on the settings selected, the remaining recording time before the memory is full is given, as well as an average of the number of text messages sent per day. www.ijinus.com LOG03V4...
  • Page 46: Configure Sending Of Recorded Data

    Poor signal quality + 113 dBm No communication possible 8.6.3. Configuring the communication PCB modem Prerequisites: A SIM card with a “voice” or SMS message package must be inserted into the holder. Inserting a SIM card See paragraph parameters. www.ijinus.com LOG03V4...
  • Page 47 User guide Before being able to send data by SMS or M2M, you must configure the modem on the communication board. ● In the “Data sending” block, click “EDIT". -> The data transmission parameter editing window is displayed. www.ijinus.com LOG03V4...
  • Page 48: Technology To Use

    Activate  the parameter to enter values in empty fields. Priority operator (Multi-operator SIM) Firmware update This feature requires a firmware update (22.1 or later). Refer to paragraph  This feature can only be used with a multi-operator SIM card. www.ijinus.com LOG03V4...
  • Page 49: Program Modem

    -> If the programming did not occur correctly, a window opens to indicate the problem encountered (SIM card absent, incorrect PIN code, etc.) ● Each time a parameter is modified (e.g. change of technology), click on the “1: Program modem” button. www.ijinus.com LOG03V4...
  • Page 50: Check Network Quality: Modem Diagnostics

    If the result is as shown above, it means that no signal has been located. ● Click the "Launch an immediate diagnostic" button to give the modem more time to detect a network. In less than a minute, a satisfactory result should appear as indicated below: www.ijinus.com LOG03V4...
  • Page 51: Data Transmission Via Internet

    When purchasing a SIM card, ask for the operator's APN and PIN code, if available, as this information will be needed. ● Connect the GSM / GPRS antenna to the connector on top of the logger. ● In Avelour, activate  Internet data sending: FTP / CoAP www.ijinus.com LOG03V4...
  • Page 52 Server name or IP address: "Server” • User name for server access: "Username” • The password associated with the specified user: "Password” ● Click on the  Force sending of data FTP button to check that data transmission is working correctly. www.ijinus.com LOG03V4...
  • Page 53 User guide -> If data is transmitted, the following window appears: ● After a few minutes, check that the data has arrived on the Ijitrack account or on a different Ijitrack server. www.ijinus.com LOG03V4...
  • Page 54: Data Transmission In Http(S)

    Uri : Enter the uri of the http request. Not available for ijinus format with files.ijitrack.com server. ● User name : In Ijinus format. If needed. It will be included in the body of the request in the user form. It is useful when sending to Ijinus servers.
  • Page 55 Authentication token : Enter the Authorization token, if required. Will be included in the request body in the Authorization header. ● Timeout :  Enter a http request timeout in seconds. ● * Custom headers*: In Ijinus format. Enables custom headers. • Key : Enter the key of the header to add. • Value : Enter its value.
  • Page 56 For sensor configuration in TOPKAPI, refer to TOPKAPI documentation. Azure Iot HUb format For preformatted transmission to Azure IoT Hub. The uri is preconfigured in the correct format: /devices/$ID/messages/events?api-version=2021-04-12 Request header: Header Authorization 58d97-32fb3 The body is in the format '' { "payload":"base64:sdip<gs5fsd465ggsgs" } www.ijinus.com LOG03V4...
  • Page 57: Data Transmission Via Sms

    ● If data are sent to the Ijitrack web service, no modification is required. ● If data are sent to another supervision system, contact the person in charge of supervision to define the correct SMS Site ID. www.ijinus.com LOG03V4...
  • Page 58: Data Transmission Via Lorawan

    AppKey : Key used by the server and end device to encrypt and decrypt packet data. DevAddr : Identity of the end equipment (32 bits). Test data transmission ● Click “Send information message” to send a message containing diagnostic information ● Click “Send data message” to send a message containing measurement data. www.ijinus.com LOG03V4...
  • Page 59: Advanced Settings

    On : External antenna Off : Internal antenna Integration of a logger on Orange Live objects ● Select the “Generic_classA_RX2SF12” profile. ● Copy and paste the identifier (DeveUI) and the keys (AppKey and AppUI) from the data provided in Avelour. www.ijinus.com LOG03V4...
  • Page 60: Integration Of A Logger On Wiotys

    Select “Enter end device specifics manually” ● Fill in the Frequency plan, LoRaWAN version and Regional Parameters fields as shown below: ● Copy and paste the identifier (deveUI) and the keys (appKey (= joinEui) and appUI) from the data provided in Avelour. www.ijinus.com LOG03V4...
  • Page 61: Configure An Alarm

    The SIM card must allow sending of SMS text messages. Sending an alert SMS only works if a threshold is exceeded and Anticipate data sending is active. ● Enter a phone number in the “Send alert SMS” window. www.ijinus.com LOG03V4...
  • Page 62 User guide If data is sent using FTP, approximately 3 minutes elapses between the time that the threshold is exceeded and the message is received. www.ijinus.com LOG03V4...
  • Page 63: Power Supply Configuration

    The logger collects the voltage data from the external power supply and stops measurements if a minimum voltage threshold is reached. This threshold depends on the type of external power supply and the rated voltage. Examples of thresholds: ● 12 V lead-acid battery: 12 x 0.875 = 10.5V. www.ijinus.com LOG03V4...
  • Page 64: Set Time Zone

    5 m). The "master" logger then retrieves data from a "slave" logger. This option is called pairing and is configured in the "master" logger. No settings are required on the slave logger. In the "Retrieve devices" block: ● Click "EDIT". www.ijinus.com LOG03V4...
  • Page 65: Check The Status Of Data Recording And Transmission

