Page 3
Earth Resistance Tester Statement In accordance with international copyright law, nothing in this instruction manual may be reproduced in any form (including storage and retrieval or translation into other national or regional languages) without permission and written consent. If there are any changes in the future version of this instruction manual, no further notice will be given.
Earth Resistance Tester Safety information This instrument can only be installed and operated by qualified personnel in accordance with the following safety precautions, specifications and technical data. At the same time, the use of this instrument requires compliance with all laws and safety regulations related to varieties of specific applications.
Page 5
Earth Resistance Tester ⚫ Do not install replacement parts on the meter or modify the meter. If the instrument is damaged, return it to your local dealer for servicing. ⚫ Please turn the rotary switch to the 'shutdown' position and remove the test lead before you can open the battery cover to replace the battery.
Page 6
Earth Resistance Tester are two measurement modes: two-pole method and three-pole method. It can also measure the earth voltage. The instrument uses a large liquid crystal digital display with a backlight, which is easy for the user to read. It has data storage function, which can store 100 sets of measurement data, and the data will not be lost when power is lost, which can be convenient for users to make historical data inquiry.
Page 7
Earth Resistance Tester Meter panel description ① Rotary switch It can control power switches. It is also used to select between the measurement of earth voltage, measurement of resistance in Bi-pole method or measurement of resistance in Tri-pole method. ② Key of REL It is used not only for the selection of relative measurement functions, but also for the down-flip operation when reading data.
Page 8
Earth Resistance Tester ③ Key of LIGHT It is not only used to control the switch of backlight but also used to flip up operation when reading data. ④ Key of MAX/MIN/AVG It is used to switch between the measurement of maximum, minimum and average. ⑤...
Earth Resistance Tester ⑯ C/H socket It is used to connect with the auxiliary grounding pole. Display description ① Simulation bar ② Display of data obtained ③ Display of memory used for data storage. Display symbol description: >LIMIT: Limit has been exceeded TEST: Measurement markers MAX: Maximum MIN: Minimum...
Page 10
Earth Resistance Tester READ: Data Reading MEMO: Data Storage USED: There are data in memories. 2POLE: Bi-pole method is being used for measurement of resistance 3POLE: Ti-pole method is being used for measurement of resistance KΩ: Volts (voltage) Kilohm (unit of resistance) AC symbols Battery is low with the symbol on For warnings and cautions...
Page 11
Earth Resistance Tester lead is connected in parallel to the voltage source or load terminals for measurement and the voltage value is displayed on the LCD screen. Earth resistance measurement by Bi-pole method (simple measurements) This method does not use the measurement method of auxiliary grounding rod. The existing grounding electrode with known minimum grounding resistance is used as auxiliary grounding electrode, such as metal buried pipes, common grounding of commercial power supply or building lightning rod as auxiliary grounding electrode.
Page 12
Earth Resistance Tester (2) Measurement of the earth resistance Turn the rotary switch to the "Bi-pole method" position, connect the meter to the measured device as shown above, press the 'Measure' key to start measurement, the 'Measure' key light will light up and flash, the buzzer will sound after the measurement stops automatically, and the "Measure"...
Page 13
Earth Resistance Tester resistance of the auxiliary ground rod is too large, and the current cannot flow through the instrument. (3) Calculating earth resistance values The measured value Re is the sum of the earth resistance value re of the auxiliary grounding electrode and the true earth resistance value Rx, so the measured value Re minus the value re is the true earth resistance value Rx: Rx (earth resistance value) = Re (measured value) - re (earth resistance value of the auxiliary grounding electrode).
Page 14
Earth Resistance Tester rod and C auxiliary grounding rod. The rotary switch is rotated to the 'Tri-pole method' position, and the measurement is started by pressing the 'Measure' key. The 'Measure' key light is lit and flickered. After the measurement is automatically stopped, the buzzer rings and the 'Measure' key light is extinguished.
Page 15
Earth Resistance Tester Note: Please insert the auxiliary grounding rod into the moist soil as far as possible. If you must insert dry soil, stone or sand, please wet the part inserted by the auxiliary grounding rod with water to keep the soil moist. When measuring on concrete, please level the auxiliary grounding rod, shower water or put wet towels on the auxiliary grounding rod.
Page 16
Earth Resistance Tester (2)Briefly press the " " or " " key to flip up or down the data. (3)In the read mode, press the 'READ' key to exit the read mode. Data deletion The meter can delete the data in the read mode. Briefly press the 'CLR' key to delete the data at the current position.
Earth Resistance Tester (3)In the AVG measurement mode, the average value of the measurement results is displayed during the measurement process. Backlight Press the ' ' backlight key to turn the backlight on or off. Auto shutdown The meter defaults to turn on the automatic shutdown function. Press and hold the ' ' key and turn the rotary switch to turn on the power to turn off the automatic sleep mode.
Earth Resistance Tester Size ⚫ : 118mm X 145mm X 73mm ⚫ Weight: approx.0.6kg (Batteries and accessories not included) ⚫ Accessories: 3 test leads (one 20-meter-long red lead, one 10-meter-long green lead and one 2-meter-long black lead), 2 auxiliary earth bars Technical specifications Accuracy: ±...
Earth Resistance Tester Battery replacement Warning Never replace the batteries while the meter is damp. Never replace the batteries while the meter is being used. Switch off the meter and disconnect the test leads and earth rods before replacements to avoid electrical shock. Caution Never mingle new batteries with old ones.
Need help?
Do you have a question about the MT-4105 and is the answer not in the manual?