    In the configuration window, two icons allow you to control the status of data recording and transmission. A : Current status B : Status after loading the configuration on the logger, useful information to check if the configuration being edited is correctly configured. www.ijinus.com LOG03V4...
  • Page 66: Save The Configuration To The Logger

    8.11. Save the configuration to the logger Connecting to a logger Prerequisites: The logger is connected to Avelour (see To save all the settings configured on the logger: ● Click “SEND CONFIGURATION”. -> An update loading window is displayed. www.ijinus.com LOG03V4...
  • Page 67: Visualize Measured Values In Real Time

    8.12. Visualize measured values in real time The logger is set up for measurement. To visualize the values measured and received by radio from the Ijinus loggers located nearby: ● In the windows tab, click on “View measurements received in RF”.
  • Page 68: Disconnect From The Logger

    Double-click the configuration file to display it in the main window. 8.15.2. Archive a file Archiving allows you to manage how files are displayed in the saved data window. In the Saved data window: ● Right-click on the configuration file to archive and click "Archive selected elements". www.ijinus.com LOG03V4...
  • Page 69: Create A Configuration Template

    Check the "Configuration to apply by default on a new sensor" option so that the template is applied auto- matically when connecting a new logger. ● Enter a name and click "OK". -> An .IJCZ file is created in the following directory: C:\ProgramData/Ijinus/Avelou_Main_7.xxxxx/userTem- plates. -> The new template is available in the “Edit” menu. www.ijinus.com...
  • Page 70: Apply A Configuration Template

    Create a configuration template A configuration template must be created. See Connecting to a logger ● Connect to the logger that you wish to apply a template to (see ● In the "Edit" menu, click on the template to apply. www.ijinus.com LOG03V4...
  • Page 71: Chapter 9. Data Management On Avelour

    Click "Retrieve without deleting" to keep the data in memory in the logger or "Retrieve and delete" to empty the recorder memory. ● In the "Actions" menu, click on retrieve measures. -> The saved data display window opens. www.ijinus.com LOG03V4...
  • Page 72: Retrieve Data From Auxiliary Memory

    Data transmitted via FTP are stored in the main memory. To retrieve data locally with a logger configured to send data in M2M: ● In the main Actions menu, click on Auxiliary measures (for SMS) > Retrieve measures. www.ijinus.com LOG03V4...
  • Page 73 User guide -> In the saved data window, the data retrieved appears in the browser structure. www.ijinus.com LOG03V4...
  • Page 74: Create A New Calculated Value

    Edit window for a new calculated value - Calculation of the average daily temperature value ● Define contextual parameters based on the type of filter selected. ● Click “Save and show” to display the calculated value. -> The calculated value appears in the saved data browser structure. www.ijinus.com LOG03V4...
  • Page 75: Data Graph

    Used to export the graph as a PNG image. X-axis Zoom cursor. 9.4.2. Show data graph In the Saved data window: ● Double-click on the data or select multiple data elements, right-click and click "View" to view the data as a graph. www.ijinus.com LOG03V4...
  • Page 76: Customize The Graph Display

    User guide -> The saved data viewing window opens. 9.4.3. Customize the graph display In the saved data viewing window: ● Click the configuration button to display the graph display properties editing window. Graph configuration window www.ijinus.com LOG03V4...
  • Page 77: Hide The Display Of Data On The Graph

    9.4.5. Display values in table form In the saved data viewing window: ● Click the “Show data table” button. -> Data are displayed below the graph. www.ijinus.com LOG03V4...
  • Page 78 User guide Data table www.ijinus.com LOG03V4...
  • Page 79: Export Retrieved Data

    Select the export type, the period and the export destination directory. 9.6. Delete data recorded on the logger To delete data recorded on the logger memories: ● In the "Actions" menu, click "delete measures" to delete the main memory of the logger. www.ijinus.com LOG03V4...
  • Page 80 In the "Actions" menu, click "delete measures" in the sub-menu "Auxiliary measures (for SMS)" to delete the auxiliary memory. When connecting to a logger, if data is present, it is then possible to retrieve and delete data. The deleted data will then be that of the main memory. www.ijinus.com LOG03V4...
  • Page 81: Chapter 10. Maintenance

    User guide Chapter 10. Maintenance In the event of a problem with an Ijinus logger or sensor, we recommend that you contact our after-sales depart- sav@ijinus.fr ment either by e-mail: or by telephone: +33 (0)298 090 332 You will be informed of the applicable procedure, so that you can either test the product yourself or return it to the factory for testing on our premises.
  • Page 82 Connect to the logger (see paragraph ● In the actions menu, click on "report battery change" to restart the logger and return the energy gauge to 0. -> In the device properties window, the battery gauge changes to 0. www.ijinus.com LOG03V4...
  • Page 83: Firmware Update

    By connecting to the logger in advance, the choice of device (1) is already made. To change this choice, click “Device choice”. ● In the list of actions to launch (2), select “Upgrade the device firmware”. ● Click “Choose firmware”. -> The Firmware folder opens. ● Select the corresponding .xbin file and click “Launch the action” (3). www.ijinus.com LOG03V4...
  • Page 84: Remote Firmware Update

    10.3. Remote firmware update The logger must be equipped with a modem card and configured to send data via FTP. If you are using the ijitrak server, contact Ijinus to obtain the identifiers and password and configure Avelour If using another server, contact Ijinus to obtain a version of Avelour enabling you to customize the server configuration.